Manuel d’utilisation York B5CH 036

24 pages 0.6 mb
Télécharger

Aller à la page of 24

Summary
  • York B5CH 036 - page 1

    DESCRIPTION YORK Sunline 2000 Heat Pumps are convertible single package units with a common cabinet and common roof curb for the 3, 4 and 5 ton sizes. The units were designed for residential and light commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame. All units are self--contained and assembled on rigid ...

  • York B5CH 036 - page 2

    SYSTEM PROTECTION -- Crankcase heaters and internal compressor protection are standard on all compressors. Every unit has a liquid line filter--drier , low pressure switch, high pressure switch and high temperature switch to protect all system components. A suction line freezestat is supplied on all three--phase units to protect against loss of cha ...

  • York B5CH 036 - page 3

    036-21564-002-A-0404 Unitary Products Group 3 MODELS BCH 036 048 060 SUPPL Y AIR BLOWER CENTRIFUGAL BLOWER (Dia. x Wd. in.) 12 x 10 12 x 10 12 x 10 F AN MOTOR HP (DIRECT -DRIVE) 1 F AN MOTOR HP (BEL T -DRIVE) 1.5 1.5 1.5 INDOOR COIL ROWS DEEP 4 3 3 FINS PER INCH 16 15 15 F ACE AREA (Sq. Ft.) 4.3 5.1 5.1 OUTDOOR FA N PROPELLER DIA. (in.) 22 22 24 F ...

  • York B5CH 036 - page 4

    036-21564-002-A-0404 4 Unitary Products Group COOLING CAP ACITIES - 3 TON (BCH036) Air On Indoor Coil T emperature of Air on Outdoor Coil 85 ° F9 5 ° F To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH CFM WB ° F Entering Dry Bulb, ° F Entering Dry Bulb, ° F 86 83 80 7 ...

  • York B5CH 036 - page 5

    036-21564-002-A-0404 Unitary Products Group 5 COOLING CAP ACITIES - 4 TON (BCH048) Air On Indoor Coil T emperature of Air on Outdoor Coil 85 ° F9 5 ° F To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH CFM WB ° F Entering Dry Bulb, ° F Entering Dry Bulb, ° F 86 83 80 7 ...

  • York B5CH 036 - page 6

    036-21564-002-A-0404 6 Unitary Products Group COOLING CAP ACITIES - 5 TON (BCH060) Air On Indoor Coil T emperature of Air on Outdoor Coil 85 ° F9 5 ° F To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH To t a l Cap. 1 MBH Power Input 2 KW Sensible Capacity 1 , MBH CFM WB ° F Entering Dry Bulb, ° F Entering Dry Bulb, ° F 86 83 80 7 ...

  • York B5CH 036 - page 7

    036-21564-002-A-0404 Unitary Products Group 7 HEA TING CAP ACITIES BCH036 CFM RET . AIR CAP OUTDOOR AIR TEMPERATURE, ° F (72% RH) ° F & K W - 1 0 0 1 02 03 04 05 06 0 1750 55 MBH 13.1 16.4 23.5 29.1 30.2 41.7 47.0 48.2 KW 2.9 3.0 3.2 3.3 3.5 3.7 3.8 3.9 70 MBH 1 1.9 15.0 21.5 26.7 27.7 38.2 43.1 44.1 KW 3.0 3.1 3.4 3.4 3.6 3.8 3.9 4.1 80 MBH ...

  • York B5CH 036 - page 8

    036-21564-002-A-0404 8 Unitary Products Group SUPPL Y AIR BLOWER PERFORMANCE - BCH036 & 048 with Belt-Drive MODEL BCH AIR FLOW CFM Available External S tatic Pressure - IWG* 0.20 0.30 0.40 0.50 0.60 0.70 0.80 RPM W atts RPM W atts RPM W atts RPM Watt s RPM W atts RPM W atts RPM W atts 048 2000 843 860 880 925 919 1005 956 1065 993 1 145 1030 1 ...

  • York B5CH 036 - page 9

    036-21564-002-A-0404 Unitary Products Group 9 SUPPL Y AIR BLOWER PERFORMANCE - BCH036, 048 & 060 with Direct-Drive SUPPL Y AIR BLOWER PERFORMANCE - BCH060 with Belt-Drive MODEL BCH AIR FLOW CFM Available External S tatic Pressure - IWG* 0.20 0.30 0.40 0.50 0.60 0.70 0.80 RPM W atts RPM W atts RPM W atts RPM Watt s RPM W atts RPM W atts RPM W at ...

  • York B5CH 036 - page 10

    036-21564-002-A-0404 10 Unitary Products Group HEA TER / CFM LIMIT ATIONS HEA TER SIZE NOM. KW VOL TAGE 1 UNIT MODEL SIZE, NOMINAL TONS 345 MINIMUM SUPPL Y AIR CFM 5 7 10 15 20 30 208 / 230-1-60 1,100 1,100 1,200 1,200 1,300 2 - 1,300 1,300 1,300 1,300 1,300 2 - 1,600 1,600 1,600 1,600 1,600 1,600 5 7 10 15 20 30 208 / 230-3-60 1,100 1,100 1,200 1, ...

  • York B5CH 036 - page 11

    036-21564-002-A-0404 Unitary Products Group 11 ELECTRICAL DA T A - Basic Unit (Direct-Drive) MODEL BCH POWER SUP - PL Y VOL TAGE LIMIT ATIONS (SEE NOTE 1) COMPRESSOR OUTDOOR FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, (SEE NOTE 2) AMPS MAX. HACR BREAKER SIZE, AMPS MIN. MAX. RLA LRA 036 208/230-1-60 208/23 ...

  • York B5CH 036 - page 12

    036-21564-002-A-0404 12 Unitary Products Group MODEL BCH POWER SUPPL Y HEA TER ACCESSORY MODEL NUMBER SUPPL Y AIR BLOWER MOTOR FLA ELECTRIC HEA TERS MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE 1 AMPS MAX. SIZE HACR 2 BREAKER AMPS KW ST AGES TO T AL AMPS 048 208-1-60 2CE04500506 2CE04500706 2CE04501006 2CE04501506 2CE04502006 5.0 4.0 5.6 8.0 1 1.9 15.9 ...

  • York B5CH 036 - page 13

    036-21564-002-A-0404 Unitary Products Group 13 ELECTRICAL DA T A - Basic Unit (Belt-Drive) MODEL BCH POWER SUP - PL Y VOL TAGE LIMIT ATIONS (SEE NOTE 1) COMPRESSOR OUTDOOR FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, (SEE NOTE 2) AMPS MAX. HACR BREAKER SIZE, AMPS MIN. MAX. RLA LRA 036 208/230-1-60 208/230- ...

  • York B5CH 036 - page 14

    036-21564-002-A-0404 14 Unitary Products Group MODEL BCH POWER SUPPL Y HEA TER ACCESSORY MODEL NUMBER SUPPL Y AIR BLOWER MOTOR FLA ELECTRIC HEA TERS MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE 1 AMPS MAX. SIZE HACR 2 BREAKER AMPS KW ST AGES TO T AL AMPS 048 208-1-60 2CE04500525* 2CE04500725* 2CE04501025 2CE04501525 2CE04502025 8.6 4.0 5.6 8.0 1 1.9 15 ...

  • York B5CH 036 - page 15

    036-21564-002-A-0404 Unitary Products Group 15 CLEARANCES Front 24" Back 12" (Less Economizer) 36" (With Economizer or Fixed Air/Motorized Air Damper) Left Side (Filter Access) 24" (Less Economizer) 36" (With Economizer) Right Side (OD Coil) 24" Below Unit 1 2 0" Above Unit 2 72" (For Outdoor Air Discharge) N ...

  • York B5CH 036 - page 16

    036-21564-002-A-0404 16 Unitary Products Group UNIT DIMENSIONS - CONT'D. (BCH - 3, 4 & 5 TON) REAR VIEW SIDE SUPPL Y AND RETURN AIR DUCT OPENINGS 3 DUCT COVERS - Units are shipped with all air duct openings covered. For side duct applications; 1.Remove and discard the supply and return air duct covers. 2.Connect ductwork to duct flanges on ...

  • York B5CH 036 - page 17

    036-21564-002-A-0404 Unitary Products Group 17 ROOF CURB DIMENSIONS BCH - 3, 4 & 5 TON COMPRESSOR AND OUTDOOR COIL END OF UNIT DUCT SIZES: Supply Air = 19" x 19" Return Air = 19" x 19" BACK APPROXIMA TE CENTER OF GRA VITY FRONT CENTER OF GRA VITY CORNER CORNER CORNER OPTIONS / ACCESSORIES Electric Heat (Nominal KW) 5 - 7 KW ...

  • York B5CH 036 - page 18

    FIELD--INST ALLED ACCESSORIES SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZER -- Includes a slide--in/plug--in damper assembly with fully modulating spring return motor actuator capable of introducing up to 100% outdoor air , one outdoor air electronic enthalpy sensor and a rainhood with filters. The rainhood is painted to match the basic unit and must ...

  • York B5CH 036 - page 19

    036-21564-002-A-0404 Unitary Products Group 19 TYPICAL APPLICATIONS TYPICAL ROOF-TOP INST ALLA TION ROOF JACK INST ALLA TION ROOF CURB INST ALLA TION SLAB ON GROUND INST ALLA TION FIELD-SUPPLIED DISCONNECT SWITCH TO POWER SUPPL Y CONTROL WIRING TO INDOOR THERMOST A T ROOF CURB SUPPL Y AIR DUCT RETURN AIR DUCT CONDENSA TE TRAP ...

  • York B5CH 036 - page 20

    GENERAL DESCRIPTION Units shall be factory--assembled, single packaged Heat Pumps, designed for outdoor mounted inst allation. Units shall have minimum SEER ratings of 10.0. They shall have built in field convertible duct connections for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed opti ...

  • York B5CH 036 - page 21

    (1) -- Loss--of--charge/Low--pressure switch. (2) -- High--pressure switch. If any of the above safety devices trip, an LED (light emitting diode) indicator shall illuminate. C. Unit shall incorporate “AUTO RESET” compressor over--temperature, over--current protection. D. Unit shall operate with conventional thermostat designs and have a low vo ...

  • York B5CH 036 - page 22

    6. THERMOST A TS -- Multiple models available from A.C.O., M.C.O., Electronic or Electrical Mechanical ver - sions. 7. ANTI--RECYCLE TIMER -- Assures 5--minute off--time between compressor cycles. 8. ELECTRIC HEA T -- Slide--in design, provides single point power and ranges from 5 to 30 KW . OTHER F ACTOR Y INST ALLED OPTIONS 1. HIGH PERFORMANCE BE ...

  • York B5CH 036 - page 23

    036-21564-002-A-0404 Unitary Products Group 23 ...

  • York B5CH 036 - page 24

    Unitary Products Group 5005 Y ork Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A. 035-21564-002-A-0404 Copyright 2004 by Y ork International Corporation. All Rights Reserved. Supersedes: 036-21564-001-A-0204 ...

Fabricant York Catégorie Heat Pump

Les documents que nous recevons du fabricant de l'appareilYork B5CH 036 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques York
- manuels d’utilisations B5CH 036
- fiches produit York
- dépliants
- ou étiquettes-énergie York B5CH 036
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation York B5CH 036.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation York B5CH 036, manuels d’entretien, brefs manuels ou manuels de l’utilisateur York B5CH 036. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit York B5CH 036.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil York B5CH 036, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser York B5CH 036 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs York B5CH 036.

Le manuel d’utilisation complet York, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel York B5CH 036 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières York B5CH 036, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lYork B5CH 036 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil York B5CH 036 - qui devraient nous aider dans les premières étapes lors de l'utilisation York B5CH 036
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de York B5CH 036
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service York B5CH 036 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de York B5CH 036?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec York B5CH 036, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec York B5CH 036 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)