    FOR YOUR SAFETY : This product must be inst alled and serviced by a professional service technician, qualified in hot water heater installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury , property damage, or death. Improper installation and/or operation wi ...

  • Laarsen Associates IW - page 2

    LAARS HEATING SYSTEMS Page 2 SECTION 1. General Information 1A. Introduction ................................................... 3 1B. Heater Identification ..................................... 3 1C. Flow Requirements ...................................... 4 1D. Water Chemistry ........................................... 4 SECTION 2. Installation ...

  • Laarsen Associates IW - page 3

    Mighty Therm Volume Water Heater Page 3 SECTION 1. General Information 1A. Introduction This manual provides information for the installation and operation of Laars volume water heaters. It is strongly recommended that all application and installation procedures be reviewed completely before proceeding with the installation. Consult the Laars facto ...

  • Laarsen Associates IW - page 4

    LAARS HEATING SYSTEMS Page 4 1C. Flow Requirements For proper operation, all low volume hot water heaters must have continuous flow through the heat exchanger when firing. The system pump must be capable of developing sufficient pressure to overcome the resistance of the heater plus the entire circulating system at the designed flow rate. 1D. Water ...

  • Laarsen Associates IW - page 5

    Mighty Therm Volume Water Heater Page 5 Figure 2. Typical Heater Installation with Base for Combustible Floors, Example A. Figure 3. Typical Heater Installation with Base for Combustible Floors, Example B. Figure 4. Typical Heater Installation with Base for Combustible Floors, Example C. Figure 5. Installation on Concrete Blocks or Tile. * When the ...

  • Laarsen Associates IW - page 6

    LAARS HEATING SYSTEMS Page 6 2B-1. Combustion Air Supply 1. The heater location must provide sufficient air supply for proper combustion and ventilation of the surrounding area as outlined in the latest edition of ANSI standard Z223.1, and any local codes that may be applicable. Inadequate combustion air supply may result in incomplete combustion, ...

  • Laarsen Associates IW - page 7

    Mighty Therm Volume Water Heater Page 7 maintain clearances and prevent physical damage and separation of joints. 4. Avoid ending heater vents near air conditioning or air supply fans. The fans can pick up exhaust flue products from the heater and return them inside the building, creating a possible health hazard. A minimum of 4 feet horizontal dis ...

  • Laarsen Associates IW - page 8

    LAARS HEATING SYSTEMS Page 8 4. The boiler and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig. The boiler must be isolated from the gas supply piping system by closing its individual manual gas shutoff valve during any pressure te ...

  • Laarsen Associates IW - page 9

    Mighty Therm Volume Water Heater Page 9 Special attention must be given to relief valve settings in installations where the heater is located on the ground floor of a tall building. The static pressure of the system is elevated and could cause the relief valve to leak. Where no special setting of the relief valve is ordered, the factory will furnis ...

  • Laarsen Associates IW - page 10

    LAARS HEATING SYSTEMS Page 10 2H. Pump Performance and Installation 1. The factory provided pump on PW heaters and the recommended field provided pump for model VW heaters are sized to provide proper circulation through the heater and heater-to- tank circulation loop (see Figures 11 and 12). If the heater-to-tank circulating loop does not contain m ...

  • Laarsen Associates IW - page 11

    Mighty Therm Volume Water Heater Page 11 Figure 11. Hot Water Supply System (Model VW & PW). With V ertical T ank With Horizontal T ank NOTES: Heavy line indicates Heater to Tank Circulating Loop. ...

  • Laarsen Associates IW - page 12

    LAARS HEATING SYSTEMS Page 12 CAUTION: 1. This piping arrangement is required on split systems to provide constant hot water temperatures. 2. Pipe size and length must conform to the recommendations for each heater model. 3. A loop circulator is required to maintain forced circulation in the building hot water piping system. Figure 13. Split System ...

  • Laarsen Associates IW - page 13

    Mighty Therm Volume Water Heater Page 13 Figure 15. Single Installation Piping Diagram, Model IW. Figure 14. Dual Installation Piping Diagram, Model IW. NOTES: 1. All water connections 2" N.P.T. models. 2. Drain valve per ASME requirements. 3. A loop circulator is required to maintain forced circulation in the building hot water piping system. ...

  • Laarsen Associates IW - page 14

    LAARS HEATING SYSTEMS Page 14 Figure 16. Two-Temperature Hot Water Supply System (Model VW or PW). With V ertical T ank With Horizontal T ank Legend B - Check Valve in Hot Water Supply to Tempering Valve C - Check Valve in Return Line from Building Loop D - Tempering Valve E - Venturi (Suction) Tee H - Throttling Valves in Building Loop Returns I - ...

  • Laarsen Associates IW - page 15

    Mighty Therm Volume Water Heater Page 15 Figure 17. Two-Temperature Hot Water Supply System with Vertical Tank for Models VW and PW Water Heaters. Legend B - Check Valve C - Check Valve D - Tempering Valve H - Throttling Valves in Building Loop Returns J - Circulating Pump for Return Loop K - Service Valves to Isolate Heater and Pump for Service ...

  • Laarsen Associates IW - page 16

    LAARS HEATING SYSTEMS Page 16 2 I . Water Pressure It is very important that water pressure in the system be maintained above 30 psi. If the system pressure should drop below this, the vapor pressure of water in the suction side of the pump can cause hammer and cavitation in the pump and damage the heater through lack of water circulation. If for a ...

  • Laarsen Associates IW - page 17

    Mighty Therm Volume Water Heater Page 17 proven to be lit. Whenever the pilot flame is interrupted, the main gas valve closes within 0.8 seconds. b. Electronically Supervised Standing Pilot System (System #16): When pilot flame fails, the ignition control module responds in less than 0.8 seconds and provides 100% safety shutdown. 2. Operating Contr ...

  • Laarsen Associates IW - page 18

    LAARS HEATING SYSTEMS Page 18 gas supply, the automatic safety shutoff devices must be checked. 1. Before beginning the tests, make sure the main manual gas valve, and any other heater firing valves are in the “OFF” position. 2. Make sure the heater’s power switch is in the “ON” position. After placing the manual pilot gas valve in the op ...

  • Laarsen Associates IW - page 19

    Mighty Therm Volume Water Heater Page 19 depressed for one minute then release. Once the pilot is lit, the power is supplied through the aquastat to the main gas valve. 2. To set the temperature and high-limit controls: When using a tank aquastat: Set the tank aquastat to the desired tank temperature. Set the heater temperature control 20°F higher ...

  • Laarsen Associates IW - page 20

    LAARS HEATING SYSTEMS Page 20 Lower the front of the burner (to avoid damaging pilot shield) then remove the burner tray. Caution Black carbon or green soot on a dirty heat exchanger can, under certain conditions, be ignited by a random spark or open flame. To prevent this unlikely occurrence, dampen the soot deposits with wet brush or fine water s ...

  • Laarsen Associates IW - page 21

    Mighty Therm Volume Water Heater Page 21 II. HEATER IS POUNDING, KNOCKING OR EMITTING STEAM FROM RELIEF VALVES. Possible Cause What To Do A. Low or no water flow. A. This condition is usually caused by lack of adequate water flow through heater. Check the following: 1. Is the heater wired into the pump circuit so that the heater cannot fire unless ...

  • Laarsen Associates IW - page 22

    LAARS HEATING SYSTEMS Page 22 Key Description Model Model Model Model Model Model Model Model Model N o 50 0 6 00 71 5 8 50 1010 1200 1430 1670 1825 1 T op Panel Assembly 10535701 10535702 10535703 10535704 10535705 10535706 10535707 10535708 10535709 2 S pacer , Flue Collector — — 10540800 10540800 10540800 10540800 10540800 10540800 3 End Pan ...

  • Laarsen Associates IW - page 23

    Mighty Therm Volume Water Heater Page 23 Figure 22. Parts Identification. NOTE: T emperature Control Wells - Inlet/Outlet Header 1. Firing Mode L, K, & C - 2 Dry Wells 2. Firing Mode H A. Natural Gas Boilers & Heaters 500 thru 850 - 2 Dry Wells 1010 thru 1430 - 3 Dry Wells 1670 thru 1825 - 4 Dry Wells B. Propane Gas Boilers & Heaters 50 ...

  • Laarsen Associates IW - page 24

    LAARS HEATING SYSTEMS Page 24 Key Description Model Model Model Model Model Model Model Model Model N o 50 0 6 00 71 5 8 50 1010 1200 1430 1670 1825 2 1 T ile, Heat Shield/Spcr , Frt. & Rr . 10560100 — — — — —— — — —— — — —— — — (2) 22 T ile, Heat Shield/Sp acer , Front —— 10547901 10547902 —— —— 1054 ...

  • Laarsen Associates IW - page 25

    Mighty Therm Volume Water Heater Page 25 Figure 23. Tile Assemblies. ...

  • Laarsen Associates IW - page 26

    LAARS HEATING SYSTEMS Page 26 Key Description Model Model Model Model Model Model Model Model Model N o 50 0 6 00 71 5 8 50 1010 1200 1430 1670 1825 4 3 Ignition Control, Electronic E0100900 E0100900 E0100900 E0100900 E0100900 E0100900 E0100900 E0100900 E0100900 4 4 T ransformer , 1 1 5V/24V E0086100 E0086100 E0086100 E0086100 E0086100 E0086100 E00 ...

  • Laarsen Associates IW - page 27

    Mighty Therm Volume Water Heater Page 27 Key Description Model Model Model Model Model Model Model Model Model N o 50 0 6 00 715 85 0 1010 1200 1430 1670 1825 6 4 Safety Gas V alve, On-Off, T wo St age (Nat) V0046600 V0046600 V004600 V004600 V0046700 V0046700 V0046700 V0046700 V0046800 65 Safety Gas V alve, On-Off, T wo St age (Pro) V0046600 V00466 ...

  • Laarsen Associates IW - page 28

    LAARS HEATING SYSTEMS Page 28 Key Description Model Model Model Model Model Model Model Model Model N o 50 0 6 00 71 5 8 50 1010 1200 1430 1670 1825 8 9 Plug, 3/4, Sq. Hd. P0027000 P0027000 P0027000 P0027000 P0027000 P0027000 P0027000 P0027000 P0027000 9 0 Pipe Extension 1/2" Female Pipe Extension 1/2" Male P0072300 P0072300 P0072300 P007 ...

  • Laarsen Associates IW - page 29

    Mighty Therm Volume Water Heater Page 29 Figure 21. Outdoor Parts. ...

  • Laarsen Associates IW - page 30

    LAARS HEATING SYSTEMS Page 30 Key Description Model Model Model Model Model Model Model Model Model N o 50 0 6 00 71 5 8 50 1010 1200 1430 1670 1825 1 T op Panel Assembly 10660701 10660702 10660703 10660704 10660705 10660706 10660707 10660708 10660709 2 Rear Windshield 10658101 10658102 10658103 10658104 10658105 10658106 10658107 10658108 10658109 ...

  • Laarsen Associates IW - page 31

    Mighty Therm Volume Water Heater Page 31 Key Description Model Model Model Model Model Model Model Model Model N o 50 0 6 00 71 5 8 50 1010 1200 1430 1670 1825 7 Front Support, Flue Collector 10662101 10662102 10662103 10662104 10662105 10662106 10662107 10662108 10662109 8 T ile Cover , Front & Rear 10661501 10661502 10661503 10661504 10661505 ...

  • Laarsen Associates IW - page 32

    Pump Rotating Sections and Repair Parts Check pump assembly on heater for H.P . rating and find correct Laars part number from table below . Description 1/4 HP 1/3 HP 3/4 HP Pump Rotating Assembly, B&G , 1522 w/3 “ IMP , Bronze, 1P A0048700 —— —— Pump Rotating Assembly, B&G , Series 90 w/3 “ Impeller , 1P A0077100 —— —— ...

Fabbricante Laarsen Associates Categoria Water Heater

I documenti che otteniamo dal fabbricante del dispositivoLaarsen Associates IW possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Laarsen Associates
- manuali per l’uso IW
- schede prodotto Laarsen Associates
- opuscoli
- o etichette energetiche Laarsen Associates IW
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Laarsen Associates IW.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Laarsen Associates IW, manuali di manutenzione, brevi manuali o manuali utente Laarsen Associates IW. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Laarsen Associates IW.

Manuali per l’uso simili

Manuale completo del dispositivo Laarsen Associates IW, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Laarsen Associates IW dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Laarsen Associates IW.

Il manuale per l’uso completo Laarsen Associates, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Laarsen Associates IW - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Laarsen Associates IW, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Laarsen Associates IW che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Laarsen Associates IW - che ci dovrebbe aiutare nei primi passi durante l'uso Laarsen Associates IW
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Laarsen Associates IW
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Laarsen Associates IW in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Laarsen Associates IW?

Utilizza il modulo sottostante

Se non hai risolto il problema con Laarsen Associates IW con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Laarsen Associates IW è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)