    FieldPoint ™ Operating Instructions FP-AI-112 and cFP-AI-112 16-Channel, 16-Bit Anal og Input Modu les These operating instructions descri be ho w to install and use the FP-AI-112 and cFP-AI-112 analog input modules (referred to inclusiv ely as the [c]FP-A I-112). Fo r information about configuring and accessing the [c]F P- AI-112 ov er a network ...

  • National Instruments FP-AI-112 - page 2

    FP-AI-112 and cFP-AI-112 2 ni.com T o install the FP- AI-112, refer to Figure 1 and complete the follow ing steps: 1. Slide the terminal base key to either position X (used for an y module) or position 1 (used for the FP- AI-112). 2. Align the FP- AI-112 alignmen t sl ots with the guide rails on the terminal base. 3. Press firmly to seat the FP- AI ...

  • National Instruments FP-AI-112 - page 3

    © National Instruments Corp. 3 FP-AI-112 and cFP-AI-112 3. Using a number 2 Phillips scre wdriv er with a shank of at least 64 mm (2.5 in.) length, tighten the captiv e screws to 1. 1 N ⋅ m (10 lb ⋅ in.) of torque. The n ylon coating on the screws pre vents them from loosening. Figure 2. Installing the cFP-AI-112 Wiring the [c]FP-AI-112 The FP ...

  • National Instruments FP-AI-112 - page 4

    FP-AI-112 and cFP-AI-112 4 ni.com Y ou can use an external power supply to po wer field de vices. Connect the positi ve lead of the e xternal power supply to both V terminals and the negat ive lead to both C termina ls. Ensure that the current through both V terminals can nev er exceed 2 A. Install 2 A maximum, fast-acting fuses between the e xtern ...

  • National Instruments FP-AI-112 - page 5

    © National Instruments Corp. 5 FP-AI-112 and cFP-AI-112 Caution Cascading power between two modules defeats isolation between those modules. Cascading power from the network module defeats all isolation between modules in the FieldPoint bank. Measuring V oltage with the [c]FP-AI-112 Figure 3 sho ws how to connect a v oltage source without an exter ...

  • National Instruments FP-AI-112 - page 6

    FP-AI-112 and cFP-AI-112 6 ni.com Input Ranges The input ranges for voltage signals are 0 –1 V , 0 –5 V , 0 –10 V , ± 60 mV , ± 300 mV , ± 1V , ± 5 V , and ± 10 V . T o prevent inaccurate readings, choose an input range such that the signal you are measuring does not exceed either end of the rang e. Signals that greatly ex ceed the confi ...

  • National Instruments FP-AI-112 - page 7

    © National Instruments Corp. 7 FP-AI-112 and cFP-AI-112 ( number of input range s with 60 Hz filter ) × 0.10 s + ( number of channels with 500 Hz filter ) × 0.007 s + ( number of input ranges with 500 Hz filter ) × 0.012 s + 0.16 s = Update Period For the f astest performance, conf igure all unused channels for the 500 Hz f ilter setting and fo ...

  • National Instruments FP-AI-112 - page 8

    FP-AI-112 and cFP-AI-112 8 ni.com Isolation and Sa fety Guidelines Caution Read the following in formation before attempting to connect the [c]F P-AI-112 to an y circuits that may contain hazardous voltages. This section describes the isolat ion of the [c]FP-AI-112 and its compliance wit h international sa fety standards. The field wiring connectio ...

  • National Instruments FP-AI-112 - page 9

    © National Instruments Corp. 9 FP-AI-112 and cFP-AI-112 using 14 A WG (1.6 mm) wire with a ring lug. Use the 5/16 in. panhead screw shipped with the backplane to secure the ring lug to the backplane PE ground terminal. • As with any hazardous v oltage wiring, make sure that all wiring and connections meet appl icable electrical codes and commons ...

  • National Instruments FP-AI-112 - page 10

    FP-AI-112 and cFP-AI-112 10 ni.com Effecti ve resolution by inpu t range and filter setting Update period and input band width by filter setting Normal-mode rejection ............. ........ 95 dB Nonlinearity .......... ........... ......... ........ 0.0015% (monotonicity 1 warranted ov er the operating temperature range) Input impedance (with powe ...

  • National Instruments FP-AI-112 - page 11

    © National Instruments Corp. 11 FP-AI-112 and cFP-AI-112 T ypical and warranted accuracy b y input range and temperature range Note Full scale is the maximum value of the nominal input range. F or example, for the ± 10 V input range, full scale is 10 V and ± 0.01% of full scale is 1 mV . Gain error drift ...... ......... ........... ........ ± ...

  • National Instruments FP-AI-112 - page 12

    FP-AI-112 and cFP-AI-112 12 ni.com Physical Char acteristics Indicators ................... ......... ........... ... Green POWER and READY indicators W eight FP-AI-112..... ............. ............ ..... 142 g (5.0 oz) cFP-AI-112 ....... ............ .............. 113 g (4.0 oz) Power Requirements Power from network module ............ 350 mW I ...

  • National Instruments FP-AI-112 - page 13

    © National Instruments Corp. 13 FP-AI-112 and cFP-AI-112 Shock and Vibration These specifications apply only to the cFP-AI-112. NI recommends Compact FieldP oint if your application is subject to shock and vibration. Operating vibration, random (IEC 60068-2-64)....... ........... ............ 1 0 –500 Hz, 5 g rms Operating vibration, sinusoidal ...

  • National Instruments FP-AI-112 - page 14

    FP-AI-112 and cFP-AI-112 14 ni.com CE Compliance This product meets the essentia l requirements of applicable European Directi ves, as amended for CE ma rking, as follows: Lo w-V oltage Directi ve (s afety)...... ... 73/23/EEC Electromagnet ic Compatibility Directiv e (EMC) ... ........... ......... ........ 89/336/EEC Note Refer to the Declaration ...

  • National Instruments FP-AI-112 - page 15

    © National Instruments Corp. 15 FP-AI-112 and cFP-AI-112 Where to Go for Support For more information about settin g up the FieldPoint system, refer to these National Instruments documents: • FieldPoint network module user manual • Other FieldPo int I/O m odule operating instructions • FieldPoint terminal base and connector block operating i ...

  • National Instruments FP-AI-112 - page 16

    © 2004 National I nstruments Corp. All rights reser ved. 371330A-01 Jul04 *371330A-01* FieldPoint™, Nati onal Instruments™, NI™, and ni.com™ are trademarks of National Instruments Corporati on. Product and company names ment ioned herein are trademarks or trade names of thei r respective companies. For patents covering National Instruments ...

Fabbricante National Instruments Categoria Welding System

I documenti che otteniamo dal fabbricante del dispositivoNational Instruments FP-AI-112 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici National Instruments
- manuali per l’uso FP-AI-112
- schede prodotto National Instruments
- opuscoli
- o etichette energetiche National Instruments FP-AI-112
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso National Instruments FP-AI-112.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione National Instruments FP-AI-112, manuali di manutenzione, brevi manuali o manuali utente National Instruments FP-AI-112. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto National Instruments FP-AI-112.

Manuale completo del dispositivo National Instruments FP-AI-112, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare National Instruments FP-AI-112 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti National Instruments FP-AI-112.

Il manuale per l’uso completo National Instruments, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale National Instruments FP-AI-112 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice National Instruments FP-AI-112, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per National Instruments FP-AI-112 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo National Instruments FP-AI-112 - che ci dovrebbe aiutare nei primi passi durante l'uso National Instruments FP-AI-112
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del National Instruments FP-AI-112
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio National Instruments FP-AI-112 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su National Instruments FP-AI-112?

Utilizza il modulo sottostante

Se non hai risolto il problema con National Instruments FP-AI-112 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con National Instruments FP-AI-112 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)