    Standard-Eff iciency Rooftop Units with: • Exclusive integrated gas control board with diagnostics • Alumagard™ heat exchanger coating • Induced-draft fan for gas combustion • T ubular , dimpled heat exchangers • Pre-painted galvanized steel cabinet for long life and quality appearance • Commercial strength baserails with built-in rig ...

  • Bryant 580D - page 2

    The IGC also contains burner control logic for accurate and dependable gas ignition. The LED is visible without removing the unit control box access panel. This LED fault-notification system reduces service person troubleshooting time and mini- mizes service costs. The IGC also maximizes heating efficiency by controlling evaporator-fan on and off ...

  • Bryant 580D - page 3

    PROVEN COMPRESSOR RELIABILITY — Design techniques feature computer programmed balance between compressor , condenser , and evaporator. Hermetic (036-150 units) and semi- hermetic (180-300 units) compressors with suction and discharge service valves are equipped with compressor over- current and overtemperature protection to ensure dependability . ...

  • Bryant 580D - page 4

    MODEL NUMBER NOMENCLA TURE *Contains high pressure, (loss-of-charge) low-pressure, and freeze protec- tion cutout switches. NOTE: The example model number 580DEV090180CB designates a 7 1 ⁄ 2 ton 460-3-60 volt gas/electric rooftop unit with 180,000 Btuh natural gas heat, Durablade economizer , and alternate drive. 580D036-150 MODELS ONL Y 4 ...

  • Bryant 580D - page 5

    MODEL NUMBER NOMENCLA TURE (cont) 579F180-300 MODELS ONL Y NOTE: The example model number 579FEV180230CB designates a 15-ton 460-3-60 volt gas/electric rooftop unit with 230,000 Btuh natural gas heat input, economizer , and the standard low-medium fan drive static capability . 5 ...

  • Bryant 580D - page 6

    ARI* CAP ACITY RA TINGS UNIT 580D NOMINAL TONS ST ANDARD CFM NET COOLING CAP ACITY (Btuh) TOT AL kW SEER† SOUND RA TING (Bels) Belt Drive Direct Drive 036 3 1200 35,000 4.0 10.0 9.7 8.2 048 4 1600 47,000 5.5 10.0 9.7 8.2 060 5 2000 57,000 6.7 10.0 9.7 8.2 UNIT NOMINAL TONS ST ANDARD CFM NET COOLING CAP ACITY (Btuh) TOT AL kW EER SOUND RA TING (Be ...

  • Bryant 580D - page 7

    ARI* CAP ACITY RA TINGS (cont) HEA TING CAP ACITIES AND EFFICIENCIES — 580D036-150 UNIT 580D HEA TING INPUT (Btuh) Stage 2/Stage 1 OUTPUT CAP ACITY (Btuh) TEMPERA TURE RISE (F) AFUE (%) STEADY -ST A TE EFFICIENCY (%) CALIFORNIA SEASONAL EFFICIENCY (%) 036 074 —/ 72,000 59,200 25-55 80.0 80.0 77.2 036 1 15 1 15,000/ 82,000 92,000 55-85 80.0 80.0 ...

  • Bryant 580D - page 8

    PHYSICAL DA T A — 580D036-072 UNIT SIZE 580D 036 048 060 072 NOMINAL CAP ACITY (tons) 3456 OPERA TING WEIGHT (lb) Unit Al/Al* 460 470 490 565 Al/Cu* 465 476 497 576 Cu/Cu* 468 482 505 587 Economizer Durablade 34 34 34 34 Parablade 42 42 42 42 Roof Curb† 11 5 11 5 11 5 11 5 COMPRESSOR Hermetic Quantity 1111 No. Cylinders (per Circuit) 2222 Oil ( ...

  • Bryant 580D - page 9

    PHYSICAL DA T A — 580D036-072 (cont) UNIT SIZE 580D 036 MEDIUM/ HIGH HEA T 048 LOW/MEDIUM/ HIGH HEA T 060 LOW/MEDIUM/ HIGH HEA T 072 LOW/MEDIUM/ HIGH HEA T FURNACE SECTION Rollout Switch Cutout T emp (F)** 195 195 195 195 Burner Orifice Diameter (in. ...drill size) Natural Gas Std .1 13...33 .1 13...33/.1 13...33/.129...30 .1 13...33/.1 13...33/ ...

  • Bryant 580D - page 10

    PHYSICAL DA T A — 580D090-150 UNIT SIZE 580D 090 102 120 150 NOMINAL CAP ACITY (tons) 7 1 ⁄ 2 8 1 ⁄ 2 10 12 1 ⁄ 2 OPERA TING WEIGHT (lb) Unit Al/Al* 870 880 1035 1050 Al/Cu* 881 896 1057 1077 Cu/Cu* 893 907 1080 1 100 Economizer Durablade 44 44 44 44 Parablade 62 62 62 62 Roof Curb† 143 143 143 143 COMPRESSOR Hermetic Quantity 2222 No. Cy ...

  • Bryant 580D - page 11

    PHYSICAL DA T A — 580D090-150 (cont) UNIT SIZE 580D 090 LOW/MEDIUM/ HIGH HEA T 102 LOW/MEDIUM/ HIHG HEA T 120 LOW/MEDIUM/ HIGH HEA T 150 LOW/ MEDIUM HEA T FURNACE SECTION Rollout Switch Cutout T emp (F)†† 195 195 195 195 Burner Orifice Diameter (in. ...drill size) Natural Gas Std .120...31 .120...31 .120...31/.120...31/.129...30 .120...31/.1 ...

  • Bryant 580D - page 12

    PHYSICAL DA T A — 579F180-300 UNIT SIZE 579F 180 216 240 300 NOMINAL CAP ACITY (tons) 15 18 20 25 OPERA TING WEIGHT (lb) Unit Al/Al* 1650 2150 2200 2250 Economizer 11 0 11 0 11 0 11 0 Roof Curb† 200 200 200 200 COMPRESSOR Semi-Hermetic Model No. ...Quantity (Number of Cylinders) 06D-537...1 (6) 06D-824...1 (6) 06D-818...1 (4) 06D-824...2 (6) 06 ...

  • Bryant 580D - page 13

    PHYSICAL DA T A — 579F180-300 (cont) UNIT SIZE 579F 180 LOW/HIGH HEA T 216 LOW/HIGH HEA T 240 LOW/HIGH HEA T 300 LOW/HIGH HEA T FURNACE SECTION Rollout Switch Cutout T emp (F)†† 190 190 190 190 Burner Orifice Diameter (in. ...drill size) Natural Gas 0.1405...28/0.136...29 0.1405...28/0.136...29 0.1405...28/0.136...29 0.1405...28/0.136...29 T ...

  • Bryant 580D - page 14

    OPTIONS AND ACCESSORIES ITEM OPTION* ACCESSOR Y† Parablade Economizer (036-150 only) X Parablade Economizer with Power Exhaust (036-150) X Integrated Economizer (180-300) XX Durablade Integrated Economizer (036-150; Includes Hood) XX Manual Outdoor-Air Damper (ordered as standard on 180-300 units without optional economizer) XX Controls Upgrade K ...

  • Bryant 580D - page 15

    OPTIONS AND ACCESSORIES (cont) LIQUID PROP ANE (LP) CONVERSION KITS DURABLADE ECONOMIZER (SIZES 036-150) Exclusive Durablade economizer damper design saves energy while providing economical and reliable cooling. A sliding plate on the face of the economizer controls the amount of outdoor air entering the system. Closed, it provides a leakproof seal ...

  • Bryant 580D - page 16

    OPTIONS AND ACCESSORIES (cont) ACCUSENSOR™ II CONTROL (036-150 Only) MINIMUM POSITION OPEN 3 1 T P P1 T1 4 2 5 S S O D C TR B REV. B 198818A % H U M I D I T Y 90 70 60 30 10 D C B A 60 65 70 75 55 50 85 80 DAMPER DAMPER CLOSED OPEN OUTDOOR TEMP . ° F REV. 97-3672 CW–SETPOINTS–CCW CONTACTS SHOWN IN HIGH ENTHALPY RUSH AT 24VAC 3 mA MIN. A T 11 ...

  • Bryant 580D - page 17

    BASE UNIT DIMENSIONS — 580D036-072 UNIT 580D CORNER WEIGHT* ABC D lb kg lb kg lb kg lb kg 036 140 63.5 105 47.6 159 72.1 56 25.4 048 142 64.4 106 48.1 162 73.5 60 27.2 060 150 68.0 115 52.2 160 72.6 65 29.5 072 165 74.8 136 61.7 200 90.7 64 29.0 * Weights are for unit only (aluminum plate fins) and do not include options or crating. CONNECTION S ...

  • Bryant 580D - page 18

    BASE UNIT DIMENSIONS — 580D090-150 UNIT 580D CORNER WEIGHT* DIMENSIONS A B C D ‘ ‘H’ ’ ‘‘J’ ’ ‘‘K’ ’ ‘ ‘L ’ ’ lb kg lb kg lb kg lb kg ft-in. mm ft-in. mm ft-in. mm ft-in. mm 090 189 86 161 73 239 109 280 127 1-2 7 ⁄ 8 378 3-5 5 ⁄ 16 1050 2-9 11 ⁄ 16 856 2- 2 7 ⁄ 16 672 102 191 87 163 74 242 1 10 284 129 3-3 ...

  • Bryant 580D - page 19

    BASE UNIT DIMENSIONS — 579F180,216 UNIT 579F DIMENSIONS XY Z ft-in. mm ft-in. mm ft-in. mm 180 3-2 965 4-0 1219 1-10 559 216 3-7 1090 3-2 965 1- 8 508 UNIT 579F CORNER WEIGHT* ABCD lb kg Lb kg lb kg lb kg 180 384 174 370 168 358 162 538 244 216 520 235 508 230 486 220 636 288 *Weights are for unit only (aluminum plate fins) and do not in- clude ...

  • Bryant 580D - page 20

    BASE UNIT DIMENSIONS — 579F240,300 UNIT 579F CORNER WEIGHT* DIMENSION X ABCD lb kg lb kg lb kg lb kg ft-in. mm 240 520 235 508 230 532 241 640 290 3-2 965 300 527 239 545 247 578 262 600 272 3-7 1092 *Weights are for unit only (aluminum plate fins) and do not include op- tions or crating. NOTES: 1. Dimensions in ( ) are in millimeters. 2. Center ...

  • Bryant 580D - page 21

    ACCESSOR Y DIMENSIONS Roof Curb — 580D036-072 ROOF CURB ACCESSOR Y ‘‘ A’’ UNIT SIZE 580D CRRFCURB001A00 1 8 -2 9 [356] 036-072 CRRFCURB002A00 2 8 -0 9 [610] NOTES: 1. Roof curb accessory is shipped unassembled. 2. Insulated panels. 3. Dimensions in [ ] are in millimeters. 4. Roof curb: galvanized steel. 5. Attach ductwork to curb (flange ...

  • Bryant 580D - page 22

    ACCESSOR Y DIMENSIONS (cont) Roof Curb — 580D090-150 ROOF CURB ACCESSOR Y ‘‘ A’’ UNIT SIZE 580D CRRFCURB003A00 1 8 -2 9 [356] 090- 150 CRRFCURB004A00 2 8 -0 9 [610] UNIT SIZE 580D ‘ ‘B’ ’ ‘ ‘C’ ’ ‘ ‘D’ ’ AL T DRAIN HOLE ‘ ‘E’ ’ GAS POWER CONTROL CONNECTOR P ACKAGE ACCESSOR Y 090- 150 2 8 -8 7 ⁄ 16 9 [827] ...

  • Bryant 580D - page 23

    ACCESSOR Y DIMENSIONS (cont) Horizontal and V ertical Roof Curbs and Horizontal Adapter 579F180-300 NOTE: T o prevent the hazard of stagnant water build-up in the drain pan of the indoor section, unit can only be pitched as shown. LEGEND COMPR SECT . — Compressor Section NOTES: 1. Roof curb accessory is shipped unassembled. 2. Insulated panels, 1 ...

  • Bryant 580D - page 24

    ACCESSOR Y DIMENSIONS (cont) Horizontal Supply/Return Adapter Installation 579F180-300 NOTE: 389210-201 is a fully factory preassembled horizontal adapter and includes an insulated high static regain transition duct which substantially improves fan static performance. The Barometric Relief Damper and Power Exhaust accesso- ries are not available wi ...

  • Bryant 580D - page 25

    SELECTION PROCEDURE (with 579F180 example) I DETERMINE COOLING AND HEA TING REQUIRE- MENTS A T DESIGN CONDITIONS. Given: Required Cooling Capacity ............ 170,000 Btuh Sensible Heat Capacity ............... 1 14,000 Btuh Required Heating Capacity ............ 200,000 Btuh Condenser Entering Air T emp ......... 9 5 F (Summer) Evaporator Enterin ...

  • Bryant 580D - page 26

    PERFORMANCE DA T A COOLING CAP ACITIES 580D036 (3 TONS) T emp (F) Air Entering Condenser (Edb) Air Entering Evaporator — Cfm/BF 900/0.1 1 1200/0.14 1500/0.17 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 75 TC 42.8 38.9 35.0 44.8 40.8 37.0 45.8 41.9 38.2 SHC 20.0 24.5 28.7 21.8 27.5 32.8 23.0 30.0 36.0 kW 2.91 2.81 2.70 2.99 2.88 ...

  • Bryant 580D - page 27

    PERFORMANCE DA T A (cont) COOLING CAP ACITIES (cont) 580D090 (7 1 ⁄ 2 TONS) T emp (F) Air Entering Condenser (Edb) Air Entering Evaporator — Cfm/BF 2250/0.07 2800/0.09 3000/0.10 3750/0.12 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62 75 TC 102.8 94.8 86.2 105.8 98.2 90.0 106.4 99.0 90.8 109.2 101.6 93.6 SHC 49.4 61.8 7 ...

  • Bryant 580D - page 28

    PERFORMANCE DA T A (cont) COOLING CAP ACITIES (cont) 580D120 (10 TONS) T emp (F) Air Entering Condenser (Edb) Air Entering Evaporator — Cfm/BF 3000/0.095 4000/0.125 5000/0.15 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 75 TC 135.8 124.8 1 12.0 142.4 130.6 1 19.8 146.5 134.2 123.7 SHC 66.8 82.6 97.4 73.2 93.4 1 12.7 79.7 104.4 1 ...

  • Bryant 580D - page 29

    PERFORMANCE DA T A (cont) COOLING CAP ACITIES (cont) 579F180 (15 TONS) T emp (F) Air Entering Condenser (Edb) Air Entering Evaporator — Cfm/BF 4500/0.08 5250/0.10 6000/0.11 6750/0.12 7500/0.14 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 75 TC 212.0 195.0 179.0 216.0 200.0 183.0 219.0 204.0 187.0 223.0 205.0 18 ...

  • Bryant 580D - page 30

    PERFORMANCE DA T A (cont) COOLING CAP ACITIES (cont) 579F240 (20 TONS) T emp (F) Air Entering Condenser (Edb) Air Entering Evaporator — Cfm/BF 6000/0.06 7000/0.07 8000/0.08 9000/0.09 10,000/0.10 Air Entering Evaporator — Ewb (F) 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 75 TC 274.0 250.0 226.0 280.0 256.0 232.0 284.0 260.0 236.0 288.0 264.0 ...

  • Bryant 580D - page 31

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS 580D036 (3 TONS) — ST ANDARD MOTOR (DIRECT DRIVE) Airflow (Cfm) Low Speed High Speed 208 V 230, 460, 575 V 208 V 230, 460, 575 V Esp Bhp Watts Esp Bhp W atts Esp Bhp W atts Esp Bhp Watts 900 0.49 0.21 253 0.50 0.23 277 0.51 0.26 307 0.55 0.31 363 1000 0.42 0.23 2 ...

  • Bryant 580D - page 32

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont) 580D048 (4 TONS) — ST ANDARD MOTOR (DIRECT DRIVE) Airflow (Cfm) Low Speed High Speed 208 V 230, 460, 575 V 208 V 230, 460, 575 V Esp Bhp Watts Esp Bhp W atts Esp Bhp W atts Esp Bhp Watts 1200 0.68 0.41 458 0.74 0.45 506 0.74 0.51 572 0.85 0.56 632 1300 0.6 ...

  • Bryant 580D - page 33

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont) 580D060 (5 TONS) — ST ANDARD MOTOR (DIRECT DRIVE) Airflow (Cfm) Low Speed Medium Speed High Speed 208 V 230, 460, 575 V 208 V 230, 460, 575 V 208 V 230, 460, 575 V Esp Bhp Watts Esp Bhp Watts Esp Bhp Watts Esp Bhp Watts Esp Bhp Watts Esp Bhp W atts 1500 0. ...

  • Bryant 580D - page 34

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont) 580D072 (6 TONS)* Airflow (Cfm) External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 1800 942 0.70 646 978 0.66 700 1063 0.82 771 1 147 0.97 891 1248 1.20 1081 1322 ...

  • Bryant 580D - page 35

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont) 580D090 (7 1 ⁄ 2 TONS)* Airflow (Cfm) External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 2250 514 0.55 562 593 0.76 723 662 0.99 907 724 1.22 1097 781 1.78 1318 2300 521 0.57 577 ...

  • Bryant 580D - page 36

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont) 580D102 (8 1 ⁄ 2 TONS)* Airflow (Cfm) External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 2550 559 0.72 692 634 0.97 891 700 1.21 1089 759 1.48 1318 814 1.74 1543 2600 567 0.75 71 ...

  • Bryant 580D - page 37

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont) 580D120 (10 TONS)* Airflow (Cfm) External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp Watts 3000 592 0.76 723 661 0.93 859 722 1.09 989 779 1.26 1 131 829 1.42 1267 880 1. ...

  • Bryant 580D - page 38

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 VERTICAL DISCHARGE UNITS (cont) 580D150 (12 1 ⁄ 2 TONS)* Airflow (Cfm) External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 3750 737 1.41 1300 798 1.64 1486 854 1.84 1658 909 2.12 1893 961 2.35 ...

  • Bryant 580D - page 39

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 HORIZONT AL DISCHARGE UNITS 580D036 (3 TONS) — ST ANDARD MOTOR (DIRECT DRIVE) Airflow (Cfm) Low Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v Esp Bhp Watts Esp Bhp W atts Esp Bhp W atts Esp Bhp Watts 900 0.54 0.21 253 0.57 0.23 277 0.55 0.26 307 0.60 0.31 363 1000 0.49 0.2 ...

  • Bryant 580D - page 40

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 HORIZONT AL DISCHARGE UNITS (cont) 580D048 (4 TONS) — ST ANDARD MOTOR (DIRECT DRIVE) Airflow (Cfm) Low Speed High Speed 208 v 230, 460, 575 v 208 v 230, 460, 575 v Esp Bhp Watts Esp Bhp W atts Esp Bhp W atts Esp Bhp Watts 1200 0.75 0.41 458 0.81 0.45 506 0.87 0.51 572 0.92 0.56 632 1300 ...

  • Bryant 580D - page 41

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 HORIZONT AL DISCHARGE UNITS (cont) 580D060 (5 TONS) — ST ANDARD MOTOR (DIRECT DRIVE) Airflow (Cfm) Low Speed Medium Speed High Speed 208 V 230, 460, 575 V 208 V 230,460, 575 V 208 V 230, 460, 575 V Esp Bhp Watts Esp Bhp Watts Esp Bhp Watts Esp Bhp Watts Esp Bhp Watts Esp Bhp W atts 1500 ...

  • Bryant 580D - page 42

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 HORIZONT AL DISCHARGE UNITS (cont) 580D072 (6 TONS)* Airflow (Cfm) External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 1800 885 0.63 623 942 0.73 700 1047 0.90 835 1 139 1.05 956 1 193 1.14 1031 ...

  • Bryant 580D - page 43

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 HORIZONT AL DISCHARGE UNITS (cont) 580D090 (7 1 ⁄ 2 TONS)* Airflow (Cfm) External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 0.9 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts 2250 507 0.53 547 586 0.73 700 658 0.97 891 722 1.22 1097 752 1.34 1 ...

  • Bryant 580D - page 44

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 HORIZONT AL DISCHARGE UNITS (cont) 580D102 (8 1 ⁄ 2 TONS)* Airflow (Cfm) External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 0.9 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts 2550 550 0.69 669 627 0.94 867 692 1.17 1056 754 1.45 1292 783 1.60 ...

  • Bryant 580D - page 45

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 HORIZONT AL DISCHARGE UNITS (cont) 580D120 (10 TONS)* Airflow (Cfm) External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts 3000 552 0.68 661 632 0.87 810 701 1.05 956 761 1.22 1097 816 1.36 1216 871 ...

  • Bryant 580D - page 46

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 580D036-150 HORIZONT AL DISCHARGE UNITS (cont) 580D150 (12 1 ⁄ 2 TONS)* Airflow (Cfm) External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 3750 684 1.24 1 162 755 1.48 1353 816 1.70 1540 875 1.94 1738 933 2 ...

  • Bryant 580D - page 47

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 579F180-300 UNITS 579F180 (15 TONS) Airflow (Cfm) External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 4500 801 1.05 933 890 1.26 1 1 19 971 1.46 1297 1050 1.67 1483 1 125 1.88 1670 1200 2.12 1883 4800 843 1. ...

  • Bryant 580D - page 48

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 579F180-300 UNITS (cont) 579F216 (18 TONS)* Airflow (Cfm) External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 5000 669 1.10 1019 772 1.40 1291 870 1.80 1582 963 2.10 1903 1052 2.50 2251 1 137 2.90 2623 5500 ...

  • Bryant 580D - page 49

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 579F180-300 UNITS (cont) 579F240 (20 TONS)* Airflow (Cfm) External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 1.0 1.2 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts 6000 767 1.80 1617 858 2.20 1932 944 2.50 2256 1026 2.90 2600 1 104 3.30 2967 1 181 3.80 3358 650 ...

  • Bryant 580D - page 50

    PERFORMANCE DA T A (cont) F AN PERFORMANCE — 579F180-300 UNITS (cont) 579F300 (25 TONS)* Airflow (Cfm) External Static Pressure (in. wg) 0.2 0.4 0.6 0.8 0.9 1.0 Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp W atts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp W atts 7,500 962 3.39 3123 1039 3.81 3507 1111 4.23 3895 1 179 4.66 4295 1212 4.89 4503 1245 5.1 1 4710 8 ...

  • Bryant 580D - page 51

    PERFORMANCE DA T A (cont) AIR QUANTITY LIMITS UNIT MINIMUM CFM MAXIMUM CFM 580D036 900 1500 580D048 1200 2000 580D060 1500 2500 580D072 1800 3000 580D090 2250 3750 580D102 2550 4250 UNIT MINIMUM CFM MAXIMUM CFM 580D120 3000 5,000 580D150 3750 6,250 579F180 4500 7,500 579F216 5400 9,000 579F240 6000 10,000 579F300 7000 1 1,250 SOUND POWER (T otal Un ...

  • Bryant 580D - page 52

    PERFORMANCE DA T A (cont) ACCESSOR Y/FIOP ST A TIC PRESSURE* (in. wg) − 580D036-072 COMPONENT CFM 900 1200 1400 1600 1800 2000 2200 2400 2600 3000 Durablade Economizer 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 Parablade Economizer 0.08 0.10 0.17 0.26 0.33 0.34 0.36 0.40 0.44 — LEGEND FIOP − Factory-Installed Option *The static pressur ...

  • Bryant 580D - page 53

    PERFORMANCE DA T A (cont) Durablade Economizer Barometric Relief Damper Characteristics — 580D036-150 Parablade Economizer Barometric Relief Damper Characteristics — 580D036-072 Parablade Economizer Barometric Relief Damper Characteristics — 580D090-150 AL TITUDE COMPENSA TION* — 580D036-072 ELEV A TION (ft) 72,000 AND 1 15,000 BTUH NOMINAL ...

  • Bryant 580D - page 54

    PERFORMANCE DA T A (cont) AL TITUDE COMPENSA TION* — 580D090-150 ELEV A TION (ft) 125,000, 180,000, AND 224,000 BTUH NOMINAL INPUT 250,000 BTUH NOMINAL INPUT Natural Gas Orifice Size† Liquid Propane Orifice Size† Natural Gas Orifice Size† Liquid Propane Orifice Size† 0-2,000 31 41 30 38 2,000 32 42 30 39 3,000 32 42 31 40 4,000 32 42 ...

  • Bryant 580D - page 55

    PERFORMANCE DA T A (cont) EV APORA TOR-F AN MOTOR PERFORMANCE UNIT EV APORA T OR-F AN MOTOR UNIT VOL T AGE MAXIMUM ACCEPT ABLE CONTINUOUS BHP* MAXIMUM ACCEPT ABLE OPERA TING W A TTS MAXIMUM AMP DRA W 580D036 Standard 208/230 0.34 440 2.9 460 1.4 575 1.4 Alternate 208/230 1.00 1000 5.4 460 2.3 575 2.3 580D048 Standard 208/230 0.75 850 3.5 460 1.8 57 ...

  • Bryant 580D - page 56

    ELECTRICAL DA T A — 580D036-150 UNIT 580D NOMINAL VOL T AGE (60 Hz) IFM TYPE VOL T AGE RANGE COMPR (ea) OFM (ea) IFM COMBUSTION F AN MOTOR POWER SUPPL Y DISCONNECT SIZE* Min Max RLA LRA Hp FLA FLA FLA MCA MOCP† FLA LRA 036 (3 T ons) 208/230 (single phase) Std 187 254 18.0 96.0 1 ⁄ 4 1.4 2.8 .57 26.7/26.7 35/35 26/26 106/106 Alt 4.9 28.8/28.8 ...

  • Bryant 580D - page 57

    ELECTRICAL DA T A — 579F180-300 UNIT NOMINAL VOL T AGE (60 Hz) VOL T AGE RANGE COMPRESSOR OFM IFM POWER EXHAUST COMBUSTION F AN MOT OR POWER SUPPL Y NO. 1 NO. 2 Min Max RLA LRA RLA LRA Qty Hp FLA (ea) FLA FLA LRA FLA MCA MOCP† 180 (15 T ons) 208/230 (3 phase) 187 254 61.0 266 — — 3 1 ⁄ 2 1.70 10.5/10.5 — — 0.57 92/92 150/150 4.6 18.8 ...

  • Bryant 580D - page 58

    TYPICAL PIPING AND WIRING — 580D036-150 V ertical Discharge Ducting Horizontal Discharge Ducting NEC — National Electrical Code 58 ...

  • Bryant 580D - page 59

    TYPICAL PIPING AND WIRING — 579F180-300 (579F180 shown) NEC — National Electrical Code 59 ...

  • Bryant 580D - page 60

    TYPICAL WIRING SCHEMA TIC — 580D036-150 NOTES FOR 580D036-150 UNITS: 1. If any of the original wire furnished must be re- placed, it must be replaced with T ype 90 C wire or its equivalent. 2. Three-phase motors are protected under pri- mary single phasing conditions. 3. Thermostat: HH07A T170, 172, 174 and P272-2783 Subbase: HH93AZ176, 178 and P ...

  • Bryant 580D - page 61

    TYPICAL WIRING SCHEMA TIC (579F240-300, 460-v shown) 61 ...

  • Bryant 580D - page 62

    TYPICAL WIRING SCHEMA TIC (579F240-300, 460-v shown) (cont) LEGEND FOR TYPICAL WIRING SCHEMA TICS AHA — Adjustable Heat Anticipator BKR W/A T — Breaks with Amp Turns BR — Burner Relay C— Contactor , Compressor CAP — Capacitor CB — Circuit Breaker CC — Cooling Compensator CH — Crankcase Heater CLO — Compressor Lockout COMP — Comp ...

  • Bryant 580D - page 63

    CONTROLS OPERA TING SEQUENCE Cooling, Units Without Economizer — When thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC) and compressor contactor no. 1 (C1) are energized, and evaporator-fan motor (IFM), com- pressor no. 1 (580D036-150 and 579F216-300) or unloaded compressor (579F180), and ...

  • Bryant 580D - page 64

    CONTROLS (cont) Cooling, Units With Parablade Economizer (580D036-072) — When the outdoor air is above the enthalpy control (EC) set- ting, and the room thermostat calls for cooling, and the com- pressor contactor is energized to start the compressor and the condenser-fan motor . The evaporator-fan motor is energized and the economizer damper mov ...

  • Bryant 580D - page 65

    APPLICA TION DA T A 1. DUCTWORK (580D036-150) — Secure vertical discharge ductwork to roof curb. For horizontal discharge applica- tions, attach ductwork to unit, or field-supplied flanges can be attached to horizontal discharge openings and all duct- work attached to flanges. 2. DUCTWORK (579F180-300) — Ductwork should be at- tached to the ...

  • Bryant 580D - page 66

    APPLICA TION DA T A (cont) Concentric Duct Air Distribution 579F180-300 Only NOTE: Do not drill in this area, damage to basepan may result in water leak. Concentric Duct Details 579F180-300 Only NOTE: Dimensions A, A 8 and B, B 8 are obtained from field-supplied ceiling diffuser . indicates block-off panels. 66 ...

  • Bryant 580D - page 67

    GUIDE SPECIFICA TIONS — 580D036-150 P ACKAGED ROOFTOP ELECTRIC COOLING UNIT WITH GAS HEA T — CONST ANT VOLUME APPLICA TION HV AC GUIDE SPECIFICA TIONS SIZE RANGE: 3t o1 2 1 ⁄ 2 TONS, NOMINAL (COOLING) 72,000 TO 250,000 BTUH, NOMINAL (INPUT HEA TING) MODEL NUMBER: 580D Part 1 — General 1.01 SYSTEM DESCRIPTION Outdoor rooftop mounted, electri ...

  • Bryant 580D - page 68

    GUIDE SPECIFICA TIONS — 580D036-150 (cont) 5. The integrated gas controller (IGC) board shall include gas heat operation fault notification using an LED (light-emitting diode). 6. Unit shall be equipped with anti-cycle protection with one short cycle on unit flame rollout switch or 4 con- tinuous short cycles on the high-temperature limit switc ...

  • Bryant 580D - page 69

    GUIDE SPECIFICA TIONS — 580D036-150 (cont) b. Damper shall close upon indoor (evaporator) fan shutoff. c. Designed to close damper during loss of power situations. d. Equipped with 15% barometric relief damper . * 5. 25% T wo-Position Damper: a. T wo-position damper package shall include single blade damper and motor . Admits up to 25% out- door ...

  • Bryant 580D - page 70

    GUIDE SPECIFICA TIONS — 579F180-300 P ACKAGED ROOFTOP ELECTRIC COOLING UNIT WITH GAS HEA T — CONST ANT VOLUME APPLICA TION HV AC GUIDE SPECIFICA TIONS SIZE RANGE: 15 TO 25 T ONS, NOMINAL (COOLING) 172,000 to 360,000 BTUH, NOMINAL (INPUT HEA TING) MODEL NUMBER: 579F Part 1 — General 1.01 SYSTEM DESCRIPTION Unit is an outdoor rooftop mounted, e ...

  • Bryant 580D - page 71

    GUIDE SPECIFICA TIONS — 579F180-300 H. Filter Section: Standard filter section shall consist of 2 sizes of factory- installed 2-in. thick throwaway fiberglass filters of commercially available sizes. I. Controls and Safeties: 1. Unit Controls: a. Economizer control (optional) b. Capacity control (2-step) c. Unit shall be complete with self-con ...

  • Bryant 580D - page 72

    GUIDE SPECIFICA TIONS — 579F180-300 * 1 1. Enthalpy Sensor: a. For use with economizer only . b. Capable of comparing heat content (temperature and humidity) of outdoor air and indoor air and controlling economizer cut-in point at the most economical level. NOTE: T wo accessory enthalpy sensors are re- quired for differential enthalpy control. * ...

Fabbricante Bryant Categoria Heating System

I documenti che otteniamo dal fabbricante del dispositivoBryant 580D possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Bryant
- manuali per l’uso 580D
- schede prodotto Bryant
- opuscoli
- o etichette energetiche Bryant 580D
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Bryant 580D.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Bryant 580D, manuali di manutenzione, brevi manuali o manuali utente Bryant 580D. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Bryant 580D.

Manuali per l’uso simili

Manuale completo del dispositivo Bryant 580D, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Bryant 580D dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Bryant 580D.

Il manuale per l’uso completo Bryant, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Bryant 580D - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Bryant 580D, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Bryant 580D che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Bryant 580D - che ci dovrebbe aiutare nei primi passi durante l'uso Bryant 580D
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Bryant 580D