Manuel d’utilisation KMC BAC-10000

28 pages 1.33 mb
Télécharger

Aller à la page of 28

Summary
  • KMC BAC-10000 - page 1

    B AC-10000 Series 1 Operation Guide, Rev . J Oper ation Guide B A C-10000 Series FlexStat ™ B A Cnet Progr ammable T hermostats Contents Over vie w ................................................................ 2 Applications and Installation ................................... 2 Oper ation (Basic) .............................................. ...

  • KMC BAC-10000 - page 2

    B AC-10000 Series 2 Operation Guide, Rev . J Ov er vie w The KMC FlexStat series of intelligent temperature/ humidity/occupancy-sensing, w all-mounted, ther- mostat/controllers are native BACnet Advanced Application Controllers (B-AAC) for use in a BAC- net system. The FlexStat simplies networked zone control for common packaged HV AC equipment, ...

  • KMC BAC-10000 - page 3

    B AC-10000 Series 3 Operation Guide, Rev . J WED 11/19 3:20 PM COOL: OCC: FAN: HUM: 36% RH Oper ation (Basic) Enter Button Right /Menu Button Left /Ov erride Button Down /Setpoint Button Up /Setpoint Button Home, Main Menu, and Ov erride Screens Menu Override Setpoint Home Screen Configuration Screens MAIN MENU ABOUT ADVANCED ALARM DATE/TIME SCHED ...

  • KMC BAC-10000 - page 4

    B AC-10000 Series 4 Operation Guide, Rev . J Configur ation (Initial Setup) NOTE: Menus shown in this document reect rmware version R1.3.0.4 or later . Actual context-sensitive screens are dependent on rmware version, FlexStat model, and options selected. NOTE: If appear at the top of the screen (such as in the Main Menu), scroll up or do ...

  • KMC BAC-10000 - page 5

    B AC-10000 Series 5 Operation Guide, Rev . J Adv anced Menu ADVANCED APPLICATION CB PROGRAMS COMMUNICATION DATE/TIME DEVICE INPUTS LIMITS The Adv anced Menu displays v arious submenus. Not all submenus can be seen on the screen at one time. Scroll up or down to see additional submenus. T o select the desired submenu, press: 1. Up / Down to move. ...

  • KMC BAC-10000 - page 6

    B AC-10000 Series 6 Operation Guide, Rev . J Sensor Setup SENSOR SETUP IN 2: DISCH AIR TEMP The Input 2 sensor (AI2) can be congured for discharge air temperature (T ype III thermistor is the default), fan status (dry contact), or unused. • If set for discharge air temperature, the sensor can be calibrated and changed from the default T ype II ...

  • KMC BAC-10000 - page 7

    B AC-10000 Series 7 Operation Guide, Rev . J (Adv anced) B A Cnet Communications COMMUNICATIONS MAC ADDRESS: BAUD RATE: 38400 MAX MAS TER: 127 1 T o set parameters for BACnet MS/TP EIA-485 communications, press: 1. Up / Down to move among entries. 2. Enter to select. NOTE: The Max Master is the highest MAC address a device will aempt to lo ...

  • KMC BAC-10000 - page 8

    B AC-10000 Series 8 Operation Guide, Rev . J (Adv anced) T emp. Setpoint Limits LIMITS OCC MIN CL G: OCC MAX HTG: 76° F UNOCC MIN CL G: 77° F UNOCC MAX HTG: 65° F 71° F T o set the minimum and maximum allowed user/ operator setpoint v alues, press: 1. Up / Down to move among entries. 2. Enter to select. 3. Right / Le to move among v ...

  • KMC BAC-10000 - page 9

    B AC-10000 Series 9 Operation Guide, Rev . J (Adv anced) Security Lev els and P asswor ds SECURITY ACCESS LEVEL S PASSWORDS ACCESS LEVEL S SETPOINT ADJ: MAIN MENU: ADMIN S YS TEM MODE: OPER OCC OVERRIDE: USER F AN OCC/UNOCC: OPER NONE PASSWORDS USER: OPERATOR: ADMIN: 1 0 0 0 1 2 3 4 5 6 7 8 Access to the Main Menu, Setpoint Adjust, and System/Occup ...

  • KMC BAC-10000 - page 10

    B AC-10000 Series 10 Operation Guide, Rev . J (Adv anced) T est TES T L CD/KEY TEST The test menu merely tests the display’ s pixels and key functions. 1. Up / Down to move among entries. 2. Enter to select and exit. (Adv anced) T rend Logs TREND L OGS TREND 1: TREND 2: TRUE TREND 3: F ALSE TREND 4: F ALSE TREND 5: F ALSE TREND 6: F ALSE TR ...

  • KMC BAC-10000 - page 11

    B AC-10000 Series 11 Operation Guide, Rev . J Date/T ime DATE/TIME DATE: TIME: 1:43:59 PM APR 11 2009 T o enter date and time information (only), press: 1. Up / Down to move among entries. 2. Enter to select. 3. Right / Le to move among v alue elds. 4. Up / Down to increment/decrement v alue. More options (such as UTC oset and ...

  • KMC BAC-10000 - page 12

    B AC-10000 Series 12 Operation Guide, Rev . J HOLIDAY S HOL1: HOL2: MAR 21 2009 HOL3: MAY 26 2009 HOL4: JUL Y 4 2009 HOL5: SEPT 1 2009 HOL6: NOV 2 7 2009 HOL7 : NOV 28 2009 JAN 1 2009 The Holiday entries will override the normal occupied weekly schedule entries and keep those days’ seings at their setback values. Setback v alues are entered in ...

  • KMC BAC-10000 - page 13

    B AC-10000 Series 13 Operation Guide, Rev . J System Setup SYS TEM S YS TEM ENABLE: OCC OVRIDE (HRS): 1.0 INACTIVITY (SECS): 60 DISPL AY BLANKIN G: NO AUTO T o adjust the system conguration values, such as system enable (auto, o, heat, or cool), occupancy override time, and display inactivity time-out: 1. Up / Down to move among entries. 2 ...

  • KMC BAC-10000 - page 14

    B AC-10000 Series 14 Operation Guide, Rev . J Resetting the FlexStat T ypes of Reset If the FlexStat is not operating correctly or if a low limit alarm has occurred , the FlexStat should be reset (reinitialized). Any reset interrupts normal op- eration, and three types of reset exist: • A warm start is generally the least disruptive op- tion (res ...

  • KMC BAC-10000 - page 15

    B AC-10000 Series 15 Operation Guide, Rev . J Restore F actor y Restore Factory (restoring the FlexStat to the factory seings) does the following: • Clears present v alues. • Restores the object database/conguration to the defaults. • Restarts the controller ’ s (factory installed) Con- trol Basic programs. NOTE: T h e M A C a d d r e ...

  • KMC BAC-10000 - page 16

    B AC-10000 Series 16 Operation Guide, Rev . J BA Cnet MS/TP Network Communication Connect the network wiring and set the EOL switch- es accordingly . (See the Installation Guide for wiring and end-of-line switch information.) From the FlexStat menus, adjust the device instance number , the MAC address, and baud rate from the defaults as necessary . ...

  • KMC BAC-10000 - page 17

    B AC-10000 Series 17 Operation Guide, Rev . J T roubleshooting Alarm Issues Alarm, (F alse) F an F ail • Check conguration. Be sure the Fan Status option is not selected when there is no sensor/ switch for it. • Check that the IN2 (fan status) input pull-up resistor switches are fully latched in the correct positions. Any passiv e, dry conta ...

  • KMC BAC-10000 - page 18

    B AC-10000 Series 18 Operation Guide, Rev . J Co v er and Displa y Issues Cov er Binds on Bac kplate • Carefully remove the FlexStat cov er from the backplate and inspect for bent pins and/or termi- nal socket connectors. If cover pins are bent, use a needle-nose pliers to straighten them. If socket connectors are bent, use a pointed object (such ...

  • KMC BAC-10000 - page 19

    B AC-10000 Series 19 Operation Guide, Rev . J Input, Sensor , and V alue Issues Input V alues Are Outside the Expected Range • Check that ALL the input pull-up resistor switches are fully latched in the correct positions. See the Connections and W iring section of the relev ant BAC-10000 Series Installation Guide. A single incorrect switch positi ...

  • KMC BAC-10000 - page 20

    B AC-10000 Series 20 Operation Guide, Rev . J F an Does Not Run NOTE: The animated fan icon is coupled with BV18 in the packaged programming (not the actual fan output terminal). • Select Occupied mode from the Home Menu— see H/C, Fan, Occupancy, and Override on page 3 . • Override the fan to On from the Home Menu— see H/C, Fan, Occupancy, ...

  • KMC BAC-10000 - page 21

    B AC-10000 Series 21 Operation Guide, Rev . J +B –A IN4 IN3 GND IN2 Common / – / C Phase / / R Analog 9 GND 7–9 Analog 8 Analog 7 Rela y 6 SC 4–6 Rela y 5 Rela y 4 Rela y 3 SC 1–3 Rela y 2 Rela y 1 Outputs NO TE: V alues Sho wn Are Appr o ximate! BA Cnet MS/TP Network Inputs 24 V AC NO TE: SC = Switched (Relay) Common, Should Hav e the Ph ...

  • KMC BAC-10000 - page 22

    B AC-10000 Series 22 Operation Guide, Rev . J Firmw are Upgr ade The existing version of rmw are can be viewed from the About the FlexStat screen. (See About the Flex- Stat on page 4 ). Firmw are in the FlexStat can be upgraded using a PC and a KMD-5699 rmw are ash upgrade kit av ailable from KMC Controls. (For full upgrade instructions, s ...

  • KMC BAC-10000 - page 23

    B AC-10000 Series 23 Operation Guide, Rev . J Important Notices The KMC logo and T otalControl are registered trademarks and BACstage is a trademark of KMC Controls, Inc. All rights reserv ed. No part of this publication may be reproduced, transmied, tran- scribed, stored in a retriev al system, or translated into any language in any form by any ...

  • KMC BAC-10000 - page 24

    B AC-10000 Series 24 Operation Guide, Rev . J Reference Common acronyms and abbreviations in FlexStat and related documents include: amp = amperes A = amperes AAC = Adv anced Application Controller A/C = air conditioning AC = alternating current AHU = air handling unit avg. = average A WG = American W ire Gauge BACnet = Building Automation Control ...

  • KMC BAC-10000 - page 25

    B AC-10000 Series 25 Operation Guide, Rev . J For denitions of v arious terms in this document, refer to the aw ard-winning pocket-sized Green Building and Con- trols Glossary (SB-046) . A hyperlinked online version can be downloaded from the Brochures section of KMC Controls web site, www.kmccontrols.com . Some of the more important glossary te ...

  • KMC BAC-10000 - page 26

    B AC-10000 Series 26 Operation Guide, Rev . J Index Symbols 4 x 4 Hand y Box Mounting Plate: 22 A Abbreviations: 24 About the FlexStat: 4 Access Levels, P assword: 9 Accessories: 22 Acronyms: 24 Adjustment. See Configuration; Ov erride; Setpoint Administrator P assword: 9 Ad v anced Menu: 5 Alarms: 5 , 6 , 11 , 17 Analog Outputs: 14 , 20 Applicati ...

  • KMC BAC-10000 - page 27

    B AC-10000 Series 27 Operation Guide, Rev . J G Glossary , Green Buildings Controls: 25 H Heat, Cool, A uto, Off (System Enable): 13 HMO-10000 Mounting Plate: 22 Home (T emperature Displa y) Screen: 3 Horizontal Hand y Box Mounting Plate: 22 HPO-0044 Cov er Screw: 22 Humidity Alarm: 11 Dehumidification Setpoint: 13 Setup: 5 T rend Log: 10 I IN2: 6 ...

  • KMC BAC-10000 - page 28

    B AC-10000 Series 28 Operation Guide, Rev . J © 2010 KMC Controls, Inc. 913-019-02J KMC Controls, Inc. 19476 Industrial Drive, New P aris, IN 46553 574.831.5250 www .kmccontrols.com info@kmccontrols.com Setpoints Adjustment: 3 , 13 All: 13 T emperature (Only): 3 T roubleshooting: 19 Setup and Configuration: 4 SP-001 Screwdriv er: 22 Space Humidit ...

Fabricant KMC Catégorie Thermostat

Les documents que nous recevons du fabricant de l'appareilKMC BAC-10000 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques KMC
- manuels d’utilisations BAC-10000
- fiches produit KMC
- dépliants
- ou étiquettes-énergie KMC BAC-10000
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation KMC BAC-10000.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation KMC BAC-10000, manuels d’entretien, brefs manuels ou manuels de l’utilisateur KMC BAC-10000. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit KMC BAC-10000.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil KMC BAC-10000, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser KMC BAC-10000 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs KMC BAC-10000.

Le manuel d’utilisation complet KMC, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel KMC BAC-10000 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières KMC BAC-10000, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lKMC BAC-10000 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil KMC BAC-10000 - qui devraient nous aider dans les premières étapes lors de l'utilisation KMC BAC-10000
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de KMC BAC-10000
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service KMC BAC-10000 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de KMC BAC-10000?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec KMC BAC-10000, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec KMC BAC-10000 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)