Manuale per l’uso Napoleon Fireplaces BGD42P

28 pagine 2.02 mb
Scarica

Vai alla pagina of 28

Summary
  • Napoleon Fireplaces BGD42P - page 1

    1 W415-0381 / E / 02.09.06 INST ALLER: THESE INSTRUCTIONS MUST BE CONVEYED TO AND REMAIN WITH THE HOMEOWNER. Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 4Y8 Canada • (705)721-1212 • fax(705)722-6031 www .napoleonfireplaces.com • ask@napoleon.on.ca CERTIFIED UNDER CANADIAN AND AMERICAN NA TIONAL ST ANDARDS, CSA 2.33, ANSI Z21.88 FOR VENTE ...

  • Napoleon Fireplaces BGD42P - page 2

    2 W415-0381 / E / 02.09.06 WARNING • Do not burn wood or other ma terials in this f ir eplace . • Adults and especially children should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition. Supervise young children when they are in the same room as the fire place . • Due to high tempe ...

  • Napoleon Fireplaces BGD42P - page 3

    3 W415-0381 / E / 02.09.06 ALL SPECIFICA TIONS AND DESIGNS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE DUE TO ON-GOING PRODUCT IMPROVEMENTS. NAPOLEON® IS A REGISTERED TRADEMARK OF WOLF STEEL L TD. PATENTS U.S. 5.303.693.801 - CAN. 2.073.41 1, 2.082.915. © WOLF STEEL L TD. NAPOLEON products are manufactured under the strict Standard of the world re ...

  • Napoleon Fireplaces BGD42P - page 4

    4 W415-0381 / E / 02.09.06 THIS GAS FIREPLACE SHOULD BE INST ALLED AND SERV - ICED BY A QUALIFIED INST ALLER to conform with local codes. In absence of local codes, install the BG D42 to the current Na- tional Fuel Gas Code, ANSI Z223.1, or the current CAN/CGA B149, Installation Codes. Installation practices vary from region to region and it is imp ...

  • Napoleon Fireplaces BGD42P - page 5

    5 W415-0381 / E / 02.09.06 Use only Wolf S teel, Simp son Dura-V ent, Selkirk Direct Temp or American Metal Amerivent venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, and air terminal locations for ei- ther system are set out in this manual and must be ad- hered to. For Simpson Dura-V ent, Selkir ...

  • Napoleon Fireplaces BGD42P - page 6

    6 W415-0381 / E / 02.09.06 * Recommended to prevent condensation on windows and thermal breakage ** Using a Napoleon soffit heat shield, W585-0096, or equivalent, the distance may be reduced to a minimum of 18". It is recommended to maximize the distance to vinyl clad soffits. *** The periscope GD-401 requires a minimum 18 inches clearance fro ...

  • Napoleon Fireplaces BGD42P - page 7

    7 W415-0381 / E / 02.09.06 Use the GD401 periscope kit to locate the air termination above grade. The periscope must be installed so that when final grading is completed, the bottom air slot is located a minimum of 12 inches above grade. The maximum allow- able vent length depends on the fireplace, as illustrated. FIGURES 3 a-c FIGURE 4 TYPICAL VEN ...

  • Napoleon Fireplaces BGD42P - page 8

    8 W415-0381 / E / 02.09.06 VERTI C AL TERMINA TION HORIZONT AL TERMINA TION vertical rise is equal to or greater than the horizontal run horizontal run + verti- cal rise to maximum of 40 feet vertical rise is equal to or greater than the horizontal run horizontal run + verti- cal rise to maximum of 40 feet vertical rise is less than horizontal run ...

  • Napoleon Fireplaces BGD42P - page 9

    9 W415-0381 / E / 02.09.06 ELBO W VENT LENGTH V AL UES DEFINITIONS HORIZONT AL TERMINA TION REQUIRED VERTICAL RISE IN FEET (V T ) CALCULA TED HORIZONT AL VENT RUN PLUS OFFSETS IN FEET (H T ) FIGURE 5 45º FIGURE 6 90° H 1 H 2 when (H T ) < (V T ) Simple venting configuration (only one 45º and 90° elbow) for the following symbols used in the v ...

  • Napoleon Fireplaces BGD42P - page 10

    10 W415-0381 / E / 02.09.06 V 1 HORIZONT AL TERMIN A TION See graph to determine the re- quired vertical rise V T for the re- quired horizontal run H T . For vent configurations requiring more than one 45º and 90° elbow the following formulas apply: Formula 1: H T < 4.2 V T Formula 2: H T + V T < 24.75 feet FIGURE 7 REQUIRED VERTICAL RISE I ...

  • Napoleon Fireplaces BGD42P - page 11

    11 W415-0381 / E / 02.09.06 90° 90° V 1 H 1 H 2 V 2 45° 90° 45° VERTICAL TERMIN A TION Example 3: V 1 =5 f t V 2 = 10 ft V T = V 1 + V 2 = 5 + 10 = 15 ft H 1 =3 f t H 2 = 2.5 ft H R = H 1 + H 2 = 3 + 2.5 = 5.5 ft H O = .03(one 45º elbow + three 90º elbows - 135º) = .03(45+90+90+90-135)=5.4 H T = H R + H O = 5.5 + 5.4 = 10.9 ft H T + V T = 1 ...

  • Napoleon Fireplaces BGD42P - page 12

    12 W415-0381 / E / 02.09.06 H 1 VERTICAL TERMIN A TION For vent configurations requiring more than one 45º and one 90° elbow , the following formulas apply: F or mula 1: H T < 3V T F or mula 2: H T + V T < 40 fee t Example 4: when (H T ) > (V T ) Simple venting configurations See graph to determine the required vertical rise V T for the ...

  • Napoleon Fireplaces BGD42P - page 13

    13 W415-0381 / E / 02.09.06 This application occurs when venting through a roof. Installation kits for various roof pitches are available from your Napo- leon dealer . See Accesso- ries to order the specific kit required. 1. Determine the air terminal location, cut and frame 10 inch openings in the ceiling and the roof to provide the minimum 1 inch ...

  • Napoleon Fireplaces BGD42P - page 14

    14 W415-0381 / E / 02.09.06 AIR TERMINAL CONNECTOR INNER FLEX LINER OUTER FLEX LINER INNER SLEEVE HIGH TEMPERA TURE SEALANT ROOF SUPPORT FIGURE 18 A VENT SHIELD MUST BE USED IF THE W ALL TERMINAL IS INST ALLED ON COMBUSTIBLE, EXTERIOR SURF ACES. 1. Cut or frame a hole in an exterior wall with a minimum round or square opening of 10½ inches. Secure ...

  • Napoleon Fireplaces BGD42P - page 15

    15 W415-0381 / E / 02.09.06 STORM COLLAR FLASHING CAULKING WEATHE R SEALA NT 2” AIR INL ET BASE FIGURE 25 The vent system must be supported approximately every 3 feet for both vertical and horizontal runs. Use Wolf S teel vent spacers every 3 feet and either side of each elbow to maintain the minimum 1¼" clearance between the outer and inne ...

  • Napoleon Fireplaces BGD42P - page 16

    16 W415-0381 / E / 02.09.06 V ertical terminations may display a very active flame. As this appearance is not desirable, the vent exit must be restricted using restrictor plate, W500-0205. This reduces the velocity of the exhaust gases, slowing down the flame pattern and creating a more traditional appearance. Remove the two screws on either side o ...

  • Napoleon Fireplaces BGD42P - page 17

    17 W415-0381 / E / 02.09.06 TO INST ALL THE UPPER L OUVRES: Insert the upper louvres into the slots on both brackets. TO INST ALL THE L OWER L OUVRE ASSEMBL Y: At- tach each hinge to the fire- bo x with 2 screws. Position the hinge screen into place and with the con- trol door open, secure to the firebox using three screws. FIGURE 33 FIGURE 32 in p ...

  • Napoleon Fireplaces BGD42P - page 18

    18 W415-0381 / E / 02.09.06 NAILING TA B 1) Attach the nailing tabs to the corner posts using the 2 sheet metal screws supplied. Secure through the centre of the top and bottom slots in the nailing tab and then through the existing holes in the corner posts. If there are no existing holes, follow these instructions: Position the nailing tab so that ...

  • Napoleon Fireplaces BGD42P - page 19

    19 W415-0381 / E / 02.09.06 PHAZER TM logs and glowing embers, exclusive to Napo- leon Fireplaces, provide a unique and realistic glowing ef- fect that is different in every inst allation. T ake the time to carefully position the glowing embers for a maximum glow- ing effect. Log colours may vary . During the initial use of the fireplace, the colou ...

  • Napoleon Fireplaces BGD42P - page 20

    20 W415-0381 / E / 02.09.06 the log resting in the pocket of the left crossover log. 5. Place the bottom of the right crossover log (#6) against the right side of the grate. Place the top into the pocket provided on the center log (#5). Randomly place the charcoal embers along the front and sides of the log support tray in a realistic manner . Fine ...

  • Napoleon Fireplaces BGD42P - page 21

    21 W415-0381 / E / 02.09.06 against the threaded stud (B) at the other end. The blower must be able to be po- sitioned entirely onto the pad. Tilt the blower onto its side. Slide it past the controls and into the clip (C) . Secure to the threaded stud using the lock washer and wing nut provided. Ensure that the blower does not touch the fireplace b ...

  • Napoleon Fireplaces BGD42P - page 22

    22 W415-0381 / E / 02.09.06 Position the vibration reducing pad into the clip and onto the threaded stud at the other end, piercing a hole into the pad. The fan assembly must be able to be positioned en- tirely onto the pad. Slide the fan assembly past the controls and into the clip. Secure using the lock washer and nut provided. After extended per ...

  • Napoleon Fireplaces BGD42P - page 23

    23 W415-0381 / E / 02.09.06 slightly . 1. S top! Read the above safety information on this label. 2. Turn off all electric power to the fireplace. 3. Turn the gas knob clockwise to off. 4. Wait five (5) minutes to clear out any gas. If you smell gas including near the floor . S top! Follow "B" in the above safety information on this label ...

  • Napoleon Fireplaces BGD42P - page 24

    24 W415-0381 / E / 02.09.06 Air shutters have been factory set open according to the chart below: These settings are for the maximum horizontal vent run.- Adjustment may be required depending on fuel type, vent configuration and altitude. Closing the air shutter will cause a more yellow flame, but can lead to carboning. Opening the air shutter will ...

  • Napoleon Fireplaces BGD42P - page 25

    25 W415-0381 / E / 02.09.06 1 7 W135-0203 RIGHT CROSSOVER LOG (#6) 1 8 W135-0199 SMALL LEFT LOG (#2) 1 9 W135-0200 SMALL RIGHT LOG (#3) 2 0 W010-0770 BLACK DOOR C / W GLASS 2 1 W455-0026 #38 NATURAL GAS ORIFICE 2 1 W455-0003 #54 PROPANE GAS ORIFICE 22* W361-0014 VERMICULITE 2 3 W500-0028 FIRESTOP SP ACER (FLEX VENTING) 24* W500-0205 RESTRICTOR PLA ...

  • Napoleon Fireplaces BGD42P - page 26

    26 W415-0381 / E / 02.09.06 ...

  • Napoleon Fireplaces BGD42P - page 27

    27 W415-0381 / E / 02.09.06 Pilot will not light. - check if pilot can be lit by a match - check that the wire is connected to the push button ignitor . - check if the push button ignitor needs tightening. - replace the wire if the wire insulation is broken or frayed. - replace the electrode if the ceramic insulator is cracked or broken. - replace ...

  • Napoleon Fireplaces BGD42P - page 28

    28 W415-0381 / E / 02.09.06 Pilot goes out while standing; Main burner is in 'OFF' position. Gas piping is undersized. - turn on all gas appliances and see if pilot flame flutters, dimin- ishes or extinguishes, especially when main burner ignites. Monitor appliance supply working pressure. - check if supply piping size is to code. Correct ...

Fabbricante Napoleon Fireplaces Categoria Outdoor Fireplace

I documenti che otteniamo dal fabbricante del dispositivoNapoleon Fireplaces BGD42P possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Napoleon Fireplaces
- manuali per l’uso BGD42P
- schede prodotto Napoleon Fireplaces
- opuscoli
- o etichette energetiche Napoleon Fireplaces BGD42P
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Napoleon Fireplaces BGD42P.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Napoleon Fireplaces BGD42P, manuali di manutenzione, brevi manuali o manuali utente Napoleon Fireplaces BGD42P. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Napoleon Fireplaces BGD42P.

Manuale completo del dispositivo Napoleon Fireplaces BGD42P, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Napoleon Fireplaces BGD42P dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Napoleon Fireplaces BGD42P.

Il manuale per l’uso completo Napoleon Fireplaces, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Napoleon Fireplaces BGD42P - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Napoleon Fireplaces BGD42P, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Napoleon Fireplaces BGD42P che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Napoleon Fireplaces BGD42P - che ci dovrebbe aiutare nei primi passi durante l'uso Napoleon Fireplaces BGD42P
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Napoleon Fireplaces BGD42P
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Napoleon Fireplaces BGD42P in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Napoleon Fireplaces BGD42P?

Utilizza il modulo sottostante

Se non hai risolto il problema con Napoleon Fireplaces BGD42P con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Napoleon Fireplaces BGD42P è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)