    Manual 2100-511 Page 1 of 27 INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE HEA T PUMPS MODELS W18H1 W24H1 W30H1 W36H1 W42H1 W48H1 W60H1 Manual : 2100-51 1 Supersedes: NEW File: V olume III T ab 17 Date: 10-14-08 Bard Manufacturing Company , Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. © Copyright 2008 ...

  • Bard W24H1 - page 2

    Manual 2100-511 Page 2 of 27 Content s Figures Figure 1 Fresh Air Damper Assembly ................... 5 Figure 2 Unit Dimensions ...................................... 7 Figure 3A Mounting Instructions .............................. 8 Figure 3B Mounting Instructions - W18, W24, W30, W36 .... 9 Figure 3C Mounting Instructions - W42, W48, W60 ..... 1 ...

  • Bard W24H1 - page 3

    Manual 2100-511 Page 3 of 27 GETTING OTHER INFORMA TION AND PUBLICA TIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Ele ctrical Code ...................... ANSI/ ...

  • Bard W24H1 - page 4

    Manual 2100-511 Page 4 of 27 W ALL MOUNT GENERAL INFORMA TION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE W 42 H 1– A 10 X X X X X A NOTE: Vent options X, B and M are without exhaust capability. May require separate field supplied barometric relief in buildi ng. SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external sign ...

  • Bard W24H1 - page 5

    Manual 2100-511 Page 5 of 27 DUCT WORK All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conse ...

  • Bard W24H1 - page 6

    Manual 2100-511 Page 6 of 27 s s e c c A e c i v r e S r o f d e r i u q e R s e c n a r a e l C w o l f r i A r e s n e d n o C e t a u q e d A d n a S L E D O M E D I S T F E L E D I S T H G I R H 6 3 W , H 0 3 W , H 4 2 W , H 8 1 W " 5 1 " 0 2 H 0 6 W , H 8 4 W , H 2 4 W " 0 2 " 0 2 o t d e r i u q e R s e c n a r a e l C m u ...

  • Bard W24H1 - page 7

    Manual 2100-511 Page 7 of 27 *Optional top outlet (factory installed only) for W30H and W36H models only. FIGURE 2 ) l a n i m o N ( s t n e m e r i u q e R n o i t a l l a t s n I d n a l a r u t c e t i h c r A r o f t i n U c i s a B f o s n o i s n e m i D L E D O M H T D I W ) W ( H T P E D ) D ( T H G I E H ) H ( Y L P P U SN R U T E R AB C B ...

  • Bard W24H1 - page 8

    Manual 2100-511 Page 8 of 27 FIGURE 3A W18H1, W24H1 MOUNTING INSTRUCTIONS ...

  • Bard W24H1 - page 9

    Manual 2100-511 Page 9 of 27 FIGURE 3B W30H1, W36H1 MOUNTING INSTRUCTIONS ...

  • Bard W24H1 - page 10

    Manual 2100-511 Page 10 of 27 FIGURE 3C W42H1, W48H1, W60H1 MOUNTING INSTRUCTIONS ...

  • Bard W24H1 - page 11

    Manual 2100-511 Page 11 of 27 FIGURE 4 ELECTRIC HEAT CLEARANCE W30H1, W36H1, W42H1, W48H1, W60H1 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is important to insure that the 1/4 inch minimum sp acing is maintained at all point ...

  • Bard W24H1 - page 12

    Manual 2100-511 Page 12 of 27 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 – MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS, FIGURE 2, FOR ACTUAL DIMENSIONS IF REQUIRED IF REQUIRED ...

  • Bard W24H1 - page 13

    Manual 2100-511 Page 13 of 27 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS ...

  • Bard W24H1 - page 14

    Manual 2100-511 Page 14 of 27 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW ...

  • Bard W24H1 - page 15

    Manual 2100-511 Page 15 of 27 ST ART UP THESE UNITS REQUIRE R-410A REFRIGERANT AND POL YOL ESTER OIL. GENERAL: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant. 3. Use manifold gauges rated for R-410A (800 psi/250 psi low). 4. R-410A is a binary blend of H ...

  • Bard W24H1 - page 16

    Manual 2100-511 Page 16 of 27 ST ART UP (Continued) IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. HIGH & LOW PRESSURE SWITCH All W**H wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switch. If tripped, this pressure switch ...

  • Bard W24H1 - page 17

    Manual 2100-511 Page 17 of 27 SEQUENCE OF OPERATION COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. HEATIN ...

  • Bard W24H1 - page 18

    Manual 2100-511 Page 18 of 27 FIGURE 8 DEFROST CONTROL BOARD ...

  • Bard W24H1 - page 19

    Manual 2100-511 Page 19 of 27 TROUBLESHOOTING SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE 1. NOTE: A thorough understanding of the defrost cycle sequence is essential. Review that section earlier in this manual prior to troubleshooting the control. Turn on AC power supply to unit. 2. Turn thermostat blower switch to “fan on” – the ...

  • Bard W24H1 - page 20

    Manual 2100-511 Page 20 of 27 CHECKING TEMPERATURE SENSOR OUTSIDE UNIT CIRCUIT 1. Disconnect temperature sensor from board and from outdoor coil. 2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open. 3. Check resistance reading to chart of resistance. Use sensor ambient temperature. (Tolerance of ...

  • Bard W24H1 - page 21

    Manual 2100-511 Page 21 of 27 TROUBLESHOOTING FIGURE 9 FAN BLADE SETTING MIS-1724 TABLE 2 FAN BLADE DIMENSION REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. 3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws. 4. Unwire cond ...

  • Bard W24H1 - page 22

    Manual 2100-511 Page 22 of 27 TABLE 4A COOLING PRESSURE TABLE Low side pressure ± 4 PSIG High side pressure ± 10 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate charge we ...

  • Bard W24H1 - page 23

    Manual 2100-511 Page 23 of 27 TABLE 5 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductor ...

  • Bard W24H1 - page 24

    Manual 2100-511 Page 24 of 27 TABLE 6 RECOMMENDED AIRFLOW TABLE 7 INDOOR BLOWER PERFORMANCE l e d o M d e t a R * M F C d e t a R * P S E d e d n e m m o c e R e g n a R w o l f r i A d e e p S y r o t c a F n o i t c e n n o C H 8 1 W0 0 6 1 0 3 .5 2 7 - 5 7 5h g i H H 4 2 W0 0 80 2 .0 5 9 - 0 0 7h g i H H 0 3 W0 0 0 10 4 .0 0 3 1 - 0 3 9h g i H H ...

  • Bard W24H1 - page 25

    Manual 2100-511 Page 25 of 27 TABLES 8 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY TABLE 9 ELECTRIC HEAT s l e d o M1 - V 0 4 21 - V 8 0 23 - V 0 4 23 - V 8 0 23 - V 0 6 4 W Ks p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T B 47 . 6 10 5 6 3 14 . 4 10 4 2 0 1 58 . 0 25 6 0 7 11 . 8 10 0 8 2 1 64 . 4 10 0 5 0 25 . 2 10 6 3 5 12 . ...

  • Bard W24H1 - page 26

    Manual 2100-511 Page 26 of 27 W18H1-A W24H1-A W24H1-B W24H1-C W30H1-A W30H1-B W30H1-C W36H1-A W36H1-B W36H1-C W42H1-A W42H1-B W42H1-C W48H1-A W48H1-B W48H1-C W60H1-A W60H1-B W60H1-C TABLE 10 OPTIONAL ACCESSORIES r e b m u N t r a P 4 0 A - A 2 0 H W H EX 8 0 A - A 2 0 H W H EX 4 0 A - H 4 2 W H EX 8 0 A - H 4 2 W H EX 6 0 B - H 4 2 W H EX 5 0 A - 0 ...

  • Bard W24H1 - page 27

    Manual 2100-511 Page 27 of 27 TABLE 11 VENT & CONTROL OPTIONS W18, W24 W30, W36 W42, W48, W60 r e b m u N t r a Pn o i t p i r c s e D 4 1 - C M CT D O XXX 5 1 - C M C) y l n o e s a h P - 1 V 0 3 2 ( t i K t r a t S 1 XXX 1 1 1 K S) y l n o e s a h P - 1 V 0 3 2 ( t i K t r a t S 2 XXX 8 2 - C M CC A L XXX 2 - D A F Bd r a d n a t S - r e p m ...

Fabbricante Bard Categoria Heat Pump

I documenti che otteniamo dal fabbricante del dispositivoBard W24H1 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Bard
- manuali per l’uso W24H1
- schede prodotto Bard
- opuscoli
- o etichette energetiche Bard W24H1
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Bard W24H1.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Bard W24H1, manuali di manutenzione, brevi manuali o manuali utente Bard W24H1. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Bard W24H1.

Manuali per l’uso simili

Manuale completo del dispositivo Bard W24H1, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Bard W24H1 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Bard W24H1.

Il manuale per l’uso completo Bard, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Bard W24H1 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Bard W24H1, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Bard W24H1 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Bard W24H1 - che ci dovrebbe aiutare nei primi passi durante l'uso Bard W24H1
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Bard W24H1
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Bard W24H1 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Bard W24H1?

Utilizza il modulo sottostante

Se non hai risolto il problema con Bard W24H1 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Bard W24H1 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)