    UPS OPER ATING INSTRUCTIO NS PROTECT A . 1000 PROTECT A . 1400 PROTECT A. ...

  • AEG Protect A. 1400 VA - page 2

    2 ...

  • AEG Protect A. 1400 VA - page 3

    3 EN Thank you fo r deciding t o purchase the PROT ECT A. UPS from AE G Pow er Solutions. The following safety instructions are an important part of the operating instruction s are will protect y ou against problems from operating errors and possible dangers. Please read these instructions carefully prior to commissioning! ...

  • AEG Protect A. 1400 VA - page 4

    4 1 Notes on these Operating Instructions Duty to provide information These operating instructions will help you to install an d operate the U ninterruptible Po wer Supply (UPS), PROTECT A . 1000 or PROT ECT A. 14 00 - referred to as PROTECT A . in this document - safely and properl y, and f or its i ntended purpose. T hese op erating instructions ...

  • AEG Protect A. 1400 VA - page 5

    5 EN obligations suc h as warra nty agreements, service contracts , etc. entered into by A EG or its representatives without prior notice in the event of maintenanc e and r epair w ork being carried out wit h a nything other than original AEG parts or spare parts purchas ed from AEG. Handling PROTECT A . is desi gned and co nstructed so that all ne ...

  • AEG Protect A. 1400 VA - page 6

    6 Table of Contents 1 Notes on these Opera ting Instruc tions ..............................4 2 System Overvie w .................................... ..........................7 2.1 Brief Overvie w .......................................... ..................7 2.2 Principle of Operat ion............................... ..................8 3 Safety . ...

  • AEG Protect A. 1400 VA - page 7

    7 EN 6 Displays and Tr oubleshooting .........................................26 6.1 LC Displa y ............................................... .................26 6.2 W arning Sounds........................................ ...............29 6.3 General Tr oubleshooting and Fault R ectification .....29 7 Maintenance ............................... ...

  • AEG Protect A. 1400 VA - page 8

    8 Important UPS data is m onitored perm anently an d transf erred to the com puter via U SB or the RS232 in terface and u sing the CompuW atch software. Features of the PROT ECT A.: ♦ VI (line – interactive) protec tion technolog y ♦ Autom atic voltage regulatio n against mains voltage deviations (AVR) ♦ Microproces sor control for hig h re ...

  • AEG Protect A. 1400 VA - page 9

    9 EN Inverter Battery Rectifier Load Mains Line filter A. V. R. ~ ~ the i nternal energ y st orage, som ething which in tur n has a positive eff ect on battery availab ility. UPS Block diagra m PROTECT A . The static by pass switch is a ctivated in the event of a m ains failure. The inverter t hen tak es over t he voltage sup ply of t he connected ...

  • AEG Protect A. 1400 VA - page 10

    10 3 Safety 3.1 General Safety Instructions Read these oper ating instructions carefully prior to commiss ioning of the PR OTECT A. UPS and observe the safety instructions! Only us e the unit if it is in a technically perf ect c ondition and always in accordance with its intended purpose , while being aware of safety a nd danger aspects, and in acc ...

  • AEG Protect A. 1400 VA - page 11

    11 EN The output ma y be live, e ven if th e U PS is not connected to the m ains supp ly, as the U PS has its own internal po wer suppl y (battery)! For health and safet y reasons, the uni t m ust be earthed correctl y! PROTECT A. m ay onl y be operated with or connected to a 220 / 230 / 240 VA C m ains with protect ive grou nding us ing a mains co ...

  • AEG Protect A. 1400 VA - page 12

    12 ♦ Condensat ion may occur if the UPS is brough t from a cold environm ent into the room where it is to be installed. The U PS must be absol utely dry prior to start - up. As a result, leave it to acc limatise for at least two hours. ♦ Never c onnect the m ains input and the UP S output! ♦ Ensure that no fluids or foreig n bodies can pene t ...

  • AEG Protect A. 1400 VA - page 13

    13 EN W hen replacing t he batt eries, the fol lowing m ust be o bserved: Only ever use identical , maintenance-free sea led lead batteries with the sam e data as the ori ginal batteries . Danger! Explosive ! Never throw batteries into open fire. Never open or dam age batteries. (Elec trolyte m ay leak out and damage sk in and eyes. It m ay be toxi ...

  • AEG Protect A. 1400 VA - page 14

    14 3.3 CE Certificate ...

  • AEG Protect A. 1400 VA - page 15

    15 EN 3.4 Technical Data Type rating PROTECT A. 1000 1000 VA / 600 W PROTECT A. 1400 1400 VA / 840 W UPS input Nominal connecti on voltage 220 / 230 / 240 Vac Voltage range with out batter y 170 Vac to 280 Vac Frequenc y (automatic detection) 50 / 60 Hz Connection Non-heating app liance connector IEC 320 C 14 UPS output Rated output volta ge / 230 ...

  • AEG Protect A. 1400 VA - page 16

    16 Charging tim e (to 90 % of rated ca pacity) 6 h T y pe Sealed, m aintenance-free PROTECT A. 1000 2 bl ock b at te ri e s 1 2 V / 7 A h e.g. C SB, type GP1272F2 3- 5 y ear s a cc. t o EU R OBA T Yuasa, type NP7- 12D Connection plug 6.3 mm Panasonic, t ype LC-R127R2P (Fas ton 250) PROTECT A. 1400 2 block bat teri es 1 2 V / 9 A h e.g. C SB, type H ...

  • AEG Protect A. 1400 VA - page 17

    17 EN Directives The PROT ECT A. meets the prod uct standard EN 5 0091. The CE m ark on the unit confirm s compliance with the EC outline directives f or 73/23 EEC – L ow voltage and f or 89/336 EEC – Electrom agnetic com patibility if the instal lation instructions describ ed in the oper ating instructions are observed. For 73/23 EEC lo w-volt ...

  • AEG Protect A. 1400 VA - page 18

    18 Check the content is complete: ♦ PROT ECT A. with 1000 or 1400 VA ♦ Mains c onnection cable with shockpr oof plug acc. to CEE 7/7 Second m ains connection cable with UK plug acc. to BS 1363 ♦ T wo device connecting cab les ♦ USB / R S232 comm unication cable ♦ Managem ent software “Co mpuW atch” on CD ♦ Operating instructions Ple ...

  • AEG Protect A. 1400 VA - page 19

    19 EN 4.3 Connections, Operating and Display Elements Front Rear 1 Main switch of the U PS (mains switch) 2 LC display with: - Display of operat ing mode with pictogram s - Measured value d isplays [V] - UPS capacit y utilisation dis play [%] - UPS rem aining op. time displa y [min.] - Fault indication 1 Load connections with overvoltage protecti o ...

  • AEG Protect A. 1400 VA - page 20

    20 5 Inst allation and Operatio n 5.1 Check Remove the UPS f rom its transport packaging and check that it has not been dam aged in tra nsit. If you find an y dam age, pack the unit up again and send it back to w here you purchased it. 5.2 Installation Install t he U PS unit in a pr otected location where th ere i s an adequate air s upply a nd whe ...

  • AEG Protect A. 1400 VA - page 21

    21 EN 5.3 Charging The PROT ECT A. is supplied with its batter y f ully c harged. Nevertheless, energ y m ay have been lost d uring transport, so the batter y should be fully recharged before it is used f or the first time. Connect the input of the U PS (no. 2 in the f igure in c hapter 4. 3 on page 19) to the mains connection cable pr ovided a nd ...

  • AEG Protect A. 1400 VA - page 22

    22 i In this c onnection, note the special pr operty of the two additional output s ockets identified with “SURGE ONL Y” (chapter 4.3 / no. 7 / pg . 19). These are always live irr espective of the other outputs. T hey are n ot bac ked up by the UPS, nor can the y be s witched off using the m ain s witch of the UP S. It is intended for loads tha ...

  • AEG Protect A. 1400 VA - page 23

    23 EN i The interfaces are mutuall y exc lusive. T here is no provision f or simultaneous operation of RS232 and USB. 5.7 Operation Once you have con nected the UPS to a suitable mains connection, you can start operat ion using the UPS main switch. Switching O N and OFF:  To switch on, pres s the main switch on the f ront of the UPS (chapter 4.3 ...

  • AEG Protect A. 1400 VA - page 24

    24 The connected l oads are po wered using the m onitored and filtered m ains voltage , whi ch is ad ditionally st abilised by th e integrated A.V.R. control unit. The “LINE MODE” symbol shows that the un it is active. 5.7.2 Battery Operation / Auton omous Operation W hen there is a m ains fai lure or if the input voltage m oves outside the t o ...

  • AEG Protect A. 1400 VA - page 25

    25 EN 5.7.3 System Diagnosis / Fault Test If the m onitoring e lectronics dete ct an irregularity, the fault indicator is ac tivated which is sig nalled b y th e “Fault” pictogram and a digita l f ault c ode, possibl y acc ompanied b y an acous tic fault signa l. This might occur beca use th e batter y undervoltage lim it has been reached, if t ...

  • AEG Protect A. 1400 VA - page 26

    26 6 Displays and T roublesh ooting 6.1 LC Display The blue back lit displa y is automatically act ivated after the mains voltage is con nected. It oper ates irrespectiv e of the main switch setting and also when a fault is indicated. 1) The start of operational re adiness is signalled on the LC display by all t he inform ation content lighti ng up ...

  • AEG Protect A. 1400 VA - page 27

    27 EN 4) If the UPS is in battery mode, th e “BATTER Y” pictogram lights up and the ba ttery sym bol flashes ever y second. The remaining s tandb y tim e is displayed dur ing b attery operation accor ding to the load a pplied. T his time is shown in minutes and is in dicated by the “MIN” pictogram . i The display sho ws “0” if the volta ...

  • AEG Protect A. 1400 VA - page 28

    28 Fault CODE Possible fault cause 01 Output short circuit (output voltage less th an 60 V) 02 Overload indicator Immediate fau lt mess age in m ains/normal operation with a cap acity utilisation of > 120%, at a c apacit y utilisation > 110% the fault m essage com es after 5 minutes or after 30 seconds in battery operation. 03 Output voltag e ...

  • AEG Protect A. 1400 VA - page 29

    29 EN 6.2 Warning Sounds Warning sound Meaning Sounds every 10 seconds. UPS is operating in battery mode. Sounds every second. UPS is running in ba ttery mode an d will shortly shut down (battery system has rea ched the battery undervo ltage limit). Sounds every tw o seconds Battery syste m faulty, it may have to be re newed (battery diagnosi s neg ...

  • AEG Protect A. 1400 VA - page 30

    30 Miniature circuit breaker triggered Press reset button o f miniature circuit breaker; Mains nor mal, but “Battery” LED fla shes Mains cable loose Insert the plug fir mly into the non- heating appliance so cket of the UPS. Software is not ins talled correctly Check the softw are settings. Support is available at www .AEGpartnerNet.de Communic ...

  • AEG Protect A. 1400 VA - page 31

    31 EN 7 Maintenance The P ROT ECT A. consists of state-of-the-art, non-wearing components. W e do, however, recomm end regular visual checks of the unit to m aintain its c ontinuous av ailabilit y and operational reliab ility. Check whether: ♦ there is an y mechanical da mage or foreign bodi es can be found in the s ystem, ♦ any cond uctive dir ...

  • AEG Protect A. 1400 VA - page 32

    32 7.1 Battery Replacement ATTENTIO N: A batter y can cause an electr ic shock, and represents a consid erable hazard if ha ndled incorrectl y. The f ollowing precaution s should b e taken before the batter y is renewed. ♦ Switch of f the UPS and dis connect the m ains cable from the sock et. ♦ Rem ove any rings, wristwat ch and other m etallic ...

  • AEG Protect A. 1400 VA - page 33

    33 EN Once you hav e l ifted off the ac tual front pane l ( which you c an put down on t op of the u nit as s hown – never d isconnect th e flat-ribbon cable) n ext rem ov e the int ernal battery cove r. Now slowly p ull the two batter y block s out f orwards until yo u can acces s the c able plug c onnections. Firs t disconnect the negative term ...

  • AEG Protect A. 1400 VA - page 34

    34 8 Sto rage and Disposal Storage Long storag e tim es without charging or discharging the ba tter y at regular interva ls ma y lead to perm anent damage of the batter y. If the batter y is store d at ro om temperature (20° C to 30° C) it will autom atically disc harge at a rate of 3-6% per m onth due to internal reactions. Storing the batter y ...

  • AEG Protect A. 1400 VA - page 35

    35 EN 9 List of T erms 9.1 Technical Terminology AVR Automatic Voltage Reg ulation Automatic voltage regulation against mains voltage deviations DC/DC booster Circuit technology for increasing a D C voltage to a higher voltage level EPO E mergency Pow er Off Device for emerg ency shutdown PFC P ower Factor Correction Circuit technology for minimisi ...

  • AEG Protect A. 1400 VA - page 36

    36 Guarantee Certificate T y pe: …….……… ……….…....... ................................ ............... Unit number:…….…… ………….…....... ................................. ............ Date of purchase:…….… …………….….... .......................... ................... Dealer stam p / signature Errors a ...

Fabricant AEG Catégorie Uninterruptible power supply (

Les documents que nous recevons du fabricant de l'appareilAEG Protect A. 1400 VA peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques AEG
- manuels d’utilisations Protect A. 1400 VA
- fiches produit AEG
- dépliants
- ou étiquettes-énergie AEG Protect A. 1400 VA
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation AEG Protect A. 1400 VA.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation AEG Protect A. 1400 VA, manuels d’entretien, brefs manuels ou manuels de l’utilisateur AEG Protect A. 1400 VA. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit AEG Protect A. 1400 VA.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil AEG Protect A. 1400 VA, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser AEG Protect A. 1400 VA par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs AEG Protect A. 1400 VA.

Le manuel d’utilisation complet AEG, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel AEG Protect A. 1400 VA - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières AEG Protect A. 1400 VA, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lAEG Protect A. 1400 VA qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil AEG Protect A. 1400 VA - qui devraient nous aider dans les premières étapes lors de l'utilisation AEG Protect A. 1400 VA
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de AEG Protect A. 1400 VA
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service AEG Protect A. 1400 VA dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de AEG Protect A. 1400 VA?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec AEG Protect A. 1400 VA, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec AEG Protect A. 1400 VA il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)