    INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE AIR CONDITIONERS MODELS W A381 W A423 W A484 W A491 W A602 Manual : 2100-398A Supersedes: 2100-398 File: V olume III T ab 16 Date: 05-28-02 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. © Copyright 2002 ...

  • Bard WA602 - page 2

    Contents Figures Figure 1 Unit Dimensions ...................................... 3 Figure 2 Fresh Air Damper Assembly ................... 6 Figure 3 Mounting Instructions .............................. 8 Figure 4 Electric Heat Clearance .......................... 9 Figure 5 W all Mounting Instructions .................... 10 Figure 6 W all Mounting ...

  • Bard WA602 - page 3

    Manual 2100-398 Page 1 GETTING OTHER INFORMA TION AND PUBLICA TIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Electrical Code ...................... ANSI/NFPA 70 ...

  • Bard WA602 - page 4

    Manual 2100-398 Page 2 W ALL MOUNT GENERAL INFORMA TION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE W A 42 3 – A 10 X N X X X A NOTE: All vent options are without exhaust capability. May require separate field supplied barometric relief in building. TABLE 1 ELECTRIC HEAT TABLE s l e d o M A - 1 8 3 A W A - 3 2 4 A W A - 4 8 4 A W A - 1 9 4 A W A - 2 ...

  • Bard WA602 - page 5

    Manual 2100-398 Page 3 MIS-1262 FIGURE 1 UNIT DIMENSIONS l e d o M h t d i W ) W ( h t p e D ) D ( t h g i e H ) H ( y l p p u Sn r u t e R EF G I J K L M N O P Q R S T A BCB 8 3 A W 2 4 A W 8 4 A W 9 4 A W 0 6 A W 5 7 0 . 2 42 3 4 . 2 25 7 8 . 4 88 8 . 98 8 . 9 28 8 . 5 18 8 . 9 28 8 . 3 40 1 . 9 16 6 . 1 30 0 . 0 38 6 . 2 34 9 . 6 29 6 . 4 33 4 . ...

  • Bard WA602 - page 6

    Manual 2100-398 Page 4 j Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. k Based on 75 ° C copper wire. All wiring must conform to NEC and all local codes. l These “ Minimum Circuit Ampacity ” values are to be used for sizing the field power conductors. Refer to the National Electric ...

  • Bard WA602 - page 7

    Manual 2100-398 Page 5 j Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. k Based on 75 ° C copper wire. All wiring must conform to NEC and all local codes. l These “ Minimum Circuit Ampacity ” values are to be used for sizing the field power conductors. Refer to the National Electric ...

  • Bard WA602 - page 8

    Manual 2100-398 Page 6 FILTERS A one inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A one inch washable filter and two inch pleated filter are also available as optional accessories. The internal filter brackets a ...

  • Bard WA602 - page 9

    Manual 2100-398 Page 7 INST ALLA TION INSTRUCTIONS W ARNING Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage, injury or death. WALL MOUNTING INFORMATION 1. Two holes for the supply and return air openings must be cut through the wall as shown i ...

  • Bard WA602 - page 10

    Manual 2100-398 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS-416 ...

  • Bard WA602 - page 11

    Manual 2100-398 Page 9 FIGURE 4 ELECTRIC HEAT CLEARANCE SIDE SECTION VIEW OF SUPPL Y AIR DUCT FOR W ALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURF ACES. MIS-277 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is i ...

  • Bard WA602 - page 12

    Manual 2100-398 Page 10 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS MIS-548 MIS-549 SEE FIGURE 3 – MOUNTING INSTRUCTIONS SUPPLY AIR OPENING RETURN AIR OPENING RETURN AIR OPENING SUPPLY AIR OPENING BOTTOM MOUNTING BRACKET. MOUNT ON WALL BEFORE INSTALLING UNIT. RETURN AIR OPENING SUPPLY AIR OPENING WALL STRUCTURE FACTORY ...

  • Bard WA602 - page 13

    Manual 2100-398 Page 11 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS-550 ...

  • Bard WA602 - page 14

    Manual 2100-398 Page 12 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of el ...

  • Bard WA602 - page 15

    Manual 2100-398 Page 13 FIGURE 8 UNIT 24V TERMINAL BOARD MIS-1373D ...

  • Bard WA602 - page 16

    Manual 2100-398 Page 14 ST ART UP IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. HIGH PRESSURE SWITCH The WA381, WA484, WA491 and WA602 models are supplied with a remote reset high pressure switch. If tripped, this pressure switch may be reset by turning the thermostat off then back on ...

  • Bard WA602 - page 17

    Manual 2100-398 Page 15 SEQUENCE OF OPERATION COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase of constant air circulation. On all 230 vo ...

  • Bard WA602 - page 18

    Manual 2100-398 Page 16 REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. 3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws. FIGURE 9 FAN BLADE SETTING TROUBLESHOOTING 4. Unwire condenser fan motor. 5. Slide complete motor, f ...

  • Bard WA602 - page 19

    Manual 2100-398 Page 17 TABLE 9 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY V alues shown are for units equipped with standard 1 inch throwaway filter or 1 inch washable filter . Derate ESP by .15 for 2 inch pleated filters. l e d o M3 2 4 A W4 8 4 A W2 0 6 A W W K h g i H d e e p S w o L d e e p S h g i H d e e p S w o L d e e p S h g i H d e e p ...

  • Bard WA602 - page 20

    Manual 2100-398 Page 18 Low side pressure ± 2 PSIG High side pressure ± 5 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions. NOTE: Pressure table based on high ...

  • Bard WA602 - page 21

    Manual 2100-398 Page 19 TABLE 11 OPTIONAL ACCESSORIES WA381-A WA381-B WA381-C WA423-A WA423-B WA423-C WA484-A WA484-B WA484-C WA491-A WA491-B WA491-C WA602-A WA602-B WA602-C t r a P r e b m u Nn o i t p i r c s e D 5 0 A - 5 0 A W H E 8 0 A - 5 0 A W H E 0 1 A - 5 0 A W H E 5 1 A - 5 0 A W H E s e g a k c a P r e t a e H s e g a k c a P r e t a e H ...

Fabricant Bard Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilBard WA602 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Bard
- manuels d’utilisations WA602
- fiches produit Bard
- dépliants
- ou étiquettes-énergie Bard WA602
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Bard WA602.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Bard WA602, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Bard WA602. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Bard WA602.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Bard WA602, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Bard WA602 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Bard WA602.

Le manuel d’utilisation complet Bard, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Bard WA602 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Bard WA602, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lBard WA602 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Bard WA602 - qui devraient nous aider dans les premières étapes lors de l'utilisation Bard WA602
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Bard WA602
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Bard WA602 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Bard WA602?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Bard WA602, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Bard WA602 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)