    POOL AND SP A HEA TER 120/240 V AC NA TURAL GAS/LP GAS INSTALLATION and USER’S GUIDE MODELS Natural Propane 200K B TU/HR 460730 460731 250K B TU/HR 460732 460733 300K B TU/HR 460734 460735 400K B TU/HR 460736 460737 IMPOR T ANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SA VE THESE INSTRUCTIONS If the information in these instructions i ...

  • Pentair 200K BTU/HR - page 2

    INST ALLA TION, OPERA TION AND SERVICE MANUAL TO INSTALLER: Affix these instructions adjacent to the heater. T O CONSUMER: Retain these instructions f or future reference. FOR YOUR SAFETY - This product must be installed and serviced by a professional service technician, qualified in pool heater installation. Improper installation and/or operation ...

  • Pentair 200K BTU/HR - page 3

    SAFET Y INSTRUCTIONS ( Continued ) This appliance is equipped with an unconventional gas control valve that is factory set with a manifold pressure of -.2 inches wc. Improper installation, adjustment, alteration, ser- vice or maintenance can cause property damage, personal injury or loss of life. Installation or service must be performed by a quali ...

  • Pentair 200K BTU/HR - page 4

    The heater may not be installed within five feet of the inside surface of a pool or spa unless it is separ ated by a solid fence, wall or other permanent barrier . A Propane (LPG) fired heater must not be installed in a garage in Massachusetts, by order of the Massachuset ts State Fire Marshall. For more inf ormation, call the Fire Marshall’ s of ...

  • Pentair 200K BTU/HR - page 5

    C. Use only your hand to turn the gas control on or off . Never use tools. If you cannot change the ON/OFF setting by hand, don’t try to repair it, call a qualified service technician. Force or at tempted repair may result in fire or explosion. D. Do not use this heater if any part has been under water . Immediately call a qualified service techn ...

  • Pentair 200K BTU/HR - page 6

    8. Push the toggle switch away from you to switch the gas on. 9. Replace the Door Access P anels. All panels must be in place when operating the heater . 10. Set 3-way v alves on inlet and outlet to pool or spa, as appropriate. 11. T urn on all electric power to the appliance. 12. Press either the POOL ON or SPA ON button switch on the operating co ...

  • Pentair 200K BTU/HR - page 7

    The SERVICE SYSTEM light indicates that there is insufficient water flow to the heater . If the pump is oper- ating, this usually indicates that the filter and/or skim- mers should be cleaned (some filters may require back- washing). If the light remains on after the filter/skimmers have been serviced, the system should be checked by a qualified se ...

  • Pentair 200K BTU/HR - page 8

    CARE AND MAINTENANCE MAINTENANCE INSTRUCTIONS Risk of fire or explosion from flammable vapors. Do not store gasoline, cleaning fluids, v arnishes, paints, or other volatile flammable liquids near heater or in the same room with heater . The following maintenance is recommended every six months and at the start of every swimming season: 1. Inspect t ...

  • Pentair 200K BTU/HR - page 9

    OUTDOOR INST ALL A TION INSTRUCTIONS For heaters located outdoors, using the built -in stackless venting system. Risk of explosion if a unit burning propane gas is installed in a pit or other low spot. Propane is heav- ier than air . Do not install the heater using propane in pits or other locations where gas might collect. Consult your local build ...

  • Pentair 200K BTU/HR - page 10

    CONTROL P ANEL INDEXING The exhaust discharges vertically from outside the vent cover . The heater control panel assembly located on the top panel can be rotated to any of three positions for convenient access to the panel as f ollows: 1. Remove the bolts from the door panels. R emove both door panels. 2. Remove the f our corner screws that secure ...

  • Pentair 200K BTU/HR - page 11

    NOTICE: Combustion air contaminated by corrosive chemical fumes can damage the heater and will void the warr anty (See T able 1 below). HEA TER CLEARANCES – OUTDOOR SHEL TER (Canada) or INDOOR (U.S. ) The following clear ances must be maintained from com- bustible surfaces: TOP ......................................3 ft. (1 m) EXHAUST SIDE ...... ...

  • Pentair 200K BTU/HR - page 12

    OUTSIDE VENT COVER REMOV AL The heater is supplied from the factory with a built -in stackless outside vent for outdoor installation. R emove the outside vent cover f or outdoor shelter installation. VER TICAL VENTING - NEGA TIVE PRESSURE (See Figures 11 and 12) V ent the heater vertically in a negative pressure (positive dr aft) system in accordan ...

  • Pentair 200K BTU/HR - page 13

    5. Use Listed firestop for floor and ceiling penetrations. Use Listed thimble for wall penetr ations. Use a Listed roof flashing, roof jack, or roof thimble for all roof penetrations. Do not fill the space around the vent (that is, the clear air space in the thimble or firestop) with insulation. The roof opening must be located so that the vent is ...

  • Pentair 200K BTU/HR - page 14

    Risk of fire or asphyxiation if vent is not assembled according to manufacturer’ s instructions or if vent parts from different manuf acturers are mixed. V ent parts from different manuf acturers ARE NOT interchange- able. Mixing parts from more than one manufacturer may cause leaks or damage to vent. When installing a vent, pick one manufacturer ...

  • Pentair 200K BTU/HR - page 15

    The terminal must be located (Canada): • at least 10 feet (3.3M) from any opening into a build- ing. • at least 12" (.3M) abov e finished grade or the normally expected snow accumulation level, whichever is higher • At least 4 feet (1.2M) horizontally from electric meters, gas meters, regulators and relief equipment • At least 7 feet ( ...

  • Pentair 200K BTU/HR - page 16

    Install a check valv e to prevent back -siphoning through the heater when the pump is off . NOTICE: Improper operation of chemical f eeders can cause severe damage to the heater which is not covered by the warr anty . Install the chemical feeder downstream of the heater (see “W ater Chemistry , ” below). Install a chemical resistant one-way che ...

  • Pentair 200K BTU/HR - page 17

    17 V erify proper operation of the w ater pressure switch at the start of every season and every six months thereafter by the following steps: 1. Lower the thermostat setting to turn off the heater . 2. Wait at least 15 minutes after the burner is of f , and then turn off the filter pump. 3. T urn up the thermostat as though to fire the burner . 4. ...

  • Pentair 200K BTU/HR - page 18

    18 PRESSURE RELIEF V AL VE Canadian code requires and some U.S. local codes may require installation of a pressure relief valv e. Purchase separately and install a 3/4" pressure relief valve comply- ing with the ANSI/ASME Boiler and Pressure V essel Code, having a capacity equal to the Btu/hr r ating of the heater . The relief pressure of the ...

  • Pentair 200K BTU/HR - page 19

    19 Risk of fire and explosion. Improper inst allation, adjustment, alteration, service, or main- tenance of the Combination Gas Control V alve can lead to fire or explosion, causing loss of life, per- sonal injury , or property damage. These instructions are for the use of qualified service technicians only! Do not attempt this procedure unless you ...

  • Pentair 200K BTU/HR - page 20

    20 GAS CONNECTIONS The heater requires a gas supply of not less than 4" (10.2cm) wc and not more than 14" (35.6cm) wc. Gas supply pressures outside of this range may result in improper burner operation. A minimum flowing or dynamic inlet pressure of 4" (10.2cm) wc is required to maintain input rating. The gas supply must be installed ...

  • Pentair 200K BTU/HR - page 21

    Connect the L1 of the power supply to the black wire, the L2 or neutral lead to the red wire, and the ground wire to the green wire. A time clock controlling the filter pump should have a low- voltage Fireman’ s Switch that switches off the heater at least 15 minutes before shutting off the pump . FIREMAN’S SWITCH CONNECTION NOTICE: If , while ...

  • Pentair 200K BTU/HR - page 22

    22 6. Reinstall the access door panels. The fuse for the Fireman’ s Switch is a 1.25 amp 1-1/4x1/4" f ast blow fuse, av ailable locally . MAXIMUM TEMPERA TURE SET POINT 1. Unbolt and remove the Door Panels (see Figure 3, Page 5). 2. Access the control panel board on the underside of the top cover . Locate the red button on the corner of the ...

  • Pentair 200K BTU/HR - page 23

    23 Hazardous voltage. Can shock, burn or kill. Disconnect power before servicing any components. Fire and Explosion hazard. Do not jumper switch terminals to remedy a failed safety switch. W ARNIN G W ARNIN G Initial T roubleshooting Only qualified, trained service technicians with appropriate test equipment should service the heater . Remember tha ...

  • Pentair 200K BTU/HR - page 24

    24 Heater Will Not Fire - A S tart GO TO “HEA TER WILL NOT FIRE - B” Page 25 Heater should fire on demand for heat. Check Fireman’s Switch circuit connections (time clock, wiring, external controller relay). Remove jumper . Check wiring between T ransformer and J7 terminals on Control Board and between J7 and Fireman’s Switch on T erminal B ...

  • Pentair 200K BTU/HR - page 25

    25 Heater Will Not Fire - B S tart Increase POOL/SP A tempera- ture setting on Membrane Pad above actual water tem- perature. Heater should fire on demand for heat. If not, and no other red LED’s light, replace Control Board. Service pump/filter and elimi- nate other flow obstructions. Heater should fire on call for heat. Re-verify that water flo ...

  • Pentair 200K BTU/HR - page 26

    26 Heater Will Not Fire - C S tart Go to “INITIAL TROUBLESHOOTING” Continue to observe heater for several minutes. Cycle heater on and off several times. Observe for delayed or rough ignition, poor combus- tion, premature extinction of flame, evidence of boiling, or operation of any diagnostic LED. Go to pertinent trou- bleshooting section if a ...

  • Pentair 200K BTU/HR - page 27

    27 Heater Will Not Fire - D S tart IMPORT ANT! READ ME FIRST!! If your heater is correctly connected to 240 V olts AC, The Ignition Control Module (ICM) will convert the 240V AC to an intermittent pulse to the ignitor . Digital meters don’t read this type of signal well. (An analog meter will give a better reading than a digital meter). If the IC ...

  • Pentair 200K BTU/HR - page 28

    28 Diagnostic LED’ s: AGS, AFS, HLS, PS, THERMIST OR Do not jumper a safety switch to remedy a failed switch. NOTE: ES1 is a spare and should be jumpered. CAUTIO N Service pump and filter to restore proper flow . After ser- vicing, verify proper operation of Pressure Switch (PS). Replace thermistor or Control Board to correct overheating. Replace ...

  • Pentair 200K BTU/HR - page 29

    29 Diagnostic LED’ s: SFS NO (HD ) NO (Basic) NO Reset power to Heater and retry . Heater should fire. Does the Digital T emperature Display show Error Code “E05” or “E06”? Heater start s and runs OK, but temperature of exhaust climbs to 450º–500º in 3–5 minutes. Heater start s after several tries, exhaust temperature stays below 25 ...

  • Pentair 200K BTU/HR - page 30

    30 Burner T roubleshooting SYMPT OM CAUSE REMEDY Loud, high-pitched whine Flame is too rich. V erify pressure tap between gas valve and blower inlet. T urn to Page 19 and verif y that the gas regulator setting is 0.2" (0.5cm) wc below the blower inlet pressure. Replace gas orifice with smaller size. Flame is “fluttery . ” Flame is too lean ...

  • Pentair 200K BTU/HR - page 31

    31 ...

  • Pentair 200K BTU/HR - page 32

    32 ...

  • Pentair 200K BTU/HR - page 33

    33 REP AIR P AR TS – BURNER SYSTEM Model Key Part 200NA 250NA 300NA 400NA No. Description Qty . 200LP 250LP 300LP 400LP 1 Combination Gas Control V alve Kit 1 42001-0051S 42001-0051S 42001-0051S 42001-0051S 2 3/4" Union 2 38404-4097S 38404-4097S 38404-4097S 38404-4097S 3 Gas Orifice 1 • Gas Orifice Kit – NG (Incl. Key Nos. 3 and 4)† 77 ...

  • Pentair 200K BTU/HR - page 34

    34 REP AIR P AR TS – W A TER SYSTEM 1 3 20 21 22 4 5 8 9 12 11 10 2 7 6 19 14 15 13 18 17 16 * Not available separately . • Not illustrated. Model Key Part 200NA 250NA 300NA 400NA No. Description Qty . 200LP 250LP 300LP 400LP 1 T ube Sheet Coil Assembly Kit (NA, LP Series) (Includes Key No.3) 1 77707-0232 460747 77707-0233 77707-0234 2 Manifold ...

  • Pentair 200K BTU/HR - page 35

    35 REP AIR P AR TS – ELECTRICAL SYSTEM 3 8 9 1 0 11 12 4 5 19 1 3 18 15 4 2 ...

  • Pentair 200K BTU/HR - page 36

    36 Pool Heater Wiring Connection Diagram Plug –12 pin 120V – Black 240V – Red JMP 9 1 J6 JMP 1 JMP 1 External Control Interface Circuit Disabled, Heater Membrane P ad Enabled External Control Interface Circuit Enabled, "P ool On" and "Spa On" K eys Disabled. "OFF" K ey on Membrane P ad Remains Functional . CONNEC ...

  • Pentair 200K BTU/HR - page 37

    37 Pool Heater Electrical Schematic Ladder Diagram L1 L2 120/240 VA C 120/240 VA C IGNITER L1 S1 S2 L2 F1 F2 BLOWER GND GND CLASS II TRANSFORMER 24 V AC 24 V AC 24V OPERA TING CONTROL 24 V AC LOGIC TH IND AIR FLOW SWITCH HI LIMIT SWITCH WA T E R PRESSURE SWITCH COM NO AGS SWITCH VA L GAS V AL VE THERMIST OR SENSOR ST A CK FLUE SENSOR NO TES: 1.) AN ...

  • Pentair 200K BTU/HR - page 38

    © 2006 Pent air W ater Pool and Sp a, Inc. All rights reserved This document is subject to change without notice 1620 Hawkins Ave., Sanford, NC 27330 • (919) 566-8000 10951 West Los Angeles A ve., Moorpark, CA 93021 • (805) 553-5000 T rademarks and disclaimers: MasterT emp and the Pentair Pool Product s and Pentair W ater Pool and S pa logos a ...

Fabbricante Pentair Categoria Swimming Pool Heater

I documenti che otteniamo dal fabbricante del dispositivoPentair 200K BTU/HR possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Pentair
- manuali per l’uso 200K BTU/HR
- schede prodotto Pentair
- opuscoli
- o etichette energetiche Pentair 200K BTU/HR
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Pentair 200K BTU/HR.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Pentair 200K BTU/HR, manuali di manutenzione, brevi manuali o manuali utente Pentair 200K BTU/HR. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Pentair 200K BTU/HR.

Manuali per l’uso simili

Manuale completo del dispositivo Pentair 200K BTU/HR, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Pentair 200K BTU/HR dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Pentair 200K BTU/HR.

Il manuale per l’uso completo Pentair, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Pentair 200K BTU/HR - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Pentair 200K BTU/HR, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Pentair 200K BTU/HR che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Pentair 200K BTU/HR - che ci dovrebbe aiutare nei primi passi durante l'uso Pentair 200K BTU/HR
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Pentair 200K BTU/HR
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Pentair 200K BTU/HR in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Pentair 200K BTU/HR?

Utilizza il modulo sottostante

Se non hai risolto il problema con Pentair 200K BTU/HR con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Pentair 200K BTU/HR è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)