    • Refer to Service Manual RS6100004 for installation, op- eration, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. Models listed on page 3. GSH 14 SEER Remote Heat Pump RT6213004 April 2006 This manual is to be used by qualified HV AC technicians only . Goodman does not assume any re ...

  • Goodman Mfg RT6213004 - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROP- ERTY DAMAGE, PERSONAL INJURY OR DEA ...

  • Goodman Mfg RT6213004 - page 3

    PRODUCT IDENTIFICA TION 3 WARNING WARNING DO NOT CONNECT OR USE ANY DEVICE THAT IS NOT DESIGN CERTI- FIED BY GOODMAN FOR USE WITH THIS UNIT. SERIOUS PROPERTY DAMAGE, PERSONAL INJURY, REDUCED UNIT PERFORMANCE AND/OR HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF SUCH NON-APPROVED DEVICES. WARNING WARNING TO PREVENT THE RISK OF PROPERTY DAMAGE, PERS ...

  • Goodman Mfg RT6213004 - page 4

    PRODUCT DESIGN 4 GSH14 SEER split system heat pump models are available in 1 1/2 through 5 ton sizes. They are designed for 208/230 volt single phase applications. Air is drawn through the outdoor coil by a propeller fan, and is discharged vertically out the top of the unit. No additional restriction (ductwork) shall be applied. The suction and liq ...

  • Goodman Mfg RT6213004 - page 5

    5 HEA T PUMP SPECIFICA TIONS GSH14[018-060]1A* (1) Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes . (2) May use fuses or HACR type Circuit Breakers of the same size as noted. NOTE: This data is provided as a guide, it is important to electrically connect the unit and pr ...

  • Goodman Mfg RT6213004 - page 6

    6 COOLING PERFORMANCE DA T A GSH140181A* EXPA NDED PERFORMA NCE DA TA CO OLI NG OP ERA TI ON M ODEL: G SH140181A * / C A*F3131B6A *+TXV / M BR800**-1 Design Subcooling, 9 ±3 °F @ the liquid servic e valve, ARI 95 test conditio ns Outdoor A mbient Temperat ure 65 75 85 95 105 115 Entering Indoor W et Bulb Te mperature I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg RT6213004 - page 7

    7 COOLING PERFORMANCE DA T A GSH140181A* EXPA NDED PERFORMA NCE DA TA C OOL IN G OPER AT ION M ODEL: GSH 140181A * / CA* F 3131B6A *+T XV / M BR800**-1 Design Subcooling, 9 ±3 °F @ the liquid service valve, A R I 95 test conditio ns Ou tdo or Amb ie nt Tem per atu r e 65 75 85 95 105 115 Entering Indoor Wet Bulb T emperature I D B * A i r f l o w ...

  • Goodman Mfg RT6213004 - page 8

    8 COOLING PERFORMANCE DA T A GSH140241A* EXPA NDED PERFO RMA NCE DA TA COOLI NG OPER A TION MO DEL: GSH140 241A * / CA *F3636B6A *+TXV / MBR800** 1 Design Subc ooling 9 ±3 °F @ the li qui d servic e valve, A RI 95 test c ondit ions Outdoor A mbient T emperature 65 75 85 95 105 115 Entering I ndoor Wet Bul b Te mperature I D B * A i r f l o w 5 96 ...

  • Goodman Mfg RT6213004 - page 9

    9 COOLING PERFORMANCE DA T A GSH140241A* EXPA NDED PERFO RMA NCE DATA COOLING OPER A TION MO DEL: GSH140 241A * / CA *F3636B 6A *+TXV / MBR800 **1 Desi gn Subc ooling 9 ±3 °F @ the liqui d se rvice valve, A RI 95 test c onditions Outdoor A m bien t Temperature 65 75 85 95 105 115 Entering I ndoor Wet B ulb T emperatur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg RT6213004 - page 10

    10 COOLING PERFORMANCE DA T A GSH140301A* EXPA NDED PERFORMA NCE DA TA CO OLING O PER AT ION MODEL: GSH140301A * / CA *F3636B6A * +TXV / M BR1200**-1 Design Subcooling 9 ±3 °F @ the liquid service valve, A RI 95 test conditi on s Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg RT6213004 - page 11

    11 COOLING PERFORMANCE DA T A GSH140301A* EXPA NDED PERFORMA NCE DA TA CO OLING O PER AT ION MODEL: GSH140301A * / CA *F3636B6A * +TXV / M BR1200**-1 Design Subcooling 9 ±3 °F @ the liquid service valve, A RI 95 test conditi on s Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg RT6213004 - page 12

    12 COOLING PERFORMANCE DA T A GSH140361A* EXPA NDED PERFORMA NCE DA TA CO OLI NG OPER A TION MO DEL: GSH140361A * / CA* F4860C6A * +TXV / MB R1600**-1 Design Subcooling 9 ± 3°F @ the liquid service valve, A RI 95 test condi tions Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg RT6213004 - page 13

    13 COOLING PERFORMANCE DA T A GSH140361A* EXPA NDED PERFORMA NCE DA TA CO OLI NG OPER A TION MO DEL: GSH140361A * / CA* F4860C6A * +TXV / MB R1600**-1 Design Subcooling 9 ± 3°F @ the liquid service valve, A RI 95 test condi tions Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg RT6213004 - page 14

    14 COOLING PERFORMANCE DA T A GSH140421A* EXPA NDED PERFORMA NCE DATA COOLING OPERA TION M ODEL: GSH140421A* / CA *F4860D6A*+TXV / M BR2000**-1 Design Subcooling, 9 ± 3 °F @ the liquid service valv e, A RI 95 test condit i ons Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb T emperature I D B * A i r f l o w 5 96 36 77 1 ...

  • Goodman Mfg RT6213004 - page 15

    15 COOLING PERFORMANCE DA T A GSH140421A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION MODEL: GSH140421A * / CA*F4860D6A *+TXV / M BR2000**-1 D esign Subcoolin g, 9 ±3 °F @ th e liquid serv ice valve, AR I 95 te st conditi ons Outdoor Ambient Tempe rature 65 75 85 95 105 115 Enteri ng I nd oor W et Bulb Temp eratur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg RT6213004 - page 16

    16 COOLING PERFORMANCE DA T A GSH140481A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION MODEL: GSH140481A * / CA*F4860D6A *+TXV / MBR2000**-1 Design Subcooling 9 ±3 °F @ th e liquid servi ce valve, AR I 95 test condit io ns Outdoor Ambient Temper ature 65 75 85 95 105 115 Enteri ng Ind oor W et Bulb Tempe ratur e I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg RT6213004 - page 17

    17 COOLING PERFORMANCE DA T A GSH140481A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION MODEL: GSH140481A * / CA*F4860D6A *+TXV / M BR2000**-1 Design Su bcooling 9 ±3 °F @ th e liquid serv ice valve, ARI 95 te st conditio ns Outdoor Ambient Tempe rature 65 75 85 95 105 115 Enteri ng I nd oor W et Bulb Temp eratur e I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg RT6213004 - page 18

    18 COOLING PERFORMANCE DA T A GSH140601A* EXPA NDED PERFORMA NCE DATA COOLING OPER A T ION M ODEL: GSH140601A* / CA *F4860D6A* + T XV / M BR2000**-1 Design Subco oling 9 ±3 °F @ th e liquid service valv e, ARI 95 te st con diti ons Outdoor Ambient Tempe rature 65 75 85 95 105 115 Enteri ng Ind oor W et Bulb Temperatur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg RT6213004 - page 19

    19 COOLING PERFORMANCE DA T A GSH140601A* EXPA NDED PERFORMA NCE DATA COOLING OPER A T ION M ODEL: GSH140601A* / CA *F4860D6A* + T XV / M BR2000**-1 Design Subco oling 9 ±3 °F @ th e liquid service valv e, ARI 95 te st con diti ons Outdoor Ambient Tempe rature 65 75 85 95 105 115 Enteri ng Ind oor W et Bulb Temperatur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg RT6213004 - page 20

    20 PERFORMANCE DA T A Outdo or Temp. ° F. Total Btuh Sensib le Btuh Latent Btuh Total Watts 75° 18,900 13,282 5,618 1,367 80° 18,675 13,290 5,385 1,410 85° 18,450 13,295 5,155 1,452 90° 18,225 13,344 4,881 1,489 95° 18,000 13,389 4,611 1,526 100° 17 ,550 13,301 4,249 1,558 105° 17 ,100 13,201 3,899 1,589 110° 16 ,470 12,768 3,702 1,616 115 ...

  • Goodman Mfg RT6213004 - page 21

    21 EXPA NDED PERFO RMANC E DA TA MO DEL: G SH140181A* / CA*F3131B6A*+TXV / M BR800** -1 HEA TING OPERA TION Outdoor A mbient Temperature 65 60 55 50 47 45 40 35 30 25 20 17 1 5 10 5 0 -5 -10 MBh 22.6 21.4 20.2 18.8 18.0 17.4 16.2 14.9 13.6 12.5 11.5 10.9 10.5 9.4 8.3 7. 3 6.2 5.1 Delta T 34.9 33.1 31.1 29.1 27.8 26.9 25.0 23.1 20.9 19.3 17.8 16.8 1 ...

  • Goodman Mfg RT6213004 - page 22

    22 SPLIT SYSTEM HEA TING PERFORMANCE EXPA NDED PE RFO RMA NCE DA TA MODEL: GS H140421A * / CA *F4860D6A *+TXV / MB R2000**-1 HE AT I N G OP E R AT I O N Outdoor A mbient T emperat ure 65 60 55 50 47 45 40 35 30 2 5 20 1 7 15 10 5 - 5 -10 MBh 49.8 47.1 44.4 41. 5 39 .6 3 8 . 43 5 . 63 2 . 93 1 . 22 8 . 82 6 . 62 5 . 12 4 . 12 1 . 71 9 . 21 6 . 81 4 ...

  • Goodman Mfg RT6213004 - page 23

    23 HEA TING SPECIFICA TIONS capacity btuh c.o.p. 4.8 9.6 14.4 19.2 65 22.63 4.23 39.008 55.391 71.7732 88. 156 60 21.42 4.09 37.802 54.185 70.5672 86. 950 55 20.16 3.93 36.542 52.925 69.3072 85. 690 50 18.85 3.75 35.228 51.611 67.9932 84. 376 45 17.44 3.54 33.824 50.207 66.5892 82. 972 40 16.20 3.36 32.582 48.965 65.3472 81. 730 35 14.94 3.16 31.32 ...

  • Goodman Mfg RT6213004 - page 24

    24 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a s ...

  • Goodman Mfg RT6213004 - page 25

    WIRING DIAGRAMS 25 TO AVOID POSSI BLE ELECTRI CAL SHOCK, PERSONAL I NJURY, OR DEATH, DI SCONNECT THE POWER BEFORE SERVI C ING. WARNING ! GSH140[18-60]1A* US E N .E .C. CL AS S 2 WI R E NOTES : 1) TO INDOOR U NIT LOW VOL T AGE TER MINAL BLO CK & INDO OR TH ER M O ST A T . 2) STA RT AS SI ST FAC TO R Y E QUI P PED WH EN REQ U I RE D. 3) C RA NKC ...

Fabbricante Goodman Mfg Categoria Heat Pump

I documenti che otteniamo dal fabbricante del dispositivoGoodman Mfg RT6213004 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Goodman Mfg
- manuali per l’uso RT6213004
- schede prodotto Goodman Mfg
- opuscoli
- o etichette energetiche Goodman Mfg RT6213004
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Goodman Mfg RT6213004.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Goodman Mfg RT6213004, manuali di manutenzione, brevi manuali o manuali utente Goodman Mfg RT6213004. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Goodman Mfg RT6213004.

Manuali per l’uso simili

Manuale completo del dispositivo Goodman Mfg RT6213004, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Goodman Mfg RT6213004 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Goodman Mfg RT6213004.

Il manuale per l’uso completo Goodman Mfg, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Goodman Mfg RT6213004 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Goodman Mfg RT6213004, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Goodman Mfg RT6213004 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Goodman Mfg RT6213004 - che ci dovrebbe aiutare nei primi passi durante l'uso Goodman Mfg RT6213004
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Goodman Mfg RT6213004