    Installation Manual 20002158, Rev DI March 2014 Micro Motion ® ELITE ® Coriolis Flow and Density Sensors ...

  • Emerson 20002158 - page 2

    Safety and approval information This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EC declaration of conformity for directives that apply to this product. The EC declaration of conformity, with all applicable European directives, and the ...

  • Emerson 20002158 - page 3

    Contents Chapter 1 Planning ........................................................................................................................... 1 1.1 Installation checklist ........................................................................................................................1 1.2 Best practices ............................ ...

  • Emerson 20002158 - page 4

    Contents ii Micro Motion ELITE ...

  • Emerson 20002158 - page 5

    1 Planning Topics covered in this chapter: • Installation checklist • Best practices • Temperature limits • Recommendations for hygienic and self-draining applications 1.1 Installation checklist □ Make sure that the hazardous area specified on the approval tag is suitable for the environment in which the meter will be installed. □ Verif ...

  • Emerson 20002158 - page 6

    □ For optimal performance, install the sensor in the preferred orientation. The sensor will work in any orientation as long as the flow tubes remain full of process fluid. Preferred sensor orientation Table 1-3: Process Preferred orientation Alternate orientations Liquids Gases Slurries □ Install the meter so that the flow direction arrow on th ...

  • Emerson 20002158 - page 7

    • There are no pipe run requirements for Micro Motion sensors. Straight runs of pipe upstream or downstream are unnecessary. • If the sensor is installed in a vertical pipeline, liquids and slurries should flow upward through the sensor. Gases may flow upward or downward. • Keep the sensor tubes full of process fluid. • For halting flow thr ...

  • Emerson 20002158 - page 8

    Ambient and process temperature limits for ELITE CMF***M/L/H/P (excludes cryogenic modifications) and CMFS007-015 meters Figure 1-1: 140 (60) –40 (–40) 113 (45) –148 (–100) –400 (–240) 400 (204) 140 (60) A B C D D A. Ambient temperature °F (°C) B. Process temperature in °F (°C) C. All available electronic options D. Extended or remo ...

  • Emerson 20002158 - page 9

    Ambient and process temperature limits for cryogenic ELITE meters Figure 1-3: 140 (60) –40 (–40) –148 (–100) –400 (–240) 176 (80) A B C D A. Ambient temperature °F (°C) B. Process temperature in °F (°C) C. All available electronic options D. Extended or remote mount electronics only Ambient and process temperature limits for high te ...

  • Emerson 20002158 - page 10

    Ambient and process temperature limits for Super Duplex ELITE meters Figure 1-5: 140 (60) –40 (–40) –148 (–100) –40 (–40) 400 (204) A B C D A. Ambient temperature °F (°C) B. Process temperature in °F (°C) C. All available electronic options D. Extended or remote mount electronics only 1.4 Recommendations for hygienic and self- drain ...

  • Emerson 20002158 - page 11

    Installation for self-draining applications Figure 1-6: A B C A. Process pipeline B. Direction of normal process flow C. Direction of drainage Planning Installation Manual 7 ...

  • Emerson 20002158 - page 12

    2 Mounting Topics covered in this chapter: • Recommendations for lifting heavy meters • Mount the sensor • Mount electronics of high-temperature sensors • Mount a CMF010 sensor to a wall or pole • Mount a CMFS007, CMFS010 or CMFS015 sensor in a bracket • Mount a CMFS025, CMFS040 or CMFS050 sensor in a wall mount bracket • Secure wafer ...

  • Emerson 20002158 - page 13

    Acceptable lifting points Figure 2-1: Center of gravity for large meters Figure 2-2: A A. Typical center of gravity Note Complete and detailed dimensional drawings, including the location of the center of gravity, can be found through the product drawings link in our online store ( www.micromotion.com/onlinestore ). 2.2 Mount the sensor Use your co ...

  • Emerson 20002158 - page 14

    CAUTION! Do not lift the sensor by the electronics or purge connections. Lifting the sensor by the electronics or purge connections can damage the device. Mounting the sensor Figure 2-3: Notes • Do not use the sensor to support the piping. • The sensor does not require external supports. The flanges will support the sensor in any orientation. ( ...

  • Emerson 20002158 - page 15

    Components of a high-temperature sensor Figure 2-4: B A C D A. Sensor B. Electronics C. Mounting bracket D. Flexible conduit (minimum bend radius 6" [152 mm]) With some large meter sizes, the meter may ship with the electronics attached to the sensor case. The meter cannot be operated in this configuration. Detach the electronics bracket from ...

  • Emerson 20002158 - page 16

    Removing electronics from the sensor case Figure 2-5: A A. Detach electronics from sensor case and mount to a wall or instrument pole Procedure • For wall mounting, use four 5/16" or four M8 bolts to secure the mounting bracket. Mounting 12 Micro Motion ELITE ...

  • Emerson 20002158 - page 17

    Wall-mount components Figure 2-6: A B C A. Wall or flat surface B. Electronics (enhanced core processor shown) C. Flexible conduit • For mounting to an instrument pole, use a 2-inch U-bolt pipe kit to secure the mounting bracket. Mounting Installation Manual 13 ...

  • Emerson 20002158 - page 18

    Pole-mount components Figure 2-7: A B C A. Instrument pole B. Electronics (enhanced core processor shown) C. Flexible conduit 2.4 Mount a CMF010 sensor to a wall or pole The CMF010 sensor has an optional mounting configuration for use with small or flexible pipeline. If the pipeline adequately supports the sensor, this procedure can be skipped. 1. ...

  • Emerson 20002158 - page 19

    Optional mounting for CMF010 sensors Figure 2-8: A B C A. Two user-supplied 5/16" (M8) bolts B. Junction box or core processor (junction box shown) C. Mounting surface 2. If necessary, install rigid standoffs between the sensor and the mounting surface. 3. Using two user-supplied 5/16" (M8) bolts (minimum length 2 1/4" [58 mm]), secu ...

  • Emerson 20002158 - page 20

    Mounting bracket for CMFS007, CMFS010, and CMFS015 Figure 2-9: A B C A. Mounting bracket B. Mounting holes C. Supplied U-bolts 2.6 Mount a CMFS025, CMFS040 or CMFS050 sensor in a wall mount bracket The CMFS025, CMFS040, and CMFS050 sensors have an optional wall mounting bracket. 1. Assemble the bracket. Assembled wall mounting bracket for CMFS025, ...

  • Emerson 20002158 - page 21

    3. Place the sensor into the bracket. 4. Secure the sensor in the bracket with the supplied fasteners. CMFS025, CMFS040, or CMFS050 wall mounted using bracket Figure 2-11: 2.7 Secure wafer-style process connections A wafer-style connection lets you clamp the sensor into the pipeline. A wafer installation kit is shipped with a wafer-style sensor. 1. ...

  • Emerson 20002158 - page 22

    Wafer-style connection components Figure 2-12: D C B A E A. Flange nut B. Gasket (user-supplied) C. Alignment ring D. Flange bolt E. Sensor wafer 3. Insert the flange bolts through both process connections, and thread the flange nuts onto the bolts. 4. With your fingers, tighten the flange nuts. 5. Rotate the sensor alignment rings in the direction ...

  • Emerson 20002158 - page 23

    6. With a wrench, tighten the nuts in an alternating order. 2.8 Attach extended electronics If you ordered a sensor with extended electronics, you will need to install the extender onto the sensor case. Note Extended core processors are matched at the factory to specific sensors. Keep each core processor together with the sensor with which it was s ...

  • Emerson 20002158 - page 24

    Feedthrough and extender components Figure 2-14: G H E D C A B F A. Transmitter or core processor B. Extender C. O-ring D. Feedthrough E. Clamping ring F. Clamping screw G. Plastic plug H. Plastic cap 2. Loosen the clamping screw and remove the clamping ring. Leave the O-ring in place on the feedthrough. 3. Remove and recycle the plastic plug from ...

  • Emerson 20002158 - page 25

    3 Wiring Topics covered in this chapter: • Options for wiring • Connect 4-wire cable • Connect 9-wire cable 3.1 Options for wiring The wiring procedure you follow depends on which electronics option you have. Wiring procedures by electronics option Table 3-1: Electronics option Wiring procedure Integral transmitter No wiring is required betwe ...

  • Emerson 20002158 - page 26

    3.2 Connect 4-wire cable 3.2.1 Prepare the 4-wire cable Important For user-supplied cable glands, the gland must be capable of terminating the drain wires. Note If you are installing unshielded cable in continuous metallic conduit with 360º termination shielding, you only need to prepare the cable – you do not need to perform the shielding proce ...

  • Emerson 20002158 - page 27

    4-wire cable preparation Figure 3-1: Cable layout Run conduit to sensor Metal conduit Wrap the drain wires twice around the shield and cut off the excess drain wires. Micro Motion cable gland Pass the wires through the gland. Terminate the drain wires inside the gland. Cable glands Remove the core processor cover Go to the shielding procedure Done ...

  • Emerson 20002158 - page 28

    4-wire cable shielding Figure 3-2: Assemble the Gland 1. Fold the shield or braid back over the clamping insert and 1/8 inch (3 mm) past the O-ring. 2. Install the gland body into the conduit opening on the core processor housing. 3. Insert the wires through gland body and tighten the gland nut onto the gland body. Apply the Heat Shrink 1. Slide th ...

  • Emerson 20002158 - page 29

    • Twisted pair construction. • Applicable hazardous area requirements, if the core processor is installed in a hazardous area. • Wire gauge appropriate for the cable length between the core processor and the transmitter. Wire gauge Table 3-2: Wire gauge Maximum cable length VDC 22 AWG (0.35 mm 2 ) 300 ft (90 m) VDC 20 AWG (0.5 mm 2 ) 500 ft ( ...

  • Emerson 20002158 - page 30

    Core processor terminals Figure 3-3: Connect the wires to the transmitter terminals (see the transmitter manual) Reinstall and tighten the core processor cover Core processor type From Step 1 or 2 Connect the wires to the core processor terminals: Red wire > Terminal 1 (Power supply +) Black wire > Terminal 2 (Power supply –) White wire > ...

  • Emerson 20002158 - page 31

    3. Match the wires color for color. For wiring at the transmitter or remote core processor, refer to the transmitter documentation. 4. Tighten the screws to hold the wires in place. 5. Ensure integrity of gaskets, then tightly close and seal the junction box cover and all housing covers on the transmitter or core processor. 6. Refer to the transmit ...

  • Emerson 20002158 - page 32

    4 Grounding The meter must be grounded according to the standards that are applicable at the site. The customer is responsible for knowing and complying with all applicable standards. Prerequisites Micro Motion suggests the following guides for grounding practices: • In Europe, IEC 79-14 is applicable to most installations, in particular Sections ...

  • Emerson 20002158 - page 33

    5 Supplementary information Topics covered in this chapter: • Purge the sensor case • About rupture disks 5.1 Purge the sensor case If the sensor has purge fittings, they should remain sealed at all times. After a purge plug has been removed, the sensor case should be purged with argon or nitrogen and resealed. Purging the case protects interna ...

  • Emerson 20002158 - page 34

    4. Connect the supply of nitrogen or argon gas to the inlet purge connection or open inlet purge line. Leave the outlet connection open. • Exercise caution to avoid introducing dirt, moisture, rust, or other contaminants into the sensor case. • If the purge gas is heavier than air (such as argon), locate the inlet lower than the outlet, so that ...

  • Emerson 20002158 - page 35

    Purge time (continued) Table 5-1: Sensor model Purge rate, in ft 3 /hr (l/h) Time, in minutes CMFS100 20 (566) 6 CMFS150 20 (566) 6 7. At the appropriate time, shut off the gas supply, then immediately seal the purge outlet and inlet connections with the purge plugs. Note Avoid pressurizing the sensor case. If pressure inside the case elevates abov ...

  • Emerson 20002158 - page 36

    *20002158* 20002158 Rev DI 2014 Micro Motion Inc. USA Worldwide Headquarters 7070 Winchester Circle Boulder, Colorado 80301 T +1 303-527-5200 T +1 800-522-6277 F +1 303-530-8459 www.micromotion.com Micro Motion Europe Emerson Process Management Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 318 495 555 F +31 (0) 318 495 556 www.micromotion.nl M ...

Fabbricante Emerson Categoria Stereo System

I documenti che otteniamo dal fabbricante del dispositivoEmerson 20002158 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Emerson
- manuali per l’uso 20002158
- schede prodotto Emerson
- opuscoli
- o etichette energetiche Emerson 20002158
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Emerson 20002158.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Emerson 20002158, manuali di manutenzione, brevi manuali o manuali utente Emerson 20002158. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Emerson 20002158.

Manuali per l’uso simili

Manuale completo del dispositivo Emerson 20002158, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Emerson 20002158 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Emerson 20002158.

Il manuale per l’uso completo Emerson, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Emerson 20002158 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Emerson 20002158, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Emerson 20002158 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Emerson 20002158 - che ci dovrebbe aiutare nei primi passi durante l'uso Emerson 20002158
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Emerson 20002158