  • APC PMJ3XS-B - page 1

    Inst allation and Operation Manual APC Brick Panel Product s PMF3XS-B PMJ3XS-B PMP3XS-B PMH3XS-B PMG3XS-B PML3XS-B ...

  • APC PMJ3XS-B - page 2

    The Brick Panel Product Surge Protective Devices (SPD) are designed to deliver specification grade performance at the service entrance, branch panels or other critical locations. Th e APC SurgeArrest ® Branch Panel Mount Products have replaceable multi-pha se modules, a display panel w ith surge counter, LED status indicators, and an audible alarm ...

  • APC PMJ3XS-B - page 3

    Installation and Operation Ma nual 3 Precautions ........ .............. .............. .............. .............. .............. .............. ... 4 Introduction .. .............. .............. .............. .............. .............. .............. ......... 6 Unpacking and Preliminary I nspection .......................... ............. ...

  • APC PMJ3XS-B - page 4

    4 Installation and Operation Manu al Precautions At end-of-life conditions, Surge Protective Devices ( SPDs) can lose their ability to block power system voltage and attemp t to draw excessive current from the line. This SPD is equipped with overcurrent and overtemperature components that will automatically disconnect th e surge suppression element ...

  • APC PMJ3XS-B - page 5

    Installation and Operation Ma nual 5 Table 1: SPD Per Phase I 2 tI appar ent I p I th PM_3XS-B 175 kA 2 seconds 17,000 A RMS 40,000 A RMS 220 A CA UTION LOSS OF SURGE SUPPRESSION • Do not energize the SPDs until the electrical system is completely installed, inspected, tested, and all conductors have be en conn ected and functional, including the ...

  • APC PMJ3XS-B - page 6

    6 Installation and Operation Manu al Introduction Thank you for choosing the APC SurgeArrest ® PM_3X Series “Brick” Su rge Protective Device. The APC non-modular Surge Protecti ve Device (SPD) is a high-qual ity, high-en ergy surge attenuation system that ha s been designe d to protect sensitive equipment from damaging transient voltage surges ...

  • APC PMJ3XS-B - page 7

    Installation and Operation Ma nual 7 D ANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Apply appropriate p ersonal protective equipment (PPE) and foll ow safe electrical wo rk pr act ices. See NFPA 70E. • This equipment must onl y be inst alled and serviced by qualified electrical personnel. • Turn off all power su pplying this equi ...

  • APC PMJ3XS-B - page 8

    8 Installation and Operation Manu al Unpacking and Preliminary Inspection Inspect the entire shi pping containe r for damage or sig ns of mishandling before unpacking the device. Remove the packing mate rial and further inspect the device for any obvious shipping damage . If any damage is found and is a result of shipping or handling, immediately f ...

  • APC PMJ3XS-B - page 9

    Installation and Operation Ma nual 9 Electrical Voltage Rating Prior to mounting the SPD, verify that th e devi ce has the same voltage rating as the power distribution system in which it is installe d. Compare th e nameplate voltage or model number on the SPD with the namep late of the electrical distribution equipment. The specifier or user of th ...

  • APC PMJ3XS-B - page 10

    10 Installation and Operation Manu al Terminals, Wire Size, and Installation Torque Terminals are provided for phase (line), neutral, an d equipment ground connections. The SPD termin als accept a range of 12 AWG (3 mm 2 ) to 2 AWG (34 mm 2 ) copper wire for phase, neutral, and ground conn ectors. Torque connections to the followi ng values. Branch ...

  • APC PMJ3XS-B - page 11

    Installation and Operation Ma nual 11 Location of SPD Install Type 2 SPDs on the load side of th e main Overcurrent Protection De vice (OCPD) to comply with NEC Article 28 5 for Type 2 SPDs. Locate the SPD as close as possible to the circuit being ad dressed to minimize the wire length and optimize SPD perfo rmanc e. Avo id long wire runs so th at ...

  • APC PMJ3XS-B - page 12

    12 Installation and Operation Manu al Grounding The SPD has leakage current to ground when energized and can present a hazardous touch voltage. The device has SPD elements conne cted from phase to ground. To prevent hazardous touch voltage on the SPD enc losu re during normal operation or during SPD end-of-life , it is critical that there be a robu ...

  • APC PMJ3XS-B - page 13

    Installation and Operation Ma nual 13 Installation Conduit Location and Recommendations The recommended conduit entry is at the bottom of the device enclosure. Use a conduit seal that is appropriate for the enclosure rating. Special Enclosure Considerations Removing and Reconnect ing the RJ45 Patch Cables The RJ45 patch cables are marked with match ...

  • APC PMJ3XS-B - page 14

    14 Installation and Operation Manu al Wiring Follow the step s listed below when making wi ring connections. 1. Turn off all power supplying this equip ment before working on or i nside any enclosure containing this equipment. 2. Confirm the SPD voltage ra ting and configuration i s the same as th e system voltage and power system co nfiguration to ...

  • APC PMJ3XS-B - page 15

    Installation and Operation Ma nual 15 Wiring Diagrams without Integral Switch Figure 3: SIngle-Phase , T hree-Wire, Grou nded Installati on Figure 4: Three-Phase, Three- or Four-Wire, Ground ed Wye Installation Figure 5: Three-Phase, Three- or Four -Wire, High-Leg Delta Installation N 8222-0013-04 SPD A N C Made in U S A / Hecho en E.U.A. / Fabriqu ...

  • APC PMJ3XS-B - page 16

    16 Installation and Operation Manu al Operation LED Status Indicators The diagnostic display panel shows the sta tus of the SPD module with diagnostically controlled gree n/red LEDs. If a unit is operating correctly, a ll the phase LEDs will be illumin ated green. To te st the integrity of the diagnostics for each phase, push the button below the p ...

  • APC PMJ3XS-B - page 17

    Installation and Operation Ma nual 17 When power is applied to the SPD and one or more of the diagnostic display panel LEDs are red, and one or more modul e LEDs are out, the module sho uld be replaced. Refer to “Maintenance and Tr oubleshooting” on page 19 for prop er troubleshooting procedu res. Audible Alarm Push the alarm enable/disable but ...

  • APC PMJ3XS-B - page 18

    18 Installation and Operation Manu al Dry Contacts The SurgeArrest ® series SPDs come standard with dry contacts. The connection for the dry contacts is located on the back of the diagnostic display panel (lower right corner). The dry cont acts are 3-posi tion, Form “C” type with Normally Open, Normally C losed and Common conn ections. In the ...

  • APC PMJ3XS-B - page 19

    Installation and Operation Ma nual 19 Maintenance and Troubleshooting Preventive Maintenance Inspect the SPD periodically to main tain reliable system performance and continued transient voltage surge suppression. Periodicall y check the state of the diagnostic displ ay panel LED status ind icators. Routinely use the built-in diagnostics to inspect ...

  • APC PMJ3XS-B - page 20

    20 Installation and Operation Manu al Troubleshooting If a module shows two gree n indicator lights and the di splay panel shows a red phase indicator light, follow the Troubl eshooting Flow Chart in Figure 9 below. Replac ement Pa rts The following replacement part s are available. For orderi ng information re fer to the product catalog. • SPD m ...

  • APC PMJ3XS-B - page 21

    Installation and Operation Ma nual 21 ...

  • APC PMJ3XS-B - page 22

    22 Installation and Operation Manu al ...

  • APC PMJ3XS-B - page 23

    Installation and Operation Ma nual 23 ...

  • APC PMJ3XS-B - page 24

    APC Worldwide Customer Support Customer support for this or other APC products is available at no charge in the fo llowing ways: • Visit the APC website to access documents in the APC Kn owledge Base and to submit customer support requests. — www.apc.com (Corporate Headquarters) Connect to localized APC Web sites fo r spe cific countries, ea ch ...

Fabricant APC Catégorie Surge Protector

Les documents que nous recevons du fabricant de l'appareilAPC PMJ3XS-B peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques APC
- manuels d’utilisations PMJ3XS-B
- fiches produit APC
- dépliants
- ou étiquettes-énergie APC PMJ3XS-B
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation APC PMJ3XS-B.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation APC PMJ3XS-B, manuels d’entretien, brefs manuels ou manuels de l’utilisateur APC PMJ3XS-B. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit APC PMJ3XS-B.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil APC PMJ3XS-B, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser APC PMJ3XS-B par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs APC PMJ3XS-B.

Le manuel d’utilisation complet APC, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel APC PMJ3XS-B - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières APC PMJ3XS-B, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lAPC PMJ3XS-B qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil APC PMJ3XS-B - qui devraient nous aider dans les premières étapes lors de l'utilisation APC PMJ3XS-B
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de APC PMJ3XS-B
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service APC PMJ3XS-B dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de APC PMJ3XS-B?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec APC PMJ3XS-B, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec APC PMJ3XS-B il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)