    As an ENERGY ST AR ® Partner , Burnham Hydronics has determined that this boiler meets the ENERGY ST AR ® guidelines for energy efciency established by the United States Environmental Protection Agency (EP A). 102538-01R4-2/10 n o n o i t a m r o f n i g n i k e e s n e h W . r o t c a r t n o c g n i t a e h r u o y l l a c , r e l i o b o t ...

  • Burnham ES2 ES2 - page 2

    2 FOLLOW ALL INSTRUCTIONS and warnings printed in this manual and posted on the boiler. INSPECT THE BOILER ANNUALLY. To keep your boiler safe and efcient, have a service technician follow the Service checklist near the end of this manual. IF YOU ARE NOT QUALIFIED to install or service boilers, do not install or service this one. THE BOILER MAY L ...

  • Burnham ES2 ES2 - page 3

    3 5 2 1 3 4 Congratulations on your purchase of a new Burnham ® boiler—designed and constructed to provide you with years of reliable service. • ENERGY ST AR™ efficiency – friendly on the environment and your wallet. • Cast iron heat e xchanger – for reliability and durability, nothing beats a cast iron heat exchanger. Ours is made pr ...

  • Burnham ES2 ES2 - page 4

    4 ES2 Series Boiler Model Input (MBH) DOE Heating Capacity (MBH) Net I=B=R Rating (MBH) AFUE (%) ES23 70 59 51 85 ES24 105 88 77 85 ES25 140 1 18 102 85 ES26 175 147 128 85 ES27 210 176 153 85 ES28 245 206 179 85 ES29 280 235 205 85 Ratings SPECIFICA TIONS Boiler Model Depth Width Height Supply NPT (inch) Return NPT (inch) V ent (inch) Gas NPT (inc ...

  • Burnham ES2 ES2 - page 5

    5 Figure S-1: Minimum Clearances to Combustibles and Closet Dimensions SPECIFICA TIONS (continued) ...

  • Burnham ES2 ES2 - page 6

    6 Installation: 1. Unpack the crate ............................................................................................. 7 2. Position the boiler ............................................................................................ 7 3. Provide combustion air .......................................................................... ...

  • Burnham ES2 ES2 - page 7

    7 THE BOILER IS TOP-HEAVY. Do not allow it to tip over. 1. Remove the sleeve. 2. Remove the contents from the skid, except the boiler. 3. Remove the four (4) hex-drive lag screws holding the boiler to the skid (Figure 1-a). 1. UNP ACK THE CRA TE 4. Tip the boiler and shimmy it off the skid. 2. POSITION THE BOILER W ARNINGS 1. Slide the boiler into ...

  • Burnham ES2 ES2 - page 8

    8 4-a 3. PROVIDE COMBUSTION AIR INSUFFICIENT COMBUSTION AIR SUPPLY may result in the production and release of deadly carbon monoxide (CO) into the home which can cause severe personal injury or death. 4. CONNECT VENTING IMPROPER VENTING may result in property damage and the release of ue gases which contain deadly carbon monoxide (CO) into the ...

  • Burnham ES2 ES2 - page 9

    9 4. CONNECT VENTING (continued) Model ES23 ES24 ES25 ES26 ES27 ES28 ES29 Input (MBH) 70 105 140 175 210 245 280 Minimum V ent Diameter (in) 4 5 6 6 7 7 8 V ent Height (ft) With B-V ent (double wall) V ent Connector 6 0 0 6 0 4 0 2 8 8 8 8 2 8 2 8 10 10 10 10 10 10 10 10 15 15 15 15 15 15 15 15 20 20 20 20 20 20 20 20 30 20 30 30 30 30 30 30 50 20 ...

  • Burnham ES2 ES2 - page 10

    10 2. Screw the water supply manifold into the boiler outlet tapping “O.” 3. Orient the manifold with the relief valve on top. 4. Screw the relief valve into manifold tapping “RV”. i This installation is not complete until the relief v alve is installed. PIPE THE RELIEF VALVE DISCHARGE to a location where it will not harm people or damage p ...

  • Burnham ES2 ES2 - page 11

    1 1 7. Screw an installer-supplied 1¼” pipe or nipple into the water return tapping “R”. 8. Screw the supplied drain valve into tapping “D”. 6. CONNECT BOILER W A TER PIPING (contin ued) 9. See Figure 6b for suggested near boiler piping of IQ Options. 6-b Item Description Burnham Part Number 1 1¼ x 1¼ x ½ T ee 806601021 2 Immersion We ...

  • Burnham ES2 ES2 - page 12

    12 DISCONNECT ELECTRICAL POWER to the boiler and heating system before servicing. Positively assure that no voltage is present. Lock electrical boxes to prevent someone from inadvertently restoring power before the heating system is safe to operate. NEVER DEFEAT OR JUMP OUT safety devices. PROTECT EACH BOILER circuit with a properly sized over-curr ...

  • Burnham ES2 ES2 - page 13

    13 Using IQ Boiler Control Displa y 8. PROGRAM THE CONTROLS Viewing the Operating Mode Options In operating mode the user may view (but not change) boiler operating status, settings and troubleshooting information. To view IQ Boiler Control display information: 1 . Press and release the “ I ” key on the IQ Boiler Control to change from one para ...

  • Burnham ES2 ES2 - page 14

    14 Unit D i splay OR Samp le Di spl ay 1 s ec 1 s ec 1 s ec Please note that in operating mode to hold the display on the value the user can press and hold either the Up ñ or Down ò keys and the value will be continuously shown. This may be helpful in watching a value “live”. Changing the Adjustable P arameters To adjust the High Limit setpoi ...

  • Burnham ES2 ES2 - page 15

    15 9. CHECK FOR GAS AND W A TER LEAKS GAS LEAKS may result in re or explosion. WATER LEAKS may cause extensive property damage. Refer to Appendix E – Filling the System and Checking f or Leaks Using the Optional LCD Display Kit The LCD Display is an easy to use touch screen type display that allows a technician to monitor and adjust the IQ Boi ...

  • Burnham ES2 ES2 - page 16

    16 10-b 10. PERFORM ST ARTUP CHECKS AND ADJUSTMENTS FAILURE TO PERFORM THESE CHECKS of the boiler's combustion and safety systems may result in serious property damage, injury, or death. IF YOU SMELL GAS, STOP and repair the leak. Lighting the boiler when gas is leaking may cause explosion or re. Follow the checklist below: 1. Verify that t ...

  • Burnham ES2 ES2 - page 17

    17 ANNUAL MAINTENANCE CHECKLIST W ARNINGS THE BOILER CONTAINS REFRACTORY CERAMIC FIBER , a possible human carcinogen Use a NIOSH approved respirator when servicing high-temperature insulation and gasket materials. Wash exposed skin gently with soap and water after contact Wash exposed clothing separate from normal laundry. LABEL ALL WIRES prior to ...

  • Burnham ES2 ES2 - page 18

    18 TROUBLESHOOTING IQ Boiler Control Status Codes (when " Err " is not displayed) Display Status Boiler / Control Action(s) Blank Boiler and Circulator off No 120 V ac power at boiler , check breaker and wiring between breaker panel and boiler . 1 Boiler not responding to Heat Request Boiler is not seeing Heat Request. Check thermostat or ...

  • Burnham ES2 ES2 - page 19

    19 If "Err" IS display ed on the IQ Boiler Control: " Err " ashes on the IQ Boiler control display followed by a number. Use the following table along with this error number to determine the problem and possible causes: IQ Boiler Control Error Codes (when " Err " is ashing) Display Status Boiler / Control Action( ...

  • Burnham ES2 ES2 - page 20

    20 TR OUBLESHOO TING (continued) If IQ Boiler Control Sho ws Status Code “ STA 15 ": The IQ Boiler Control is “Waiting for Limit to Close” and the display on the IQ Option Panel should be the rst place to check. The IQ Option Panel display (lower display) will show one of the following status codes: IQ Option Panel Display Shows “ E ...

  • Burnham ES2 ES2 - page 21

    21 Key No. Description [Quantity] Part Number ES23 ES24 ES25 ES26 ES27 ES28 ES29 1A Block Assembly 102287-03 102287-04 102287-05 102287-06 102287-07 102287-08 102287-09 1B Canopy Gasket Kit 6206001 1C Canopy Assembly 102554-03 102554-04 102554-05 102554-06 102554-07 102554-08 102554-09 1D Flue Bafe [2] 102678-01 [3] 102678-01 [4] 102678-01 [5] 1 ...

  • Burnham ES2 ES2 - page 22

    22 REP AIR P AR TS LIST (continued) Key No. Description [Quantity] Part Number ES23 ES24 ES25 ES26 ES27 ES28 ES29 2A Base Wrapper 71807031 71807041 71807051 71807061 71807071 71807081 71807091 2B Base T ray 102543-03 102543-04 102543-05 102543-06 102543-07 102543-08 102543-09 2C Burner T ray Assembly 61807031 61807041 61807051 61807061 61807071 618 ...

  • Burnham ES2 ES2 - page 23

    23 REP AIR P AR TS LIST (continued) Key No. Description [Quantity] Part Number ES23 ES24 ES25 ES26 ES27 ES28 ES29 3A Gas V alve (Natural Gas), Honeywell VR8204P1 171 81660282 N/A Gas V alve (Natural Gas), Honeywell VR8304P4496 N/A 81660283 Gas V alve (LP Gas), Honeywell VR8204C3015 81660146 N/A Gas V alve (LP Gas), Honeywell VR8304P4314 N/A 8166016 ...

  • Burnham ES2 ES2 - page 24

    24 REP AIR P AR TS LIST (continued) Key No. Description [Quantity] Part Number ES23 ES24 ES25 ES26 ES27 ES28 ES29 4A IQ Boiler Control 102289-01 4B IQ Option Panel 102291-01 4C T ransformer 102516-01 4D T emperature Sensor 10241 1-01 ...

  • Burnham ES2 ES2 - page 25

    25 Key No. Description [Quantity] Part Number ES23 ES24 ES25 ES26 ES27 ES28 ES29 5A Jacket Left Side Panel 102566-01 5B Jacket Right Side Panel 102567-01 5C Jacket Rear Panel 102569-03 102569-04 102569-05 102569-06 102569-07 102569-08 102569-09 5D Jacket V estibule Panel 102565-03 102565-04 102565-05 102565-06 102565-07 102565-08 102565-09 5E Jacke ...

  • Burnham ES2 ES2 - page 26

    26 REP AIR P AR TS LIST (continued) Key No. Description [Quantity] Part Number ES23 ES24 ES25 ES26 ES27 ES28 ES29 6A Supply W ater Manifold 80607001 6B T emperature/Pressure Gauge 100282-01 6C Circulator Wiring Harness 6130701 6D 30 PSI Relief V alve 81660363 6E Drain V alve 806603012 6F V ent Damper 102284-01 102284-02 102284-03 102284-04 102284-0 ...

  • Burnham ES2 ES2 - page 27

    27 INTERNAL WIRING Figure IW-1: W iring Diagram ...

  • Burnham ES2 ES2 - page 28

    28 INTERNAL WIRING (continued) Figure IW-2: W iring Schematic ...

  • Burnham ES2 ES2 - page 29

    29 Figure IW-3: Single Zone System with Domestic Hot W ater T ank Figure IW-4: Multiple Zone System with Zone Circulators INTERNAL WIRING (continued) ...

  • Burnham ES2 ES2 - page 30

    30 Figure IW-5: Multiple Zone System with Zone V alves Figure IW-6: Multiple Zone System with Zone Circulator Panel INTERNAL WIRING (continued) ...

  • Burnham ES2 ES2 - page 31

    31 T STAT 1 VALVE 1 T STAT 2 VALVE 2 T STAT 3 OFF ON ZONE 4 PRIORITY TACO ZVC 404 (OR EQIV.) FOUR ZONE ZONE VALVE CONTROL WITH OPTIONAL PRIORITY THERMOSTAT BOILER JACKET PANEL 1 2 3 T T 1 1 4 2 3 5 6 7 8 2 3 LINE VOLTAGE FACTORY WIRING SIZE 14 AWG TYPE TW OR TEW/AWM WIRE LINE VOLTAGE FIELD WIRING VALVE 3 T STAT 4 VALVE 4 POWER POWER IN T T ZONE 1 T ...

  • Burnham ES2 ES2 - page 32

    32 APPENDIX A – COMBUSTION AIR PROVIDE ENOUGH AIR to ventilate the boiler room, dilute the ue gases, and sustain combustion. Ignition failure, overheating, re, carbon monoxide, and spillage of ue gases may result from poor air supply. If the boiler is a Direct Vent boiler and exchanges all combustion air and combustion products directly ...

  • Burnham ES2 ES2 - page 33

    33 APPENDIX B – VENTING VENT THIS BOILER according to the instructions. Failure to do so may cause products of combustion to enter the building resulting in severe property damage, personal injury or death. i Install this boiler according to this manual and the National Fuel Gas Code, ANSI Z223.1/NFP A 54, the Natural Gas and Propane Installation ...

  • Burnham ES2 ES2 - page 34

    34 APPENDIX B1 – A TMOSPHERIC VENTING Figure B-1: T ypical Atmospheric V ent Installation GENERAL W ARNINGS FOR A TMOSPHERIC VENTING SYSTEMS USE ATMOSPHERIC VENTING only with boilers approved for atmospheric venting as noted in the Specifications Section of this manual. INSPECT EXISTING CHIMNEY for obstructions and deterioration and repair or li ...

  • Burnham ES2 ES2 - page 35

    35 THIS P A GE INTENTIONALL Y LEFT BLANK ...

  • Burnham ES2 ES2 - page 36

    36 APPENDIX C – GAS PIPING ASSURE GAS PIPING IS LEAK FREE AND OF PROPER SIZE and type for the connected load. SHUT OFF MAIN GAS SUPPLY prior to installing or servicing boiler gas piping. 1. Determine the boiler’s maximum gas demand and minimum gas supply pressure (printed on the boiler’s rating label) and the demand of other gas appliances se ...

  • Burnham ES2 ES2 - page 37

    37 5. Bond all above-ground gas piping to a grounding electrode and ensure the piping is electrically continuous. DO NOT USE GAS PIPING AS A GROUNDING ELECTRODE. Refer to National Electrical Code, NFPA 70. 6. Install sediment trap, ground-joint union and manual shut-off valve upstream of boiler gas control valve and outside jacket. 7. When the pipi ...

  • Burnham ES2 ES2 - page 38

    38 (2) Comply with the boiler’s specic water quality requirements. See the Specifications Section of this manual. (3) Comply with the boiler’s specic requirements for minimum water ow through the boiler, installing a system bypass or primary-secondary loop if necessary to maintain ow through the boiler when serving small zones. 3. ...

  • Burnham ES2 ES2 - page 39

    39 Figure D-0: Piping Schematic Symbols APPENDIX D – System Piping (continued) ...

  • Burnham ES2 ES2 - page 40

    40 Figure D-W1: W ater Boiler , Series Loop APPENDIX D – System Piping (continued) Figure D-W2: W ater Boiler , T wo or More Zones ...

  • Burnham ES2 ES2 - page 41

    41 Figure D-W3: W ater Boiler , T ankless Coil, T wo or More Zones APPENDIX D – System Piping (continued) Figure D-W4: W ater Boiler , Indirect W ater Heater , T wo or More Zones ...

  • Burnham ES2 ES2 - page 42

    42 APPENDIX D – System Piping (continued) Figure D-W5: W ater Boiler , Indirect W ater Heater Figure D-W6: Multiple W ater Boilers, Indirect Water Heater , T wo or More Zones ...

  • Burnham ES2 ES2 - page 43

    43 APPENDIX E – FILLING THE SYSTEM AND CHECKING FOR LEAKS Fill entire heating system with water and vent air from system. Use the following procedure on a Series Loop or multi-zoned system installed as per the gure below. Remove air from system when lling. 1. Close full port ball valve located between vertical hose bib and air scoop in boil ...

  • Burnham ES2 ES2 - page 44

    44 APPENDIX F – ADJUSTING GAS INPUT RA TE Natural Gas Boilers: 1. Turn off gas supply to all appliances other than gas-red boiler. 2. Note the rated manifold gas pressure listed on the boiler’s rating label. 3. Connect Manometer to manifold pressure tapping on Gas Valve (Figure F-1). 4. Light main burners by adjusting thermostat to highest s ...

  • Burnham ES2 ES2 - page 45

    45 Seconds for T wo (2) Revolutions Size of Gas Meter Dial One-Half Cu. Ft. One Cu. Ft. T wo Cu. Ft. 24 150.0 300.0 450.0 26 138.4 276.9 415.3 28 128.5 257.1 385.7 30 120.0 240.0 360.0 34 105.8 21 1.7 317.6 38 94.7 189.4 284.2 42 85.7 171.4 257.1 46 78.2 156.5 234.7 50 72.0 144.0 216.0 55 65.4 130.9 196.3 60 60.0 120.0 180.0 65 55.3 1 10.7 166.1 70 ...

  • Burnham ES2 ES2 - page 46

    46 APPENDIX G – CHECKING DRAFT AND COMBUSTION CHECK DRAFT (GAS BOILERS WITH DRAFT HOODS) 1. Insofar as is practical, close all doors and windows in the building. 2. Turn on all appliances not connected to the same venting system as the boiler being checked. 3. Turn on all exhaust fans (such as range hoods and bathroom exhausts) to their maximum s ...

  • Burnham ES2 ES2 - page 47

    47 The IQ Boiler Control stores two boiler supply temperature setpoints in its memory; one setpoint is for the High Limit Setting and the second is for the Operating Setpoint. APPENDIX H – IQ CONTROL SYSTEM IQ Control System Overvie w The “IQ Control System” consists of an IQ Boiler Control and an IQ Option Panel with optional “plug in” c ...

  • Burnham ES2 ES2 - page 48

    48 APPENDIX H – IQ Contr ol System (continued) IQ Option Cards: For example, if additional safety limits are required, select Manual or Automatic Reset Aquastat or Low Water Cutoff IQ Option Cards. Additionally, if energy savings and improved home comfort is desired, select an Outdoor Reset IQ Option Card. The Outdoor Reset IQ Option Card regulat ...

  • Burnham ES2 ES2 - page 49

    49 The LCD Display kit includes a mounting bracket and wiring harness to allow simple physical installation and “plug-in” style electrical connection. This intuitive display reduces setup and troubleshooting time by providing the user adjustment and alarm focused “help” and “information” screens. APPENDIX H – IQ Contr ol System (conti ...

  • Burnham ES2 ES2 - page 50

    50 APPENDIX H – IQ Contr ol System (continued) Burnham Part Number Item Description 102723-01 Outside Reset IQ Option Card, Domestic Hot W ater Priority , for use with Option Control Panel, with Outside Air T emperature Sensor with 60 inch lead, Instructions, Unit Pack. No additional pipe ttings required. 102294-01 Outdoor Reset IQ Option Card ...

  • Burnham ES2 ES2 - page 51

    51 SER VICE RECORD DA TE SERVICE PERFORMED ...

  • Burnham ES2 ES2 - page 52

    52 L L i i m m i i t t e e d d W W a a r r r r a a n n t t y y F F o o r r R R e e s s i i d d e e n n t t i i a a l l G G r r a a d d e e W W a a t t e e r r a a n n d d S S t t e e a a m m B B o o i i l l e e r r s s Using Cast Iron, Carbon Steel, Cast Aluminum, or Stainless Steel Heat Exchangers a a n n d d P P a a r r t t s s / / A A c c c c e ...

Fabbricante Burnham Categoria Boiler

I documenti che otteniamo dal fabbricante del dispositivoBurnham ES2 ES2 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Burnham
- manuali per l’uso ES2 ES2
- schede prodotto Burnham
- opuscoli
- o etichette energetiche Burnham ES2 ES2
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Burnham ES2 ES2.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Burnham ES2 ES2, manuali di manutenzione, brevi manuali o manuali utente Burnham ES2 ES2. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Burnham ES2 ES2.

Manuali per l’uso simili

Manuale completo del dispositivo Burnham ES2 ES2, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Burnham ES2 ES2 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Burnham ES2 ES2.

Il manuale per l’uso completo Burnham, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Burnham ES2 ES2 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Burnham ES2 ES2, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Burnham ES2 ES2 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Burnham ES2 ES2 - che ci dovrebbe aiutare nei primi passi durante l'uso Burnham ES2 ES2
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Burnham ES2 ES2
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Burnham ES2 ES2 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Burnham ES2 ES2?

Utilizza il modulo sottostante

Se non hai risolto il problema con Burnham ES2 ES2 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Burnham ES2 ES2 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)