Manuale per l’uso York STELLAR PLUS H4DH018 THRU 060

20 pagine 0.57 mb
Scarica

Vai alla pagina of 20

Summary
  • York STELLAR PLUS H4DH018 THRU 060 - page 1

    TECHNICAL GUIDE STELLAR PLUS TM SPLIT -SYSTEM AIR CONDITIONERS 12 SEER MODELS: H4DH018 THRU 060 (1.5 THRU 5 NOMINAL TONS) Due to contin uous product improv ement, specification s are subjec t to change without n otice. V isit us on the web at www .york.com for the m ost up-to-date te chnical informatio n. Additional r a ting i nformation can be f o ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 2

    036-2102 0-003 Rev. C (0203) 2 Unitary Produ cts Group All dimensions are in i nches. They are subject to change without notice. Certified dimensions will be pr ovided upon request. Physi cal and El ectrical D at a MODE L H4DH018S06 H 4DH024S06 H4DH030S06 H4DH036S06 H4DH042S 06 H4DH048S06 H4DH060S06 Unit Supply V oltage 208/230 – 1 – 60 Normal ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 3

    036-2102 0-003 Rev. C (0203) Unitary Pro ducts Group 3 Procedures: 1.Unit factor y charge liste d on the unit namep late includes refrigeran t for the c ondenser, the smallest e vaporator and for 1 5 f eet of interconnec ting line tubin g. 2.V er ify the orifice size and ad ditional char ge required f or specific eva porator coil in the system u si ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 4

    036-2102 0-003 Rev. C (0203) 4 Unitary Produ cts Group - = No t appl icabl e COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COI L 1 MODEL 1. G2FD co ils availabl e with a fa ctory ins talled horizo ntal drain pan. See pric e pages for specific m odel numbe r . COOLING MODEL ELEC TRIC 2 HEA T KW 2. Single phase units re quire sin ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 5

    036-2102 0-003 Rev. C (0203) Unitary Pro ducts Group 5 COOLING CAP ACI TY - Upf l ow , Downflow, & Horizont al Furnaces and Coils * UNIT MODEL FURNACE** COIL MODE L COO LING CFM RANGE (MIN.-M AX.) W RA TED CFM NET MBH SEER W/O TXV SEER + TXV 1 EER TOTAL SE N S. H4DH018S06 575 725 14,17 G1F A024S14,17 650 18.2 13.7 12.20 - 10.60 14 G1F A030S 14 ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 6

    036-2102 0-003 Rev. C (0203) 6 Unitary Produ cts Group * Require s a 2FD B lower Time Delay u nless a standa rd furn ace is equip ped with one. ** Refer to Quick Select ion Chart for sp ecific furnace match-up . H4DH042S06 1225 1575 17 G1F A048S 17 1400 41.0 30.8 12.15 - 10.70 21,24 G1F A048S21 1400 41.5 31.1 12.30 - 10.80 21,24 G1F A060S21,24 1400 ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 7

    036-2102 0-003 Rev. C (0203) Unitary Pro ducts Group 7 COOLING CAP AC ITY - With V ar iable Speed Fu rnaces UN IT M ODEL V ARIABL E SPEED FURNACE MODE L COIL MODEL 1 W COO LING RA TED CFM NET MBH SEER W/O TXV SEER + TXV 2 EER TOTAL SE N S. 1 PH 12 SEER AC / P1DU / P1XD / P1XU - V ARIABLE SP EED 3 H4DH018S06 P1DUA12V G 1F A024S14 14 645 18.8 14.1 14 ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 8

    036-2102 0-003 Rev. C (0203) 8 Unitary Produ cts Group For No tes see Pa ge 8. H4DH036S06 P1DUB16V G 1F A036S17 17 1220 35.8 26.5 13.00 - 1 1.80 P1DUB16V G 1F A048S17 17 1220 38.0 28.1 13.50 - 12.40 P1DUB16V G1HD036 - 1220 35.8 26.5 13. 00 - 1 1.65 P1DUB16V G1HD048 - 1220 38.5 28.5 13. 50 - 1 1.85 P1DUB16V G1UA 036S17 17 1220 35.8 26.5 13.00 - 1 1. ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 9

    036-2102 0-003 Rev. C (0203) Unitary Pro ducts Group 9 H4DH048S06 P1DUB16V G 1F A048S17 17 1500 48.5 36.4 13.00 - 1 1.85 P1DUB16V G1UA 048S17 17 1500 48.5 36.4 13.00 - 1 1.85 P1DUC20V G1F A048S 21 21 1610 48.0 36.0 12. 45 - 1 1.20 P1DUC20V G1F A060S 21 21 1610 49.5 37.1 13. 30 - 1 1.60 P1DUC20V G1HD048 - 1610 49.0 36.8 12.25 - 1 1.35 P1DUC20V G1UA0 ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 10

    036-2102 0-003 Rev. C (0203) 10 Unitary Produ cts Group 1. For co ndensin g unit only. Does not include effect of evap orator mo tor pow er or he at. 2. Perfo rmance ba sed on 15 ° superhe at and 15° sub-cooli ng at con densing unit . a. Increas e capacity 1% f or each 2° increas e in sub-coo ling. b. Decrease capacity 1% fo r each 2° de crease ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 11

    036-2102 0-003 Rev. C (0203) Unitary Pro ducts Group 11 TYPICAL INST ALLA TIO N TYPICAL FIELD WIRING - 1 PHAS E APPLICATION L INST ALLA T ION THERMOST A T TO INDOOR BLOWER TO COI L NEC CLASS 2 WIRING NEC CLASS 1 WIRING TO POWER SUPPL Y WEA THERPROOF DISCONNECT SWITCH Seal open ing(s) wi th perma gum or equivale nt 24 ” SER VICE ACCESS CLEARANCE 4 ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 12

    036-2102 0-003 Rev. C (0203) 12 Unitary Produ cts Group Multipliers for determining the performance with oth e r indoor sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H4DH018S06 INDOOR COIL MODEL NO. G1F A024S14,17 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 600 650 700 ID DB 85 80 75 70 85 80 75 70 85 80 75 70 ID WB 72 67 62 57 72 6 ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 13

    036-2102 0-003 Rev. C (0203) Unitary Pro ducts Group 13 Multipliers for determining the performance with oth e r indoor sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H4DH024S06 INDOOR COIL MODEL NO. G1F A024S14,17 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 800 850 900 ID DB 85 80 75 70 85 80 75 70 85 80 75 70 ID WB 72 67 62 57 72 6 ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 14

    036-2102 0-003 Rev. C (0203) 14 Unitary Produ cts Group Multipliers for determining the performance with oth e r indoor sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H4DH030S06 INDOOR COIL MODEL NO. G1F A036S17,21 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 980 1030 1080 ID DB 85 80 75 70 85 80 75 70 85 80 75 70 ID WB 72 67 62 57 72 ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 15

    036-2102 0-003 Rev. C (0203) Unitary Pro ducts Group 15 Multipliers for determining the performance with oth e r indoor sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H4DH036S06 INDOOR COIL MODEL NO. G1F A036S17,21 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 1 100 1200 1300 ID DB 85 80 75 70 85 80 75 70 85 80 75 70 ID WB 72 67 62 57 ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 16

    036-2102 0-003 Rev. C (0203) 16 Unitary Produ cts Group Multipliers for determining the performance with oth e r indoor sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H4DH042S06 INDOOR COIL MODEL NO. G1F A048S17 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 1300 1400 1500 ID DB 85 80 75 70 85 80 75 70 85 80 75 70 ID WB 72 67 62 57 72 6 ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 17

    036-2102 0-003 Rev. C (0203) Unitary Pro ducts Group 17 Multipliers for determining the performance with oth e r indoor sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H4DH048S06 INDOOR COIL MODEL NO. G1F A048S21 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 1450 1600 1750 ID DB 85 80 75 70 85 80 75 70 85 80 75 70 ID WB 72 67 62 57 72 6 ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 18

    036-2102 0-003 Rev. C (0203) 18 Unitary Produ cts Group Multipliers for determining the performance with oth e r indoor sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H4DH060S06 INDOOR COIL MODEL NO. G1F A060S21,24 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 1600 1800 2000 ID DB 85 80 75 70 85 80 75 70 85 80 75 70 ID WB 72 67 62 57 7 ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 19

    036-2102 0-003 Rev. C (0203) Unitary Pro ducts Group 19 MA TCHIN G INDOOR COMPONENTS G1UA 1/2 CASED UPFLOW G1HD HORIZONT AL DUCT G2FD* MUL TI-POSITION (UPFLOW , HORIZONT AL AND DOWNFLOW) * Available with factory inst alled horizontal drain pan. ADD-ON COILS - FOR FURNACE APPLICA TIONS G1NA UNCASED UPFLOW G1F A FULL CASED UPFLOW AIR HANDLERS - FOR N ...

  • York STELLAR PLUS H4DH018 THRU 060 - page 20

    Subject to change without notice. Printed in U.S.A. 036-21020-003 Rev. C ( 0203) Copyright © by York International Corp. 2003. All rights reserved. Supersedes: 036-21020-003 Rev. B (0702) Unit ary 5005 Norma n Product Y ork OK Group Drive 7306 9 NOTES ...

Fabbricante York Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoYork STELLAR PLUS H4DH018 THRU 060 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici York
- manuali per l’uso STELLAR PLUS H4DH018 THRU 060
- schede prodotto York
- opuscoli
- o etichette energetiche York STELLAR PLUS H4DH018 THRU 060
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso York STELLAR PLUS H4DH018 THRU 060.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione York STELLAR PLUS H4DH018 THRU 060, manuali di manutenzione, brevi manuali o manuali utente York STELLAR PLUS H4DH018 THRU 060. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto York STELLAR PLUS H4DH018 THRU 060.

Manuali per l’uso simili

Manuale completo del dispositivo York STELLAR PLUS H4DH018 THRU 060, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare York STELLAR PLUS H4DH018 THRU 060 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti York STELLAR PLUS H4DH018 THRU 060.

Il manuale per l’uso completo York, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale York STELLAR PLUS H4DH018 THRU 060 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice York STELLAR PLUS H4DH018 THRU 060, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per York STELLAR PLUS H4DH018 THRU 060 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo York STELLAR PLUS H4DH018 THRU 060 - che ci dovrebbe aiutare nei primi passi durante l'uso York STELLAR PLUS H4DH018 THRU 060
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del York STELLAR PLUS H4DH018 THRU 060
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio York STELLAR PLUS H4DH018 THRU 060 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su York STELLAR PLUS H4DH018 THRU 060?

Utilizza il modulo sottostante

Se non hai risolto il problema con York STELLAR PLUS H4DH018 THRU 060 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con York STELLAR PLUS H4DH018 THRU 060 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)