Manuel d’utilisation AquaStar 125B LPL

20 pages 0.46 mb
Télécharger

Aller à la page of 20

Summary
  • AquaStar 125B LPL - page 1

    W ARNING : Improper inst allation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer , service agency or the gas supplier . Upon completion of the installation, these instructions should be handed to the user of the applian ...

  • AquaStar 125B LPL - page 2

    2 This well engineered, gas water heater has been specially designed to operate as a circulating water heater . FEA TURES - High Quality Materials for Long Working Life. - Copper heating coils for endless supply of hot water . - Safety thermocouple at pilot burner . - Automatic overheating protection shut-off sensor . - Stainless steel burners with ...

  • AquaStar 125B LPL - page 3

    3 D861_059 MINIMUM INST ALLA TION CLEARANCES FROM COMBUSTIBLE AND NON COMBUSTIBLE MA TERIALS FOR ALCOVE OR CLOSET INST ALLA TIONS FRONT VIEW SIDE VIEW AQUAST AR MODEL 125BL * Some local codes require 18” in garage installations MODEL 125BL TOP (A ) 12 " FRONT (B) 4 " BACK 0 " SIDES 4 " FLOOR (C) 12 " * VENT D IAMETER 5 &q ...

  • AquaStar 125B LPL - page 4

    4 If you are using the AquaStar for combined space heating and potable water heating (see schematic diagram below) , all piping and other components connected to the system must be suit able for pot able water , (b) toxic chemicals such as those commonly used for boiler treatment to prevent corrosion and freezing must not be introduced into the sys ...

  • AquaStar 125B LPL - page 5

    5 7 . Correct gas pressure is critical for the optimum operation of this heater (see specifications on page 2). Gas piping must be sized to provide the required pressure at the maximum output of the heater , while all the other gas appliances are in operation. Check with your local gas supplier , and see the section on connecting the gas supply . 8 ...

  • AquaStar 125B LPL - page 6

    6 dilution of flue gases. Appliances located in confined spaces: The confined space must be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. Each opening must have a minimum free area of one square inch per: - 1000 Btu/hr if all air is taken from ins ...

  • AquaStar 125B LPL - page 7

    7 Fig. 3 - V ent Adaptor for High Altitude Canadian Installations W ARNING : Failure T O INCREASE THE VENT SIZE TO SIX INCHES AND/or assure that the manifold pressure is set to proper value listed for applications at high altitudes will cause unsafe venting, asphyxiation, and will void CSA Certification. GAS CONNECTIONS and Gas Regulator NOTE: The ...

  • AquaStar 125B LPL - page 8

    8 GAS PIPING , CONNECTIONS and Gas Regulator Before connecting the gas supply , check the rating plate on the right side of the front cover to be sure that the heater is rated for the same gas to which it will be connected. In the United S tates: The inst allation must conform with local codes or , in the absence of local codes, the National Fuel G ...

  • AquaStar 125B LPL - page 9

    9 THREADED ASSEMBL Y SWEA TED ASSEMBL Y 1/2” FLEX PIPE PRV TO APPROPRIA TE DISCHARGE S FITTING PIPE PRV TO APPROPRIA TE DISCHARGE 1/2” FLEX Fig. 6-Plumbing connections for the Aquastar 125BL NOTE: Do not apply soap solution to pilot filter screen or pilot orifice area. If you have a leak, shut off the gas. Af ter verifying that required gaskets ...

  • AquaStar 125B LPL - page 10

    10 Fig. 7 - Pressure Relief V alve Connecting the pressure relief valve (PRV) A listed pressure relief valve supplied with the heater must be installed at the time of installation. No valve is to be placed between the PR V and the heater . No reducing coupling or other restriction may be installed in the discharge line. The discharge line must be i ...

  • AquaStar 125B LPL - page 11

    11 T o clean the pilot burner and/ or the pilot orifice : Turn off the gas at the unit. Remove the cover of the heater . T o do so, remove incandescent particle tray and unscrew the central screw located at the bottom of the front cover . Pull main cover out toward you and lift up and out. Pull the air screen off, wash it and blow any lint of f (Se ...

  • AquaStar 125B LPL - page 12

    12 C . Gas regulator may be shut or damaged. 2. In-line AquaStar gas regulator jammed (usually on LP gas) Replace or unlock the regulator . Note: The regulator furnished with the heater is designed for low gas pressure. Excessive pressure will lock it up (propane only). Locking usually happens if the gas pressure between the gas tank (propane) and ...

  • AquaStar 125B LPL - page 13

    13 WA TER IS TOO HOT 1 . Gas flow is higher than necessary . Move gas control slide to the left. 2. T emperature (aquastat) control is set too high If unit is plumbed in a recirculating loop system the aquastat temperature relay for the primary circulator pump is possibly set too high. WA TER IS NOT HOT ENOUGH 1. Water flow rate is too high. Decrea ...

  • AquaStar 125B LPL - page 14

    14 HOT W A TER TEMPERA TURE FLUCTUA TES 1. Cold water is mixing with the hot water between the AquaStar and the outlet (if not being used with a circulator pump) See #5 under “ Burners do Not Ignite When Hot Water Turned On ” . 2. Storage in tank (recirculating system) has not fully recovered S torage capacity in t ank is inadequate. Increasing ...

  • AquaStar 125B LPL - page 15

    15 Fig. 10 - Diagram of AquaS t ar 125 BL 2 4 6 7 1 5 8 10 1. Heat exchanger 2. Pilot assembly 3. Burner manifold gas pressure test nipple 4. Pilot gas tubing 5. Main gas burner 6. Gas valve 7. Gas control slide 8. Piezo igniter 9. Location of pressure tap nipple 10. W ater valve 1 1. Gas inlet gas pressure test nipple 3 11 9 ...

  • AquaStar 125B LPL - page 16

    16 Fig. 1 1 - INTERIOR COMPONENTS DIAGRAM AND P ARTS LIST ...

  • AquaStar 125B LPL - page 17

    17 Fig. 1 1 INTERIOR COMPONENTS DIAGRAM AND P ARTS LIST 125BL 1 Cover ¤ 8 705 421 031 2 Cap cover ¤ 8 703 304 01 1 3 W ater connection gasket ¤ 8 710 103 043 4 Draft divertor ¤ 8 705 505 354 5 Heat exchanger ¤ 8 705 406 235 6 Hot water pipe ¤ 8 700 705 431 7 Cold water pipe ¤ 8 700 705 294 8 Heat exchanger washer ¤ 8 710 103 045 9 Overheat ...

  • AquaStar 125B LPL - page 18

    18 ...

  • AquaStar 125B LPL - page 19

    19 ...

  • AquaStar 125B LPL - page 20

    Replacement Parts available from North American Distributor CONTROLLED ENERGY CORP . 340 Mad River Park W ait sfield, V ermont 05673 Phone 800-642-31 11 Fax (802) 496-6924 ww w .controlledenergy .com techsuppport@controlledenergy .com VULCANO T ermodomésticos S.A. Estrada de Cacia 3801 - 856 Aveiro - PORTUGAL GA S LI NE SI ZE Nat ur al Gas Nom i n ...

Fabricant AquaStar Catégorie Water Heater

Les documents que nous recevons du fabricant de l'appareilAquaStar 125B LPL peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques AquaStar
- manuels d’utilisations 125B LPL
- fiches produit AquaStar
- dépliants
- ou étiquettes-énergie AquaStar 125B LPL
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation AquaStar 125B LPL.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation AquaStar 125B LPL, manuels d’entretien, brefs manuels ou manuels de l’utilisateur AquaStar 125B LPL. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit AquaStar 125B LPL.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil AquaStar 125B LPL, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser AquaStar 125B LPL par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs AquaStar 125B LPL.

Le manuel d’utilisation complet AquaStar, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel AquaStar 125B LPL - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières AquaStar 125B LPL, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lAquaStar 125B LPL qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil AquaStar 125B LPL - qui devraient nous aider dans les premières étapes lors de l'utilisation AquaStar 125B LPL
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de AquaStar 125B LPL
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service AquaStar 125B LPL dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de AquaStar 125B LPL?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec AquaStar 125B LPL, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec AquaStar 125B LPL il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)