    S1C/S1H Single-Zone & S2C Dual-Zone SiDe DiSCHarge DuCtleSS Split SyStem ConDenSing unitS P/N# 240005897 Rev . B [05/08] Straight Cool/hea t pump S1C/S1h Nominal Circuit Capacities S1C/S1H: 9,000, 12,000, 18,000, 24,000 Btuh and S1C 30-36 Btuh Cooling onl y S2C Nominal Circuit Capacities: 9,000-12,000 Btuh Enviromaster International LLC 5780 Su ...

  • EMI Volts/HZ/pH - page 2

    www .enviromaster.com Side Discharge Condensers 2 inSt alla tion, opera tion anD maintenanCe manUal S1C/S1H Single-Zone & S2C DUal-Zone ConDenSing UnitS Shipping Damage MUST be Reported to the Carrier IMMEDIA TEL Y!!! Examine the exterior . Remove cover and examine compressor and piping for signs of damage. This manual is intended as an aid to ...

  • EMI Volts/HZ/pH - page 3

    www .enviromaster.com Side Discharge Condensers 3 proDUCt DeSCription The AmericaSeries S1C/H and S2C condensing units are, air-cooled, vertically arranged side discharge, high efciency units designed specically to meet or ex - ceed a 13 SEER rating. The S1C 9,000-36,000 Btuh and S1H 9, 000- 24, 000 Bt uh ca pac ity co nde ns ing u nit wil l ...

  • EMI Volts/HZ/pH - page 4

    www .enviromaster.com Side Discharge Condensers 4 itemS For ConSiDera tion • Locate the unit as close to the indoor section as possible. ( S ee T ubing Specications chart on pape 7.) • If the unit is used for low ambient cool - ing down to 32°F , this option must be specied to prevent system damage. • A void high trafc areas and pre ...

  • EMI Volts/HZ/pH - page 5

    www .enviromaster.com Side Discharge Condensers 5 inSt alla tion inStrUCtionS Unit moUnting inStrUCtionS Continued 5. Insert lag bolts through the holes in the bottom of the unit and tighten to secure. 6. Insert lag bolts through the holes in the feet on the back of the unit and tighten to secure. 7. Replace the front panel, do not tighten the side ...

  • EMI Volts/HZ/pH - page 6

    www .enviromaster.com Side Discharge Condensers 6 inSt alla tion inStrUCtionS c. Slide the side panel out to access the high/low electrical connections and wire diagram. Note: Remove the plastic edge guards from the holes and replace with a water- tight strain relief tting (High V) and a split grommet tting ( l ow V) 5. Power should be run to ...

  • EMI Volts/HZ/pH - page 7

    www .enviromaster.com Side Discharge Condensers 7 inSt alla tion inStrUCtionS 10. T o replace side panel slide the slotted holes of the panel onto the loosened screws of the front panel so that the edge of th e front pa nel cove rs th e edge of the side panel. eleCtriCal Wiring Continued 1 1. Fasten all remaining loose screws. reFrigerant piping Th ...

  • EMI Volts/HZ/pH - page 8

    www .enviromaster.com Side Discharge Condensers 8 Condenser Evaporator Figure 1 Condenser Evaporator 30' 15' p-trap inSt alla tion • A P-trap is recommended when the suc - tion riser is equal to or greater than 20 feet in height . • When the condenser is installed above the evaporator , the P-trap will help the return of oil back to t ...

  • EMI Volts/HZ/pH - page 9

    www .enviromaster.com Side Discharge Condensers 9 inSt alla tion inStrUCtionS reFrigerant piping Continued 2. Protect the valves by wrapping with a wet rag "heat sink" before brazing. 3. We recommend the use of a shield (can be made from some scrap metal) to protect the paint. 4. Braze tubing into ttings. 1. Clean the ends of tubing an ...

  • EMI Volts/HZ/pH - page 10

    www .enviromaster.com Side Discharge Condensers 10 inSt alla tion inStrUCtionS 9. Refer to Charts on page 12 to “ne tune” the refrigerant charge to meet your conditions. reFrigerant proCeSSing Complete piping ConneCtionS import ant noteS: 1. T o nd the charge adjustment and system charge for any evaporator and tubing length: Line Adjustme ...

  • EMI Volts/HZ/pH - page 11

    www .enviromaster.com Side Discharge Condensers 11 The units are delivered precharged with refrigerant for the condenser coil and the evaporator . Charging of the eld installed piping is required. Refer to the refrigerant charge table for the proper amount to be added for the applications interconect piping. Unit service valves are solid brass, ...

  • EMI Volts/HZ/pH - page 12

    www .enviromaster.com Side Discharge Condensers 12 Single Zone opera tion CHartS ...

  • EMI Volts/HZ/pH - page 13

    www .enviromaster.com Side Discharge Condensers 13 Single Zone opera tion CHartS ...

  • EMI Volts/HZ/pH - page 14

    www .enviromaster.com Side Discharge Condensers 14 Single Zone opera tion CHartS ...

  • EMI Volts/HZ/pH - page 15

    www .enviromaster.com Side Discharge Condensers 15 Single Zone opera tion CHartS ...

  • EMI Volts/HZ/pH - page 16

    www .enviromaster.com Side Discharge Condensers 16 Single Zone Hea t pUmp opera tion CHartS ...

  • EMI Volts/HZ/pH - page 17

    www .enviromaster.com Side Discharge Condensers 17 Single Zone Hea t pUmp opera tion CHartS ...

  • EMI Volts/HZ/pH - page 18

    www .enviromaster.com Side Discharge Condensers 18 DUal Zone opera tion CHartS ...

  • EMI Volts/HZ/pH - page 19

    www .enviromaster.com Side Discharge Condensers 19 opera tion anD maintenanCe The S1C/H and S2C outdoor sections are the compressor bearing units of the system. It operates at the command of the indoor section or room thermostat. Therefore, the system operation will be described in the manual pertaining to the indoor section. EMI units are designed ...

  • EMI Volts/HZ/pH - page 20

    www .enviromaster.com Side Discharge Condensers 20 Single-Zone anD DUal-Zone SeqUenCe oF opera tion Note: For remote wall mounted ther - mostat operation be sure to select EMI p/n 240004180 or a suitable 24 v , two sage heating, heat pump thermostat. Condenser operation: The transform - er locate d in the indo or unit pro vides 24V , low- v olt con ...

  • EMI Volts/HZ/pH - page 21

    www .enviromaster.com Side Discharge Condensers 21 DFT TST R and DF2 DeFroSt Control boarD teSting DeFroSt opera tion USing teSt pinS Single-Zone anD DUal-Zone SeqUenCe oF opera tion W arning! B ef or e re mo vi ng t he ac ce ss pa ne ls to the unit make sure that all power is dis - c on ne ct ed fr om th e un it . F ai lu re t o d o s o could resu ...

  • EMI Volts/HZ/pH - page 22

    www .enviromaster.com Side Discharge Condensers 22 moUnting DimenSionS model Size a b C D S1C/S1H 9, S1C/S1H 2 4 ⅝” 14 11 / 16 ” 3” 12 7 / 16 ” S1C/S1H 8, S1C/S1H 2 4 ⅝” 22 11 / 16 ” 3” 12 7 / 16 ” S1C 3, S1C 6 7” 23 15 / 16 ” 3” 12 7 / 16 ” Easy access interconnects on back of unit 1/2” Diameter Lag Holes a a b D C So ...

  • EMI Volts/HZ/pH - page 23

    www .enviromaster.com Side Discharge Condensers 23 NOtE: All EMI products are subject to ongoing development. Design and specications may change without notice. CAC WLC/WLH * Important - This system has been designed and manufactured to meet ENERGY ST AR criteria for energy efciency . However, proper refrigerant charge and proper air ow ar ...

  • EMI Volts/HZ/pH - page 24

    www .enviromaster.com Side Discharge Condensers 24 S1C/S1H Single Zone S1H eleCtriCal SpeCiFiCa tionS model # V olts/HZ/pH Fan motor Compressor t otal ampS min V olt m.C.a. HaCr brKr ampS Hp rla lra S1H9A 1 15/60/1 1.4 0.125 6.6 39.2 8.0 104 9.7 15 S1H2A 1 15/60/1 1.4 0.125 8.6 48.3 10.0 104 12.2 20 S1H9D 208/230/60/1 0.8 0.125 3.4 23.0 4.2 197 5.1 ...

  • EMI Volts/HZ/pH - page 25

    www .enviromaster.com Side Discharge Condensers 25 WLC CAC S2C Cooling SYStemS WitH S2C SiDe DiSCHarge Cassette Condenser btuh Seer SHr eer ref. CAC12 + CAC12 S2C99 18,000 13.0 .81 1 1.7 R22 CAC12 + CAC12 S2C22 23,000 13.0 .74 1 1.8 R22 CAC12 + CAC12 S2C92 21,000 13.0 .77 1 1.8 R22 Cooling SYStemS WitH S2C SiDe DiSCHarge W all Unit (s) C o n d e n ...

  • EMI Volts/HZ/pH - page 26

    www .enviromaster.com Side Discharge Condensers 26 The T est Unit Performance Data sheet below is provided for use by a qualied service professional in the event that there is a problem with the unit. In order for our T echnical Service Department to better serve you, please complete and have this information ready when calling. Make sure to inc ...

  • EMI Volts/HZ/pH - page 27

    www .enviromaster.com Side Discharge Condensers 27 emi’S proDUCt line inDoor UnitS oUtDoor UnitS S1C & S1H Single Zone Side Discharge S2C &S2H Dual Zone Side Discharge WLC/WLH High Wall Air Handler CAC/CAH Cassette Air Handler UNC/UNH Universal Floor or Ceiling Air Handler T2C, T3C, T4C and T2H, T3H, T4H; 2, 3 and 4 Zone T op Discharge ...

  • EMI Volts/HZ/pH - page 28

    Phone: 1-800-228-9364 Fax: 1-800-232-9364 5780 Success Drive, Rome, NY 13440 ...

Fabricant EMI Catégorie Ventilation Hood

Les documents que nous recevons du fabricant de l'appareilEMI Volts/HZ/pH peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques EMI
- manuels d’utilisations Volts/HZ/pH
- fiches produit EMI
- dépliants
- ou étiquettes-énergie EMI Volts/HZ/pH
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation EMI Volts/HZ/pH.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation EMI Volts/HZ/pH, manuels d’entretien, brefs manuels ou manuels de l’utilisateur EMI Volts/HZ/pH. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit EMI Volts/HZ/pH.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil EMI Volts/HZ/pH, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser EMI Volts/HZ/pH par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs EMI Volts/HZ/pH.

Le manuel d’utilisation complet EMI, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel EMI Volts/HZ/pH - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières EMI Volts/HZ/pH, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lEMI Volts/HZ/pH qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil EMI Volts/HZ/pH - qui devraient nous aider dans les premières étapes lors de l'utilisation EMI Volts/HZ/pH
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de EMI Volts/HZ/pH
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service EMI Volts/HZ/pH dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de EMI Volts/HZ/pH?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec EMI Volts/HZ/pH, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec EMI Volts/HZ/pH il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)