    V ariab le Speed Modular Multi-position Air Handler s 2-5 T ons T AM7A0A24H21SB T AM7A0B30H21SB T AM7A0C36H31SB T AM7A0C42H31SB PUB. NO . 22-1847-03 T AM7A0C48H41SB T AM7A0C60H51SB T AM7B0C60H51SA ...

  • Trane TAM7A0C42H31SB - page 2

    2 Pub . No . 22-1847-03 Featur es and Benefits © 2012 T rane • Unique cabinet design – 2% or less air leakage – Precision applied - durab le door seals – Specially designed air seal around refrigerant, condensate and conduit connections – Double w all f oamed cabinet system – R-4.2 Insulating V alue (A vg Insulat - ing V alue R-8.2) ? ...

  • Trane TAM7A0C42H31SB - page 3

    Pub . No . 22-1847-03 3 Contents Features and Benefits 2 Optional Equipment 4 Unique Cabinet Design Features and Benets 5 General Data 6 T AM7A0A24H21SB 6 T AM7A0B30H21SB 6 T AM7A0C36H31SB 6 T AM7A0C42H31SB 6 T AM7A0C48H41SB 6 T AM7A0C60H51SB 6 T AM7B0C60H51SA 6 P erformance Data 7 Electrical Data 13 Field Wiring 20 Con ver tibility 24 Dimensio ...

  • Trane TAM7A0C42H31SB - page 4

    4 Pub . No . 22-1847-03 Optional Equipment Accessory Number Description Fits Cabinet Size BA YEV AC05BK1AA Electric Heater , 5kW , Breaker , RS-485 Control, 1 Ph A to C BA YEV AC05LG1AA Electric Heater , 5kW , Lugs, RS-485 Control, 1 Ph A to C BA YEV AC08BK1AA Electric Heater , 8kW , Breaker , RS-485 Control, 1 Ph A to C BA YEV AC08LG1AA Electric H ...

  • Trane TAM7A0C42H31SB - page 5

    Pub . No . 22-1847-03 5 5 Conduit Connections Locations r Integrated Horizontal Drain P ans 6 T ool-less Door Fastener s 7 Alert Code Viewport e Compact 20.8” Depth with Doors Remo ved 1 Unique Cabinet Design 2 Precision Durable Door Seals q Electronic Expansion V alve (EEV) 3 Refrigeration Connections 9 All Aluminum Coil t Safety Door Switch 4 C ...

  • Trane TAM7A0C42H31SB - page 6

    6 Pub . No . 22-1847-03 General Data PRODUCT SPECIFICA TIONS MODEL T AM7A0A24H21SB RA TED V OL TS/PH/HZ. 200-230/1/60 RA TINGS 1 See O .D . Specications INDOOR COIL — T ype Plate Fin Rows — F .P .I. 3 - 14 F ace Area (sq. ft.) 3.67 T ube Size (in.) 3/8 Refrigerant Control EEV Drain Conn. Size (in.) 2 3/4 NPT DUCT CONNECTIONS See Outline Draw ...

  • Trane TAM7A0C42H31SB - page 7

    Pub . No . 22-1847-03 7 T AM7A0A24 AIRFLO W PERFORMANCE CONST ANT CFM MODE / CONST ANT TORQ UE MODE OUTDOOR MUL TIPLIER (T ONS) COOLING AIRFLOW SETTING Airow Po we r EXTERNAL ST A TIC PRESSURE HEA TING AIRFLOW SETTING Airow Po we r EXTERNAL ST A TIC PRESSURE 0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9 1.5 tons 360 CFM/ton CFM W atts 542 / 652 38 ...

  • Trane TAM7A0C42H31SB - page 8

    8 Pub . No . 22-1847-03 T AM7A0B30 AIRFLO W PERFORMANCE CONST ANT CFM MODE / CONST ANT TORQ UE MODE OUTDOOR MUL TIPLIER (T ONS) COOLING AIRFLOW SETTING Airow Po we r EXTERNAL ST A TIC PRESSURE HEA TING AIRFLOW SETTING Airow Po we r EXTERNAL ST A TIC PRESSURE 0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9 1.5 tons 360 CFM/ton CFM W atts 591 / 685 30 ...

  • Trane TAM7A0C42H31SB - page 9

    Pub . No . 22-1847-03 9 T AM7A0C36 AIRFLO W PERFORMANCE CONST ANT CFM MODE / CONST ANT TORQ UE MODE OUTDOOR MUL TIPLIER (T ONS) COOLING AIRFLOW SETTING Airow Po we r EXTERNAL ST A TIC PRESSURE HEA TING AIRFLOW SETTING Airow Po we r EXTERNAL ST A TIC PRESSURE 0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9 2 tons 350 CFM/ton CFM W atts 724 / 858 44 / ...

  • Trane TAM7A0C42H31SB - page 10

    10 Pub . No . 22-1847-03 Minimum Heating Airo w Settings T AM7A0C42 AIRFLO W PERFORMANCE CONST ANT CFM MODE / CONST ANT TORQ UE MODE OUTDOOR MUL TIPLIER (T ONS) COOLING AIRFLOW SETTING Airow Po we r EXTERNAL ST A TIC PRESSURE HEA TING AIRFLOW SETTING Airow Po we r EXTERNAL ST A TIC PRESSURE 0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9 2.5 tons ...

  • Trane TAM7A0C42H31SB - page 11

    Pub . No . 22-1847-03 11 Minimum Heating Airo w Settings T AM7A0C48 AIRFLO W PERFORMANCE CONST ANT CFM MODE / CONST ANT TORQ UE MODE OUTDOOR MUL TIPLIER (T ONS) COOLING AIRFLOW SETTING Airow Po we r EXTERNAL ST A TIC PRESSURE HEA TING AIRFLOW SETTING Airow Po we r EXTERNAL ST A TIC PRESSURE 0.1 0.3 0.5 0.7 0.9 0.1 0.3 0.5 0.7 0.9 3 tons 33 ...

  • Trane TAM7A0C42H31SB - page 12

    12 Pub . No . 22-1847-03 Minimum Heating Airo w Settings T AM7A0C60H51SB, T AM7B0C60H51SA AIRFLO W PERFORMANCE CONST ANT CFM MODE / CONST ANT TORQ UE MODE OUTDOOR MUL TIPLIER (T ONS) COOLING AIRFLOW SETTING Airow Po we r EXTERNAL ST A TIC PRESSURE HEA TING AIRFLOW SETTING Airow Po we r EXTERNAL ST A TIC PRESSURE 0.1 0.3 0.5 0.7 0.9 0.1 0.3 ...

  • Trane TAM7A0C42H31SB - page 13

    Pub . No . 22-1847-03 13 Electrical Data Notes: 1. See Air Handler nameplate for appro ved combinations of Air Handlers and Heaters 2. Heater model numbers may ha v e additional sufx digits. kW BTUH kW BTUH No Heater 0 - - 3.0** 4 15 - - 3.0** 4 15 BAYEVAC05++1 1 4.80 16400 20.0 29 30 3.60 12300 17.3 25 25 BAYEVAC08++1 1 7.68 26200 32.0 44 45 5. ...

  • Trane TAM7A0C42H31SB - page 14

    14 Pub . No . 22-1847-03 Electrical Data kW BTUH kW BTUH No Heater 0 - - 3.0** 4 15 - - 3.0** 4 15 BAYEVAC05++1 1 4.80 16400 20.0 29 30 3.60 12300 17.3 25 25 BAYEVAC08++1 1 7.68 26200 32.0 44 45 5.76 19700 27.7 38 40 BAYEVAC10++1 1 9.60 32800 40.0 54 60 7.20 24600 34.6 47 50 BAYEVAC10LG3 1-3 PH 9.60 32800 23.1 32 35 7.20 24600 20.0 28 30 BAYEVBC15L ...

  • Trane TAM7A0C42H31SB - page 15

    Pub . No . 22-1847-03 15 Electrical Data kW BTUH kW BTUH No Heater 0 - - 4.2** 5 15 - - 4.2** 5 15 BAYEVAC05++1 1 4.80 16400 20.0 30 30 3.60 12300 17.3 27 30 BAYEVAC08++1 1 7.68 26200 32.0 45 45 5.76 19700 27.7 40 40 BAYEVAC10++1 1 9.60 32800 40.0 55 60 7.20 24600 34.6 49 50 BAYEVAC10LG3 1-3 PH 9.60 32800 23.1 34 35 7.20 24600 20.0 30 30 BAYEVBC15L ...

  • Trane TAM7A0C42H31SB - page 16

    16 Pub . No . 22-1847-03 Electrical Data kW BTUH kW BTUH No Heater 0 - - 5.5** 7 15 - - 5.5** 7 15 BAYEVAC05++1 1 4.80 16400 20.0 30 30 3.60 12300 17.3 27 30 BAYEVAC08++1 1 7.68 26200 32.0 45 45 5.76 19700 27.7 40 40 BAYEVAC10++1 1 9.60 32800 40.0 55 60 7.20 24600 34.6 49 50 BAYEVAC10LG3 1-3 PH 9.60 32800 23.1 34 35 7.20 24600 20.0 30 30 BAYEVBC15L ...

  • Trane TAM7A0C42H31SB - page 17

    Pub . No . 22-1847-03 17 AIR HANDLER ELECTRIC HEA TER PRESSURE DROP Air handler electric heater pressure drop is negligib le f or the heaters and is inc luded in the airow data f or the Series 7 air handler s. Electrical Data ...

  • Trane TAM7A0C42H31SB - page 18

    18 Pub . No . 22-1847-03 T AM7 AIR HANDLER AND HEA TER MA TRIX - ALLO WBLE COMBINA TIONS Electrical Data AIR HANDLER MODEL NUMBER AC05BK1AA 4.80 Kw BK AC05LG1AA 4.80 Kw LG AC08BK1AA 7.68 Kw BK AC08LG1AA 7.68 Kw LG AC10BK1AA 9.60 Kw BK AC10LG1AA 9.60 Kw LG BC15BK1AA 14.40 Kw BK BC20BK1AA 19.20 Kw BK CC25BK1AA 24.00 Kw BK TAM7A0A24H21SB YYYY Y 1 Y 1 ...

  • Trane TAM7A0C42H31SB - page 19

    Pub . No . 22-1847-03 19 Electrical Data WIRING DIA GRAM FOR T AM7 AIR HANDLERS ...

  • Trane TAM7A0C42H31SB - page 20

    20 Pub . No . 22-1847-03 Comfort Control Air Handler Air Conditioner Neatly bundle all low voltage wires behind the service valve cover as shown. Field wiring Y ellow Blue Red Y ellow Green White Blue B B - Blue W G Y1 Y2 Y1 - Y ellow R O O R B YI W1 YO Y2 BK G W2 W3 * (In) (Out) Field Wiring • * For multiple stages of electric heat, jumper W1, W ...

  • Trane TAM7A0C42H31SB - page 21

    Pub . No . 22-1847-03 21 Comfort Control Air Handler Heat Pump Neatly bundle all low voltage wires behind the service valve cover as shown. Field wiring Y ellow Blue Black (X2) Red Orange Red Y ellow Orange Green White Blue B B - Blue W X2 G Y1 Y1 - Y ellow R O O R B YI Y2 W1 YO BK G W2 W3 * R - Red O - Orange (In) (Out) W1 - White Field Wiring Sin ...

  • Trane TAM7A0C42H31SB - page 22

    22 Pub . No . 22-1847-03 T wo Stage Cooling Field Wiring Comfort Control Air Handler Air Conditioner Neatly bundle all low voltage wires behind the service valve cover as shown. Y ellow/Red Field wiring Y ellow/Black Blue Red Y ellow Green White Blue B B - Blue W G Y1 Brown Y2 Y1 - Y ellow Y2 - Brown R O O R B YI W1 YO Y2 BK G W2 W3 * (In) (Out) ? ...

  • Trane TAM7A0C42H31SB - page 23

    Pub . No . 22-1847-03 23 Comfort Control Air Handler Heat Pump Neatly bundle all low voltage wires behind the service valve cover as shown. Y ellow/Red Field wiring Y ellow Blue Black (X2) Red Orange Red Y ellow Orange Green White Blue B B - Blue W X2 G Y1 Brown Y2 Y1 - Y ellow Y2 - Brown R O O R B YI W1 YO Y2 BK G W2 W3 * R - Red O - Orange (In) ( ...

  • Trane TAM7A0C42H31SB - page 24

    24 Pub . No . 22-1847-03 T AM7 Conver tibility Multi-position Air Handler Airflow Airflow Airflow Airflow Upflow Condensate Drains Refrigerant Connections Downflo w Condensate Drains Refrigerant Connections V er tical Downflo w* (as shipped) Horizontal Left* V er tical Upflow* Horizontal Right* Horizontal Left Condensate Drains Refrigerant Connecti ...

  • Trane TAM7A0C42H31SB - page 25

    Pub . No . 22-1847-03 25 Dimensions T AM7 AIR HANDLER DIMENSIONAL D A T A T AM7 AIR HANDLERS ARE ALL TWO PIECE CABINETS. Model No . H W D T AM7A0A24H21SB 49.9 17.5 21.75 T AM7A0B30H21SB 55.7 21.3 21.75 T AM7A0C36H31SB 56.9 23.5 21.75 T AM7A0C42H31SB 56.9 23.5 21.75 T AM7A0C48H41SB 61.7 23.5 21.75 T AM7A0C60H51SB T AM7B0C60H51SA 61.7 23.5 21.75 D H ...

  • Trane TAM7A0C42H31SB - page 26

    26 Pub . No . 22-1847-03 T AM7 OUTLINE DRA WING MODEL NO . A B C D E F H FLO W CONTROL GAS LINE BRAZE LIQ LINE BRAZE T AM7A0A24H21SB 49.9 17.5 14.5 39.6 14.5 7.3 24.4 EEV 3/4 3/8 T AM7A0B30H21SB 55.7 21.3 18.4 45.5 18.4 9.2 24.8 EEV 3/4 3/8 T AM7A0C36H31SB 56.9 23.5 20.5 46.7 20.5 10.3 24.2 EEV 7/8 3/8 T AM7A0C42H31SB 56.9 23.5 20.5 46.7 20.5 10.3 ...

  • Trane TAM7A0C42H31SB - page 27

    Pub . No . 22-1847-03 27 ...

  • Trane TAM7A0C42H31SB - page 28

    T rane 6200 T roup Highway T yler , TX 75707 www .trane.com 03/12 The manuf acturer has a policy of continuous product and product data improv ement and it reserves the right to change design and specifications without notice. ...

Fabricant Trane Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilTrane TAM7A0C42H31SB peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Trane
- manuels d’utilisations TAM7A0C42H31SB
- fiches produit Trane
- dépliants
- ou étiquettes-énergie Trane TAM7A0C42H31SB
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Trane TAM7A0C42H31SB.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Trane TAM7A0C42H31SB, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Trane TAM7A0C42H31SB. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Trane TAM7A0C42H31SB.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Trane TAM7A0C42H31SB, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Trane TAM7A0C42H31SB par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Trane TAM7A0C42H31SB.

Le manuel d’utilisation complet Trane, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Trane TAM7A0C42H31SB - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Trane TAM7A0C42H31SB, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lTrane TAM7A0C42H31SB qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Trane TAM7A0C42H31SB - qui devraient nous aider dans les premières étapes lors de l'utilisation Trane TAM7A0C42H31SB
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Trane TAM7A0C42H31SB
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Trane TAM7A0C42H31SB dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Trane TAM7A0C42H31SB?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Trane TAM7A0C42H31SB, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Trane TAM7A0C42H31SB il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)