  • Emerson 400A - page 1

    381333–067 K 50 Hanove r Road, F lorham Park, New J ersey 07932–1591 USA For sales or service call 1 800 800–2726 (A SCO ) www.ascopower .com AS CO PO WER TECH NO LOGI E S CA NA DA PO Box 1238, 17 Airport R oad, Brantf ord, O ntario, Can ada N 3T 5T3 Operator’s Manual Seri es 300 Automatic T ransfer S witc hes E–d esi g n, 260 an d 400 A ...

  • Emerson 400A - page 2

    ...

  • Emerson 400A - page 3

    Nameplate and Catalog Number Identificati on The T rans fer Swi tch name plate i nclude s data for e ach speci fic ASCO Series 300 A TS. Use the A TS only with in the limits show n on this namep late. A typical Catalo g Num ber is shown b elow with it s elements expla ine d. The exampl e is for a Ser ie s 300 A TS with switched neutr al , 3 pol e, ...

  • Emerson 400A - page 4

    ...

  • Emerson 400A - page 5

    SECT ION 1 INST ALLA TION 1 --- 1 Series 300 A utom atic T ransfer Switc hes are factory w ired and tested. Install ation requires skid removal then sec ur- ing the enclosure to the supporting foundati on. Suppo rtin g Fo undat ion The su ppor ting fo undation fo r the enc los ure m ust b e level and straig ht. R efer to the applic able en clos ure ...

  • Emerson 400A - page 6

    INST ALLA TION (cont inued) 1 --- 2 Engine Starting Contacts The engine control c onta ct connec ti ons are located on the t ransfe r switch. Connect si gnal wires t o appropri at e term– inals as speci fied i n T a ble A, shown in Figure 1–2. T able A. Engine start connectio ns. When norma l so urce fails T erminal s on tra nsfer switch contac ...

  • Emerson 400A - page 7

    INST ALLA TION (cont inued) 1 --- 3 F unctio nal T est The F unctional T est consists of thr ee chec ks: manual operation, v oltage check s, and el ectrical operation. NOT ICE Do these checks in the order presented to avoid damaging the auto matic transfer s witch. R ead all instructions on the W iring Diagram and labels affixed to the autom atic t ...

  • Emerson 400A - page 8

    INST ALLA TION (cont inued) 1 --- 4 observe these l ights Figure 1–5. Standard control s and indicato rs. 2–V o l t a g e C h e c k s First check nameplate on tra nsfer swi tch; rated voltage m u s tb et h es a m ea sn o r m a la n de m e r g e n c yl i n ev o l t a g e s . Use ext reme caution when using a meter to measure volta ges in the fo ...

  • Emerson 400A - page 9

    INST ALLA TION (cont inued) 1 --- 5 p r e s st h i sb u t t o n observe these l ights Figure 1–6. Standard control s and indicato rs. 3 – Electrica l Opera tion Th i s pr oce du re wi ll che ck t he e le ctr ica l o pe ra ti o n o f t he A utomatic T ransfer Switc h. Close th e transfe r switc h encl osure door a nd tighten t he screws befo re ...

  • Emerson 400A - page 10

    Hol d 15 sec .t o start t he engine generator and to transf er the load to emergency . Press to cancel the active exercise period (sto ps engine now or afte r cooldow n) Se e page 5– 1. Hol d 5 sec .t os e t 20 min. engine ex ercise perio d immediately (engine starts) and weekly thereaf ter . ³ blinks sl owly when button is r eleased (set) and d ...

  • Emerson 400A - page 11

    SECT ION 3 TEST ING & SERVIC E 3 --- 1 PREV ENTIV E MAIN TENAN CE F or high rel iabil ity and long l ife for the A TS: Ope rate t he sw itc h at l east o nce a mo nth .P e r f o r m t h i s 4–step Electrical Operat ion T e st (te st with load t ransfer). T r ansfer Swi tch T est 1. Press and ho ld the door -mounted T ra nsfer T est button unt ...

  • Emerson 400A - page 12

    TEST ING & SERVIC E (continued) 3 --- 2 MANUAL L OAD TR ANSFER This pr oced ure w ill m anual ly tr ansfer th e load if th e cont ro lle r is d i sco nne ct ed . Do no t manually operate the transfer switch until bot h power so urces are disconnected: open bot h circuit breakers . 1. Open normal and emergency source ci rcuit brea kers. 2. Use t ...

  • Emerson 400A - page 13

    SECT ION 4 ADJUST MENTS 4 --- 1 Ti me De l ay A d j u st m e n t Standard ti me delays are set to customer specificati ons (if none specif ied, st andard factory set tings are used). T o change a setting, follow proc edure on page 4-2. Use T abl e 4-1 as a gu ide to time del ay values and their c or- responding adjustment DIP switch or potentiomete ...

  • Emerson 400A - page 14

    ADJUST MENTS (continued) 4 --- 2 NOT ICE Do not make any set ting changes while the contro ller is energized. How to Change a Setti ng 1. Prev ent the transfer switch from operating b y discon- nec ting one s ourc e first, then the o ther, as fol low s: a. If the transfer s witch is in the No rmal p osition, ope n t he e mer gen cy so urce ci r cui ...

  • Emerson 400A - page 15

    SECTION 5 CONTROL FEA TURES – ENGINE EXER CISERS 5 --- 1 These timer s periodic ally exer cise the em ergenc y engine-g enerator p lant. They can b e set to exercise w ith or withou t load tr ansfer, or they can b e compl etely disab led. The engine-gen erator shoul d be exercised u nder load on ce a week for a minimum time period of 20 minutes, ...

  • Emerson 400A - page 16

    CONTRO L F EATURES (continued) 5 --- 2 Opt ion al Ac ce ssory 11BG – SOURCE AV AILABIL ITY SIG NAL & P ROGRAMMA BLE EN GINE EX ERCIS ER MOD ULE 2–line display 3 buttons connectio ns for source ava ila bilit y signal co ntacts Figure 5–2. Accessory 11BG module ( mounted behind operato r interface and connected to the co ntroll er) incl ude ...

  • Emerson 400A - page 17

    Fa s t/ Sl o w A d j u st Dayl ight Savi ng Time A dju st Date Time Start T Ime Engine Exerciser Run TIm e CONTRO L F EATURES (continued) 5 --- 3 How to Set Option a l Progra mm ab le En gin e Exe rcis er (p art o f Acc. 11BG mo dule) Haza rdous vol tage ca pabl e of causin g shock, burns, o r death is used in this t ransfer switch. Deenergize bo t ...

  • Emerson 400A - page 18

    CONTRO L F EATURES (continued) 5 --- 4 INPHASE M ONITOR FOR M OTOR LOAD TR ANSF ER Inphase monitori ng logic con trols tr ansfer and retransfe r of motor loads, so that inrush current s do not exceed normal starti ng currents. It a voids nuisance tripping of cir cuit breakers and m echanic al damag e to mot or co up li ngs . The Motor Load T ransfe ...

  • Emerson 400A - page 19

    CONTRO L F EATURES (continued) 5 --- 5 OPTIONAL STR IP HEA TER ( Accessory 44) A cc essory 44 Str ip Heater is design ed to keep ambient temp eratures within the A utomatic T ransfer Switc h en closu re a t a ccep ta ble le ve ls. Th i s acce sso ry co nsi s ts of a mounting bracket with strip heat er, thermosta t, and terminal block. A transformer ...

  • Emerson 400A - page 20

    INDEX Printed in U .S.A. Copy right - - - ASC O Power T echn ologies, L.P . 2011 A accessories, 5–2, 5–5 auxil iary cir cuits , 1–2 B battery , 4–2, 5–1 buttons, push, 3–1 bypass time delay, 1–5, 2–1, 3–1 C cable lugs, preparation, 1–1 cat alo g nu mber, cove r cleaning, 3–1 connections engine control contact, 1–2 line, 1– ...

Fabricant Emerson Catégorie Switch

Les documents que nous recevons du fabricant de l'appareilEmerson 400A peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Emerson
- manuels d’utilisations 400A
- fiches produit Emerson
- dépliants
- ou étiquettes-énergie Emerson 400A
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Emerson 400A.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Emerson 400A, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Emerson 400A. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Emerson 400A.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Emerson 400A, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Emerson 400A par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Emerson 400A.

Le manuel d’utilisation complet Emerson, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Emerson 400A - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Emerson 400A, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lEmerson 400A qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Emerson 400A - qui devraient nous aider dans les premières étapes lors de l'utilisation Emerson 400A
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Emerson 400A
5. FAQ - questions fréquemment posées