Summary
  • Liebert UPS - page 1

    U SER M ANUAL English 6 & 10 kVA 208V & 240V UPStation GXT™ ...

  • Liebert UPS - page 2

    2 IMPOR TANT SAFETY INSTRUCTIONS WARNING: Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source. Observe all cauti ons and warnings in this manual. Failure to do so MAY result in serious injury or death. Refer all UPS ...

  • Liebert UPS - page 3

    3 8. Never block or insert any object into the ventilation holes or other openings. 9. DO NOT CONNECT equipment that could overload the UPS or demand DC c urrent from the UPS, for example: electric drills, vacuum cleaners, laser printers, hairdryers or any appliance using half wave rectification. 10. Storing magnetic media on top of the UPS may res ...

  • Liebert UPS - page 4

    4 INTRODUCTION Congratulations on your choice of the UPStation GXT™ Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment. Upon generation, AC power is clean and stable. However, during transmission and distribution it may be subject t o voltage sags, spikes, or complete power ...

  • Liebert UPS - page 5

    5 MAJOR COMPONENTS EMI /RFI FILTERS These UPS components provide surge protection, and filter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the utility line and keep the sensitive equipment protected. RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT In normal opera ...

  • Liebert UPS - page 6

    6 STATIC BYPASS The UPStation GXT provides an alternate path for utility power to the connected load, in the unlikely event of a UPS malfunction. Should the UPS have an overload, over temperature, or UPS fai lure condition, the UPS automatically transfers the connected load to BYPASS providing the bypass voltage is within specification. BYPASS oper ...

  • Liebert UPS - page 7

    7 INSTALLATION These instructions are for use by competent personnel only. INSTALLATION CONSIDERATIONS Detailed instructions to help you install the UPS are provided in the following pages; however, you should give some considerati on to the proposed environment in which the UPS is to be installed, and carry out some preparatory work. UNPACKING AND ...

  • Liebert UPS - page 8

    8 Model AIRFLOW DISSIPATION* OUTPUT RATING** # Cfm m 3 h Watts K Btu/hr VA Watts GXT6000T 130 221 504 1.7 6000 4200 GXT10000T 270 459 840 2.8 10000 7000 * Increase dissipation 25% for 208X, and 240 X transformer models. ** Decrease output rating 10% for 208 and 208X model. ELECTRICAL INSTALLATION CONSIDERATIONS This UPS must be installed by compete ...

  • Liebert UPS - page 9

    9 Connecting the UPS Power cables Power cables connect to screw terminals on a terminal block that is located behind the rear mounted cable box (see figure). Permanent wiring must be routed to the cable box using approp riate materials as required by local codes. Connection of optional remote battery cabinets Full installation instructions are prov ...

  • Liebert UPS - page 10

    10 GXT6000T / 10000T - 208 UPS ONLY Models whose part number ends with a “208” are NOT fitted with an isolating output transformer and are NOT separately derived sources under the NEC. The output L1 terminal is connected to the input L1 terminal and must not be connected to ground at the UP S (see NEC 250 - 5d, 250 - 26, 250.91, 250.92). GXT600 ...

  • Liebert UPS - page 11

    11 NOTES FOR GXT6000T / 10000 T - 208 UPS ONLY 1. The installer must provide circuit breaker protection according to local codes. The UTILITY disconnect must be within sight of the UPS. Maintain service space around the UPS or use flexible conduit. 2. The installer must provide output distri bution panels and circuit breaker protection according to ...

  • Liebert UPS - page 12

    12 GXT6000T / 10000T - 208X UPS ONLY M odels whose part number ends with a “208X” are fitted with a single - phase isolating output transformer and are separately derived sources. The output neutral is already bonded to ground on the output terminals with a Bonding Jumper (see NEC 250 - 5d, 250 - 26, 250.91, 250.92). The output L1 and L2 termin ...

  • Liebert UPS - page 13

    13 NOTES FOR GXT6000T / 10000T - 208X UPS ONLY 1. The installer must provide circuit breaker protection according to local code s. The utility disconnect must be within sight of the UPS. Maintain service space around the UPS or use flexible conduit. 2. The installer must provide output distribution panels, circuit breaker protection, or emergency d ...

  • Liebert UPS - page 14

    14 GXT6000T / 10000T - 240X ONLY Models whose part number ends with a “240X” are fitted with a single - phase isolating output tr ansformer and are separately derived sources. The output neutral is already bonded to ground on the output terminals with a Bonding Jumper (see NEC 250 - 5d, 250 - 26, 250.91, 250.92). The output L1 and L2 terminals ...

  • Liebert UPS - page 15

    15 NOTES FOR GXT6000T / 10000T - 240X ONLY 1. The installer must provide circuit breaker protection according to local codes. Maintain service space around the UPS or use flexible conduit. 2. The installer must provide output distribution pan els, circuit breaker protection, or emergency disconnect switches according to local codes. Output circuits ...

  • Liebert UPS - page 16

    16 STABILIZERS / LEVELING FEET When the UPS is located in its final position before or after wiring, it is necessary to fit stabilizer brackets and, if necessary, adjust the leveling fe et. If the UPS is wired using a rigid wiring system, then movement of the UPS must be prevented by winding down the 4 leveling feet under the UPS as shown below. Fo ...

  • Liebert UPS - page 17

    17 FERRITE BEAD INSTALLATION When using either of the options below, to reduce th e risk of radio interference, fit the ferrite assemblies supplied with the UPS as follows: Serial Communications Attach the smaller enclosed ferrite bead clamp to the communication cable as shown in the drawing using the following directions: • Open the fe rrite bea ...

  • Liebert UPS - page 18

    18 COMMISSIONING THE UPS Output Voltage Selector Switches The Output Voltage Selector Switches, located on the rear of the UPS, are designed to allow selecting or changing the desired output voltage to mat ch the utility. The settings to choose from are 208, 220, 230 and 240 VAC output. NOTE: NEVER change the switch settings while UPS is on and pow ...

  • Liebert UPS - page 19

    19 CO NTROLS AND INDICATORS Fault Indicator (Red) The Fault indicator is illuminated if the UPS has detected a problem. Also, one or more of the load/battery level indicators may be illuminated (refer to Troubleshooting Guide). BYPASS Indicator (Amber) The BY PASS indicator is illuminated when the UPS is operating from BYPASS power. An alarm will s ...

  • Liebert UPS - page 20

    20 Load/Battery Level Indicators (4 Green, 1 Amber) The Load/Battery Level indicators have dual functions. During NORMAL mode operation LED indicators display the approximate electrical load placed upon the UPS; and during battery mode operation LED indicators display approximate battery capacity. The UPStation GXT is equipped with automatic and re ...

  • Liebert UPS - page 21

    21 Inpu t Breake r Outpu t Breake r Batter y Breake r Batter y Breake r GXT 6 & 10 k V A Component Diagra m 208 Models Show n Hardwire Terminal Block s Hardwir e Terminal Block s Intellislot Communications Por t T M Intellislot Communications Por t T M DB- 9 Communicaions Por t DB- 9 Communications Por t Breakers Inpu t Outpu t Adjustable level ...

  • Liebert UPS - page 22

    22 OPERATING MODES N ORMAL MODE OPERATION - UPS mode During normal operation, utility power provides energy to the UPS. The filters, the power factor correction circuit and the inverter process this power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state. The four green Leads indicate an ap ...

  • Liebert UPS - page 23

    23 BYPASS MODE OPERATION During BYPASS operation, utility power provides energy to your load and maintains the batteries in a fully charged state. The BYPASS will automatically p ower the load temporarily during overloads of the inverter, when diagnostics detect equipment problems, or when the operator selects BYPASS operation. The four green L ED ...

  • Liebert UPS - page 24

    24 MANUAL OPERATION WITH UTILITY AVAILABLE Under normal circumstances, the UPS will be operated with utility available. The UPS can operate in three possible modes with utility available: NORMAL MODE OPERATION - UPS ON LED will be on and the inverter will provide power to the load. BYPASS MODE OPERATION - BYPASS LED will be on and the bypass will p ...

  • Liebert UPS - page 25

    25 POWERING DOWN THE UPS WITH UTILITY AVAILABLE 1. Shutdown all connected load equipment. 2. Press the OUTPUT OFF/BYPASS button once until a "beep" is heard. The UPS ON LED will extinguish and t he BYPASS LED will light if the BYPASS voltage is within an acceptable range. The load is now powered through the BYPASS and there is no UPS prot ...

  • Liebert UPS - page 26

    26 POWERING UP THE UPS WITHOUT UTILITY 1. Ensure the load equipment is turned off, and all loads are pr operly connected to the UPS output. 2. Verify that the BATTERY, INPUT, AND OUTPUT circuit breakers remain closed. 3. Press the UPS ON/ALARM/BATTERY TEST button for at least one second until you hear the audible alarm emit a “double beep" t ...

  • Liebert UPS - page 27

    27 COMMUNICATIONS UPS MONITORING The UPStation GXT UPS has the capability of being monitored with stand alone computers, network workstations, network servers, o r UNIX hosts via the DB - 9 socket located on the rear of the UPS. This capability is used in applications requiring the UPS to provide status and power monitoring information to the compu ...

  • Liebert UPS - page 28

    28 COMMUNICATIONS INTERFACE PORT The UPStation GXT UPS contains a standard DB - 9 socket locat ed on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows: PIN ASSIGNMENT DESCRIPTION 1 Low Battery (open collector) 2 UPS TxD (typical RS - 232 levels) 3 UPS RxD (typical RS - 232 levels) 4 Remote Shutdown (5 - ...

  • Liebert UPS - page 29

    29 TROUBLESHOOTING The information below indicates various symptoms a user may encounter in the event the UPStation GXT develops a problem. Use this information to determine whether external factors cause the problem and how to remedy the situation. 1. The fault indicator will illuminate indicating the UPS detected a problem. 2. An alarm will sound ...

  • Liebert UPS - page 30

    30 AUDIBLE ALARM CONDITIONS CONDITION ALARM Battery mode (utility failure) One short beep every ten seconds Low battery Two short beeps every five seconds Output overload (bypass) One short beep every half second Over temperature (b ypass) One second beep every four seconds DC Bus over voltage (bypass) One second beep every four seconds PFC failure ...

  • Liebert UPS - page 31

    31 TROUBLESHOOTING GUIDE PROBLEM CAUSE SOLUTION Fault indicators and all load level LED's are illuminated UPS overloaded or load equipment is faulty Check load level display and remove non - essential loads. Recalculate lo ad VA and reduce number of loads connected to UPS. Check load equipment for faults. Fault indicators and diagnostic LED A ...

  • Liebert UPS - page 32

    32 MAINTENANCE The UPStation GXT UPS requires very little maintenance. The batteries are valve regulated, nonspillable, lead acid, and should be kept charged to obtain their designed life. The UPS continuously charg es the batteries when connected to the Utility supply. When storing the UPS for any length of time, it is recommended to apply power t ...

  • Liebert UPS - page 33

    33 SPECIFICATIONS MODEL NUMBER GXT6000T - 208 GXT10000T - 208 MODEL RATING VA/W (max) 5400 / 3780 9000 / 6300 DIMENSIONS: mm (in) Unit W x D x H 260 x 555 x 803 (10.3 x 21.9 x 31.6) 340 x 650 x 960 (13.4 x 25.6 x 37.8) Shipping W x D x H 400 x 850 x 1065 (15.8 x 33.5 x 41.9) 510 x 840 x 1235 (20.1 x 33.1 x 48.6) WEIGHT: kg (lbs) Unit 99 (218) 187 ( ...

  • Liebert UPS - page 34

    34 SPECIFICATIONS MODEL NUMBER GXT6000T - 208X GXT10000T - 208X MODEL RATING VA/W (max) 5400 / 3780 9000 / 6300 DIMENSIONS: mm (in) Unit W x D x H 260 x 555 x 803 (10.3 x 21.9 x 31.6) 340 x 650 x 960 (13.4 x 25.6 x 37.8) Shippin g W x D x H 400 x 850 x 1065 (15.8 x 33.5 x 41.9) 510 x 840 x 1235 (20.1 x 33.1 x 48.6) WEIGHT: kg (lbs) Unit 142 (313) 2 ...

  • Liebert UPS - page 35

    35 SPECIFICATIONS MODEL NUMBER GXT6000T - 240X GXT10000T - 240X MODEL RATING VA/W (max) 6000 / 4200 10000 / 7000 DIMENSIONS: mm (in) U nit W x D x H 260 x 555 x 803 (10.3 x 21.9 x 31.6) 340 x 650 x 960 (13.4 x 25.6 x 37.8) Shipping W x D x H 400 x 850 x 1065 (15.8 x 33.5 x 41.9) 510 x 840 x 1235 (20.1 x 33.1 x 48.6) WEIGHT: kg (lbs) Unit 139 (306) ...

  • Liebert UPS - page 36

    36 LIMITED WARRANTY Liebert Corporation extends the following LIMITED WARRANTY to the purchaser and to its customer (collectively referred to as the "Purchaser"): the enclosed Uninterruptible Power System (UPS) and components are free from defects in materials and workmanshi p under normal use, service, and maintenance FOR A PERIOD OF TWO ...

  • Liebert UPS - page 37

    Technical Support Global Services 1 - 800 - LIEBERT Applications U.S.A. 1 - 800 - 222 - 5877 Outside the U.S.A. 614 - 841 - 6755 U.K. +44 (0) 1793 553355 France +33 (0) 1 43 60 01 77 Germany +49 89 99 19 220 Italy +39 2 98250 1 Netherlands +31 (0) 475 503333 E - mail upstech@liebert.com W eb site http://www.liebert.com W orldwide FAX tech support + ...

Fabbricante Liebert Categoria Power Supply

I documenti che otteniamo dal fabbricante del dispositivoLiebert UPS possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Liebert
- manuali per l’uso UPS
- schede prodotto Liebert
- opuscoli
- o etichette energetiche Liebert UPS
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Liebert UPS.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Liebert UPS, manuali di manutenzione, brevi manuali o manuali utente Liebert UPS. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Liebert UPS.

Manuali per l’uso simili

Manuale completo del dispositivo Liebert UPS, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Liebert UPS dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Liebert UPS.

Il manuale per l’uso completo Liebert, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Liebert UPS - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Liebert UPS, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Liebert UPS che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Liebert UPS - che ci dovrebbe aiutare nei primi passi durante l'uso Liebert UPS
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Liebert UPS
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Liebert UPS in un dato paese, se il problema non può essere risolto da noi stessi.