    Manual 2100-467K Page 1 of 24 SINGLE P ACKAGE AIR CONDITIONERS MODELS P A13242-A P A13302-A P A13362-A P A13362-B P A13422-A P A13422-B P A13422-C P A13482-A P A13482-B P A13482-C P A13602-A P A13602-B P A13602-C INST ALLA TION INSTRUCTIONS Manual : 2100-467K Supersedes: 2100-467J File: V olume II T ab 10 Date: 07-25-12 Bard Manufacturing Company , ...

  • Bard PA13602-B - page 2

    Manual 2100-467K Page 2 of 24 CONTENTS Getting Other Informations and Publications ......... 3 General Instructions Important ................................................................. 4 Shipping Damage ..................................................... 4 General ................................................................. 4 Field In ...

  • Bard PA13602-B - page 3

    Manual 2100-467K Page 3 of 24 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. Y ou can usually nd these at your local library or purchase them directly from the publisher . Be sure to consult current edition of each standard. National Electrical Code ....................... ANS ...

  • Bard PA13602-B - page 4

    Manual 2100-467K Page 4 of 24 General InstructIOns ImPOrt ant The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. All duct work, supply and return ducts, must be properly sized for the design airow requirement of the equipment. ACCA is an excellent guide to proper sizing. All duct ...

  • Bard PA13602-B - page 5

    Manual 2100-467K Page 5 of 24 t able 2 electrIcal sPecIFIca tIOns model P a13242-a P a13302-a P a13362-a P a13362-b P a13422-a P a13422-b P a13422-c P a13482-a P a13482-b P a13482-c P a13602-a P a13602-b P a13602-c electric rating – 60 hz – circuit a 230/208-60-1 230/208-60-1 230/208-60-1 230/208-60-3 230/208-60-1 230/208-60-3 460-60-3 230/208- ...

  • Bard PA13602-B - page 6

    Manual 2100-467K Page 6 of 24 t able 3 OPtIOnal FIelD Inst alleD hea ter P acKaGes Onl Y t O be useD WIth the mODels InDIca teD heater Package model V olts & Phase P a13242-a P a13302-a P a13362-a P a13362-b P a13422-a P a13422-b P a13422-c P a13482-a P a13482-b P a13482-c P a13602-a P a13602-b P a13602-c EHP323-A05 240/208-1 X X X EHP323-A10 2 ...

  • Bard PA13602-B - page 7

    Manual 2100-467K Page 7 of 24 t able 4 OPtIOnal FIelD Inst alleD electrIc hea ter t able IMPORT ANT : While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all existing local codes.   Maximumsizeofthet ...

  • Bard PA13602-B - page 8

    Manual 2100-467K Page 8 of 24 FIGure 1a DImensIOns OF unIts Return open i ng Dr ain a cc e ss S upp ly open i ng Hi gh volt age k no ck out Lo w volt age k no ck out a cc e ss door C on trol pane l door H ea ter pa ck age a cc e ss panel Compre ss or H ea ter pa ck age k no ck out A E C D L W B F C onden ser a ir C onden ser a ir intake gr ille int ...

  • Bard PA13602-B - page 9

    Manual 2100-467K Page 9 of 24 FIGure 1b DImensIOns OF unIts A B C D F E D A H G UN IT A B C D E F GH PA /PH1324, 1330, 1336 7 3/16" 38 13/16" 36 3/4" 1 3/8" 33 5/8" 35 1/2" 18 3/16" 17 1/4" PA /PH1342, 1348, 1360 8 3/16" 39 13/16" 36 3/4" 1 3/8" 37 3/4" 39 3/4" 18 1/2" 17 1/ ...

  • Bard PA13602-B - page 10

    Manual 2100-467K Page 10 of 24 Inst alla tIOn lOca tIOn General The unit must be located outside, or in a well ventilated area. It must not be in the space being heated or cooled. A sound absorbing material should be considered if the unit is to be installed in such a position or location that might cause transmission of sound or vibration to the l ...

  • Bard PA13602-B - page 11

    Manual 2100-467K Page 1 1 of 24 36 " mi n. 24 " mi n. 24 " mi n. T he dist an ce be tw een 1 inch cl ea r an ce A cc e ss Air I nl et Com p- N ea res t Structu re Air I nl et S upp ly and Return Duc ts N ea res t Structu re N ea res t Structu re Bu il di ng C on trol P anel A cc e ss C on trol P anel A cc e ss H ea ter P a ck age A c ...

  • Bard PA13602-B - page 12

    Manual 2100-467K Page 12 of 24 FIGure 4 eleV a teD mOuntInG Pla tFOrm Bot h l eg s mus t re st on su rface o f pla tf o rm 32 °F or l owe r c lim a te 12" mi n . i f in 48" mi n. 48" mi n. 32 °F or l owe r c lim a te 12" mi n . i f in on su rface o f pla tf o rm Bot h l eg s mus t re st Pl a tf orm c an be as s hown or s o lid ...

  • Bard PA13602-B - page 13

    Manual 2100-467K Page 13 of 24 FIGure 5 cOnDensa te DraIn traP 5. Other Inst alla tIOns – Many other installations are possible with the packaged air conditioner . No matter what the installation, always consider the following facts: A. Insure that the discharge air is not obstructed in any way so as to cause operation difculties. B. The indoo ...

  • Bard PA13602-B - page 14

    Manual 2100-467K Page 14 of 24 t able 6 thermOst a t WIre sIze transFOrmer t aPs 230/208V , 1 phase and 3 phase equipment employ dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are: ta P ranGe ...

  • Bard PA13602-B - page 15

    Manual 2100-467K Page 15 of 24 E Y 1120 - 445 TH 5220 D 1151 Lo w Voltage Wiring L 2 C O 1 Unit Contr ol Panel Blo ck Y C G R W1 W2 E F Y1 C G R W1 O Y2 W2 D A E L A UX R G E B RC 3 L B Thermostat S ubbase Term i nal H EA T O N UN ITS WITH 15 O R M ORE KW YO Uni t 24V REMO VE JUM PE R FOR 2 STAGE E LECTR IC M IS - 2149 C FIGure 6 lOW VOl t aGe WIrI ...

  • Bard PA13602-B - page 16

    Manual 2100-467K Page 16 of 24 st art uP These units require R-410A refrigerant and Polyol Ester oil. General: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant. 3. Use manifold gauges rated for R-410A (800 psi/250 psi low). 4. R-410A is a binary blend of H ...

  • Bard PA13602-B - page 17

    Manual 2100-467K Page 17 of 24 three Phase scrOll cOmPressOr st art uP InFOrma tIOn (Models P A13362-B; P A13422-B, -C; P A13482-B, -C; P A13602-B, -C) All units with three phase scroll compressors are equipped with a three phase line monitor to prevent compressor damage due to phase reversal. The phase monitor in this unit is equipped with two LED ...

  • Bard PA13602-B - page 18

    Manual 2100-467K Page 18 of 24 lOW Pressure sWItch, bYP ass, anD lOcKOut sequence (standard Feature) If the low pressure switch opens for more that 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will reenergize after the delay-on-make time delay has e ...

  • Bard PA13602-B - page 19

    Manual 2100-467K Page 19 of 24 F an blaDe settInGs Shown in Figure 8 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil. Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly ...

  • Bard PA13602-B - page 20

    Manual 2100-467K Page 20 of 24 (continued on Page 20 in t able 1 1) t able 9 Pressure t able cOOlInG Air T emperature Entering Outdoor Coil Degree F LOW SIDE PRESSURE +4 PSIG HIGH SIDE PRESSURE +10 PSIG T ablesbaseduponratedCFM(airow)acrosstheevaporatorcoil. If incorrect charge suspected (more than + 4psigsuction ...

  • Bard PA13602-B - page 21

    Manual 2100-467K Page 21 of 24 t able 10 Pressure t able LOW SIDE PRESSURE +4 PSIG HIGH SIDE PRESSURE +10 PSIG T ablesbaseduponratedCFM(airow)acrosstheevaporatorcoil. If incorrect charge suspected (more than + 4psigsuction, + 10psigliquid), itisrecommendedrefrigerantchargebereclaimed,? ...

  • Bard PA13602-B - page 22

    Manual 2100-467K Page 22 of 24 suctIOn anD DIscharGe tube brazInG Compliant Scroll compressors have copper plated steel suction and discharge tubes. These tubes are far more rugged and less prone to leaks than copper tubes used on other compressors. Due to different thermal properties of steel and copper , brazing procedures may have to be changed ...

  • Bard PA13602-B - page 23

    Manual 2100-467K Page 23 of 24 FIGure 10 NOTE: Bard Models PA13242; PA13302; PA13362-A, -B; PA13422-A, -B, -C; PA13482-A, -B, -C; PA13602-A, -B, -C contain the X13-Series Motors. trOubleshOOtInG Ge x13-serIes ecm2.3 ™ mOt Ors If the Motor is Running 1. It is normal for the motor to rock back and forth on start up. Do not replace the motor if this ...

  • Bard PA13602-B - page 24

    Manual 2100-467K Page 24 of 24 FIGure 1 1 trOubleshOOtInG Ge x13-serIes ecm2.3 ™ mOt Ors cOnt’D. Model X13 Communication Diagnostics The X13 motor is communicated through 24 V AC low voltage (Thermostat Control Circuit W iring). 1. Start with unit wiring diagram to conrm proper connections and voltage (see Figure 11). 2. Initiate a demand fr ...

Fabbricante Bard Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoBard PA13602-B possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Bard
- manuali per l’uso PA13602-B
- schede prodotto Bard
- opuscoli
- o etichette energetiche Bard PA13602-B
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Bard PA13602-B.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Bard PA13602-B, manuali di manutenzione, brevi manuali o manuali utente Bard PA13602-B. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Bard PA13602-B.

Manuali per l’uso simili

Manuale completo del dispositivo Bard PA13602-B, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Bard PA13602-B dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Bard PA13602-B.

Il manuale per l’uso completo Bard, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Bard PA13602-B - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Bard PA13602-B, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Bard PA13602-B che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Bard PA13602-B - che ci dovrebbe aiutare nei primi passi durante l'uso Bard PA13602-B
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Bard PA13602-B
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Bard PA13602-B in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Bard PA13602-B?

Utilizza il modulo sottostante

Se non hai risolto il problema con Bard PA13602-B con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Bard PA13602-B è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)