    SER VICE TECHNICAL GUIDE CONTENTS 1. MS MICROPROCESSOR CONTROL ·················· 4 2. MSZ, MSY MICROPROCESSOR CONTROL ······ 7 3. MXZ MICROPROCESSOR CONTROL ·············· 21 4. MFZ MICROPROCESSOR CONTROL ·············· 35 SPLIT -TYPE AIR CONDITIONERS No. OBT16 REVISED EDITION-H Please void OBT16 ...

  • Mitsumi electronic -1 - page 2

    2 Revision A: • MXZ-3A30NA- 1 has been added. Revision B: • MXZ-2A20NA- 1 , MXZ-4A36NA, MSZ-FD, MSZ-D and MSY -D have been added. Revision C: • MXZ-2A20NA- 2 has been added. Revision D: • MSZ-GA•NA and MSY -GA•NA have been added. Revision E: • MSZ-FE•NA, MSZ-GE•NA, MSY -GE•NA and MXZ-B•NA have been added. Revision F: • MXZ-2 ...

  • Mitsumi electronic -1 - page 3

    3 1. MS MICROPROCESSOR CONTROL ·································································································· ················· 4 Indoor unit models Outdoor unit models MS-A09/12W A MU-A09/12W A 1-1. COOL OPERA TION ...

  • Mitsumi electronic -1 - page 4

    4 1-1. COOL ( ) OPERA TION 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat's OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature. 1-2. DR Y ( ) OPERA T ...

  • Mitsumi electronic -1 - page 5

    5 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature. 2. Indoor fan speed control Indoor fan operates at the set speed by F AN SPEED CONTROL button. When thermostat OFF (compressor OFF), fan speed becomes V ery Low . In AUTO the fan speed is as follows. 4. Coil frost prevention Coil frost ...

  • Mitsumi electronic -1 - page 6

    6 1-3. AUTO V ANE OPERA TION 1. Horizontal vane ECONO COOL ( ) operation (ECONOmical operation) When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.6°F (2°C) higher than that in COOL mode. Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger (indoor coil thermist ...

  • Mitsumi electronic -1 - page 7

    7 2-1. COOL ( ) OPERA TION 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat's OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature. ON -1.8°F(-1°C) or ...

  • Mitsumi electronic -1 - page 8

    8 2-2. DR Y ( ) OPERA TION Set temperature is as shown on the right chart. The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room tem- perature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature d ...

  • Mitsumi electronic -1 - page 9

    9 (2) Cold air prevention control MSZ-A09/12/15/17 MSZ-FD MSZ-FE MSZ-D MSZ-GE When the compressor is not operating, ( ) if the temperature of room temperature thermistor is less than 66°F (19°C), the fan stops. ( ) if the temperature of room temperature thermistor is 66°F (19°C) or more and ( ) if the temperature of indoor coil thermistor is le ...

  • Mitsumi electronic -1 - page 10

    10 set position set speed set position set speed Indoor fan Compressor normal Outdoor fan R.V . coil (21S4) OFF (COOL) OFF Maximum frequency horizontal Horizontal vane V ery Low (temperature of indoor coil thermistor > 64 °F) 30 seconds 30 seconds 30 seconds 40 seconds 5 seconds 5 seconds 40 seconds OFF (39°C) (18°C) OFF OFF ON (HEA T) ON ON ...

  • Mitsumi electronic -1 - page 11

    11 (2) Mode change In case of the following conditions, the operation mode is changed. COOL mode changes to HEA T mode when 15 minutes have passed with the room temperature 2 - 4°F (1 - 2°C) below the set temperature. HEA T mode changes to COOL mode when 15 minutes have passed with the room temperature 2 - 4°F (1 - 2°C) above the set temperatur ...

  • Mitsumi electronic -1 - page 12

    12 <SWING operation> In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next horizontal blow time is decided ...

  • Mitsumi electronic -1 - page 13

    13 MUZ-A24 MUY -A24 MUZ-D MUY -D MUZ-FE18 MUZ-GA MUY -GA MUZ-GE24 MUY -GE24 POWER SUPPL Y NOISE FIL TER CIRCUIT RESISTOR RELA Y SMOOTHING CAP ACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N INTELLIGENT POWER MODULE POWER F ACTOR CORRECTION MODULE U W MS 3~ V + Function of main parts NAME FUNCTION INTELLIGENT POWER MODULE It supplies 3-phase ...

  • Mitsumi electronic -1 - page 14

    14 3. Purpose of P AM adoption P AM (Pulse Amplitude Modulation) has been adopted for the ef fi ciency improvement and the adaptation to IEC harmonic cur- rent emission standard Outline of simple partial switching method In conventional inverter models, DIODE MODULE recti fi es AC voltage to DC voltage, SMOOTHING CAP ACITOR makes its DC waveform ...

  • Mitsumi electronic -1 - page 15

    15 4. Intelligent power module INTELLIGENT POWER MODULE consists of the following components · IGBT (x6): Converts DC waveform to 3-phase AC waveform and outputs it. · Drive Circuit: Drives transistors. · Protection circuit: Protects transistors from overcurrent. Since the above components are all integrated in INTELLIGENT POWER MODULE, INTELLIG ...

  • Mitsumi electronic -1 - page 16

    16 2-7-4. Characteristics of sine wave control in case of brushless DC motor ● Although ordinary 3-phase induction motor requires energy to excite the magnetic fi eld of rotor , brushless DC motor does not need it. So, higher ef fi ciency and torque are provided. ● This control provides the most ef fi cient waveform corresponding to the rota ...

  • Mitsumi electronic -1 - page 17

    17 2-8. OPERA TIONAL FREQUENCY CONTROL OF OUTDOOR UNIT 1. Outline The operational frequency is as following: First, the target operational frequency is set based on the difference between the room temperature and the set tempera- ture. Second, the target operational frequency is regulated by discharge temperature protection, high pressure protectio ...

  • Mitsumi electronic -1 - page 18

    18 (2) T ime chart OFF T ime Ti m e ON Operational frequency of the compressor Commanded to open Standard opening degree Opening degree is corrected according to discharge temperature. (Refer to (3)) Positioning Air conditioner ON Air conditioner OFF (thermostat off) LEV opening degree About 15 minutes 2-9. EXP ANSION V AL VE CONTROL (LEV CONTROL) ...

  • Mitsumi electronic -1 - page 19

    19 (3) Control data F E D C B A T arget discharge temperature Operational frequency of the compressor 30 50 70 90 1 10 130 23 38 53 69 84 99 (Hz) (Hz) ( Other models ) ( MUZ-FE18 MUZ-GE24 MUY -GE24 ) (a) Reference value of target discharge temperature COOL / HEA T ( MUZ ) °F/°C Applied model A B C D E F MUZ-A09/12 COOL 122/50 127/53 140/60 151/66 ...

  • Mitsumi electronic -1 - page 20

    20 2. Pre-heat control ON condition (1) Pre-heat control is turned ON for 15 or 30 minutes after the breaker is turned ON. (2) 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 minutes and turned OFF for 30 minutes. This is repeated as shown in the graph until the breaker is turned OFF . When the defrost thermistor reads ...

  • Mitsumi electronic -1 - page 21

    21 3-1. INVERTER SYSTEM CONTROL POWER SUPPL Y NOISE FIL TER CIRCUIT RESISTOR RELA Y SMOOTHING CAP ACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N INTELLIGENT POWER MODULE POWER F ACTOR CORRECTION MODULE U W MS 3~ V + 3-1-1. Inverter main power supply circuit Function of main parts NAME FUNCTION INTELLIGENT POWER MODULE It supplies 3-phase A ...

  • Mitsumi electronic -1 - page 22

    22 3. Power factor improvement Booster coil reactor and POWER F ACTOR CORRECTION MODULE rectify AC to DC and control its voltage. In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. POWER F ACTOR CORRECTION MODULE and reactor stabilize the voltage of DC supplied to inverter circuit and make its wavefo ...

  • Mitsumi electronic -1 - page 23

    23 3-2. EXP ANSION V AL VE CONTROL (LEV CONTROL) Linear expansion valve (LEV) is controlled by “Thermostat ON” commands given from each unit. Indoor unit status LEV opening Stop of all indoor unit Opening before stop → 500 pulses in 15 minutes When outdoor unit is operating, some indoor units stop and some operate. COOL: 5 pulses (full closed ...

  • Mitsumi electronic -1 - page 24

    24 In COOL mode, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super heat) at the heat exchanger , and when temperature difference develops, the indoor coil thermistors adjust LEV opening to diminish the super heat. This action is called Evaporation T emperature Protection. Indoor heat exchanger (MXZ-3A30NA) ...

  • Mitsumi electronic -1 - page 25

    25 23 54 69 84 100 1 15 131 146 38 14 32 41 50 59 68 77 86 MXZ-2A/2B MXZ-3A/4A 23 Compressor operating frequency (Hz) 4Hz 01 02 03 04 05 06 07 08 09 10 LEV Opening (code) Determination of LEV standard opening in each indoor unit • The standard opening is on the straight line, which connects an each standard point in the section where divided into ...

  • Mitsumi electronic -1 - page 26

    26 MXZ-3A30NA- 1 MXZ-4A36NA MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA Exclusive LEV Standard opening (pulse) LEV Opening (code) 123456789 1 0 COOL 126 130 134 138 150 160 170 180 190 200 HEA T 248 248 258 266 274 280 286 292 300 306 Difference in capacity Difference in operation number Code3,4 Code5,6 Code7,8 Code9,10 Code1 1,12 Code13,14 Code15or above 23 ...

  • Mitsumi electronic -1 - page 27

    27 (1) LEV opening correction by discharge temperature The target discharge temperature is determined according to frequency zone and number of operation unit of the com- pressor . <Correction> COOL DRY HEA T Discharge temperature ● 2 ● 2 ● Each correction • (Each gas pipe temperature thermistor - Minimum gas pipe temperature thermist ...

  • Mitsumi electronic -1 - page 28

    28 Correct the LEV opening according to the difference between target discharge temperature and discharge temperature. (2) Separate correction (COOL,DRY) (Correction by the separate super heat) a) Correct the LEV separately by temperature difference between each gas pipe temperature and the minimum gas pipe temperature of all. Calculate each super ...

  • Mitsumi electronic -1 - page 29

    29 3-3. OPERA TIONAL FREQUENCY RANGE b) Correct the LEV separately by temperature difference “ ∆ R T” between main/sub indoor coil thermistor . ∆ RT (°F/°C) LEV opening correction (pulse) 10.8/6 ∆ RT 2 7.2/4 ∆ RT < 10.8/6 1 ∆ RT < 7.2/4 1 In addition, decrease the target discharge temperature corresponding ∆ RT . ∆ RT (°F ...

  • Mitsumi electronic -1 - page 30

    30 MXZ-3A30NA- 1 MXZ-4A36NA Number of operating unit Capacity code COOL (Hz) DRY (Hz) HEA T (Hz) Min. Max. Min. Max. Defrost 1 4 2 55 82 52 07 05 8 7 2 55 82 52 07 05 8 9,10 25 71 25 20 80 58 12 25 80 35 20 80 58 2 8 ~ 10 25 80 31 20 80 58 1 1 ~ 13 25 80 31 20 80 58 14 ~ 16 25 80 42 20 80 58 17 ~ 25 80 42 20 80 58 3 ( MXZ-3A ) 12 ~ 25 80 52 20 80 5 ...

  • Mitsumi electronic -1 - page 31

    31 3-4. HEA T DEFROSTING CONTROL (1) Starting conditions of defrosting When the following conditions a) ~ c) are satisfied, the defrosting starts. a) The defrost thermistor reads 26.6°F (-3°C) or less. b) The cumulative operation time of the compressor has reached any of the set values (defrost interval: 40-150 min- utes). c) More than 5 minutes ...

  • Mitsumi electronic -1 - page 32

    32 COOL Fan speed changes so that the condensing temperature stays within the target range. Fan speed Revolution per minutes (rpm) MXZ-2B20NA- 1 MXZ-3B MXZ-4B 1 100 100 2 150 150 3 200 200 4 250 250 5 300 300 6 350 350 7 400 400 8 450 450 9 500 500 10 550 550 1 1 600 600 12 650 650 13 700 700 14 750 750 HEA T Fan speed is switched according to the ...

  • Mitsumi electronic -1 - page 33

    33 1. Pre-heat control is turned ON for 15 or 30 minutes, after the breaker is turned ON. 2. 30 minutes after the unit is stopped, pre-heat control is turned ON for 15 or 30 minutes and turned OFF for 30 minutes. This is repeated as shown in the graph until the breaker is turned OFF . When the defrost thermistor reads less than 69.8°F (21°C), pre ...

  • Mitsumi electronic -1 - page 34

    34 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature and set temperature. 3-9. DR Y OPERA TION 3-10. HEA T OPERA TION 2. High pressure protection In HEA T operation the indoor coil thermistor detects the temperature of the indoor heat exchanger . The compressor opera- tional frequency is controlled to preve ...

  • Mitsumi electronic -1 - page 35

    35 4 MFZ MICROPROCESSOR CONTROL 3. Coil frost prevention Refer to MXZ MICROPROCESSOR CONTROL, COOL OPERA TION (3-8.2.). 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat's OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Refer to MXZ MICROP ...

  • Mitsumi electronic -1 - page 36

    36 1. Thermostat control Refer to MXZ MICROPROCESSOR CONTROL, HEA T OPERA TION (3-10.1.). 4-3. HEA T ( ) OPERA TION 2. Indoor fan speed control (1) Indoor fan operates at the set speed by F AN SPEED CONTROL button. In Auto the fan speed is as follows. 3. High pressure protection In HEA T operation, the indoor coil thermistor detects the temperature ...

  • Mitsumi electronic -1 - page 37

    37 4-5. INDOOR F AN MOTOR CONTROL (1) Rotational frequency feedback control The indoor fan motor is equipped with a rotational frequency sensor , and outputs signal to the microprocessor to feed- back the rotational frequency . Comparing the current rotational frequency with the target rotational frequency (Super High, High, Med., Low), the micropr ...

  • Mitsumi electronic -1 - page 38

    38 4-6. AUTO V ANE OPERA TION Horizontal vane (1) Cold air prevention in HEA T operation When any of the following conditions occurs in HEA T operation, the vane angle changes to V ertical position automati- cally to prevent cold air blowing on users. Compressor is not operating. Defrosting is performed. Indoor coil thermistor reads 75.2°F or belo ...

  • Mitsumi electronic -1 - page 39

    39 ...

  • Mitsumi electronic -1 - page 40

    New publication, effective Jan. 201 1 Specifications subject to change without notice. HEAD OFFICE: TOKYO BLDG.,2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAP AN © Copyright 2006 MITSUBISHI ELECTRIC CO.,L TD Distributed in Jan. 201 1. No. OBT16 REVISED EDITION-H Distributed in Sep. 2010. No. OBT16 REVISED EDITION-G 6 Distributed in Mar . 2010. ...

Fabricant Mitsumi electronic Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilMitsumi electronic -1 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Mitsumi electronic
- manuels d’utilisations -1
- fiches produit Mitsumi electronic
- dépliants
- ou étiquettes-énergie Mitsumi electronic -1
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Mitsumi electronic -1.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Mitsumi electronic -1, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Mitsumi electronic -1. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Mitsumi electronic -1.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Mitsumi electronic -1, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Mitsumi electronic -1 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Mitsumi electronic -1.

Le manuel d’utilisation complet Mitsumi electronic, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Mitsumi electronic -1 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Mitsumi electronic -1, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lMitsumi electronic -1 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Mitsumi electronic -1 - qui devraient nous aider dans les premières étapes lors de l'utilisation Mitsumi electronic -1
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Mitsumi electronic -1
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Mitsumi electronic -1 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Mitsumi electronic -1?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Mitsumi electronic -1, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Mitsumi electronic -1 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)