    FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4 918-063a MODELS: P33R-NG2 Natural Gas P33R-LP2 Propane P33R Zero Clearance Rear Direct V ent Gas Fireplace 04/26/04 Owners & Inst allation Manual WARNING: If the information in these instructions are not followed exactly , a fire or explosion may result causin ...

  • Regency P33R-LP2 - page 2

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 2 To the New Owner: Congratulations! You are the owner of a state-of-the-art Gas Stove by FIREPLACE PRODUCTS INTERNATIONAL. The P33R-2 is a hand crafted appliance and has been designed to provide you with all the warmth and charm of a wood fireplace at the flick of a switch. The mode ...

  • Regency P33R-LP2 - page 3

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 3 T ABLE OF CONTENTS Operating Instructions Lighting Plate Instructions ......................................... 2 8 Operating Instructions ............................................... 2 9 Lighting Procedure .................................................... 2 9 Shutdown Proced ...

  • Regency P33R-LP2 - page 4

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 4 This is a copy of the label that accompanies each P33R-2 Zero Clearance Direct Vent Gas Fireplace. We have printed a copy of the con- tents here for your review. The safety label is located on the front inside base of the unit, visible when the bottom louver is open. NOTE: Regency ...

  • Regency P33R-LP2 - page 5

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 5 INST ALLA TION IMPORT ANT : SA VE THESE INSTRUCTIONS The P33R-NG2 or P33R-LP2 Direct Vent Fire- place must be installed in accordance with these instructions. Carefully read all the instructions in this manual first. Consult the "authority having jurisdiction" to determin ...

  • Regency P33R-LP2 - page 6

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 6 INST ALLA TION CHECKLIST 1) Locate appliance a ) Room location, page 6 b ) Clearances to Combustibles, page 6 c ) Mantle Clearances, page 7 d ) Framing & Finishing Requirements, page 8 e ) Venting Requirements, pages 10 to 15. 2) Assemble Top Facing Support and Side Nailing Str ...

  • Regency P33R-LP2 - page 7

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 7 COMBUSTIBLE MANTELS INST ALLA TION Clearances for Bay or Flush Front WARNING Fire hazard is an extreme risk if these clearances are not ad- hered to. Because of the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of unit ...

  • Regency P33R-LP2 - page 8

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 8 INST ALLA TION Install Side Nailing Strips, and Top Facing Support before unit is slipped into position. See page 9 for assembly details. 3) For exterior walls, insulate the enclosure to the same degree as the rest of the house, apply vapour barrier and drywall, as per local instal ...

  • Regency P33R-LP2 - page 9

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 9 "C" Screw Position: For a facing material depth of 1-1/4"(32mm), the top facing support must be reversed. The Top Facing Support, the Side Nailing Strips and the 2 Top Standoffs must be correctly positioned and attached to the top before unit is slipped into position ...

  • Regency P33R-LP2 - page 10

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 10 EXTERIOR VENT TERMINA TION LOCA TIONS INST ALLA TION . B B B B A C V V V V V V V A A V Fixed Fixed Openable Closed Closed Openable N L B E B M D F K H j V ertical T ermination V V ent terminal Area where terminal is not permited A Air supply outlet 24" V A G Inside corner det ...

  • Regency P33R-LP2 - page 11

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 11 INST ALLA TION VENTING INTRODUCTION The P33R-2 uses the "balanced flue" technology Co Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to ...

  • Regency P33R-LP2 - page 12

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 12 INST ALLA TION PROCEDURES for Regency Direct Vent System (Flex) Minimum and Maximum Vent Clearances INST ALLA TION 1) Locate the unit in the framing, rough in the gas (preferably on the right side of the unit) and the electrical (Junction block is on the left side) on the left. Lo ...

  • Regency P33R-LP2 - page 13

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 13 SIMPSON DURA-VENT VENTING COMPONENTS LIST All Simpson Dura-Vent components are available directly from Regency. All components available directly from Regency. Part # Description Part # Description P a r t # Description INST ALLA TION Simpson Dura-Vent Direct Vent GS SIMPSON DURA- ...

  • Regency P33R-LP2 - page 14

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 14 VENTING ARRANGEMENTS - HORIZONT AL TERMINA TIONS SIMPSON DURA-VENT DIRECT VENT GS SYSTEM or Regency Direct Vent (Flex) for Horizontal Terminations (Propane & Natural Gas) INST ALLA TION (Dura-Vent System or Regency DV Flex) The diagram shows all allowable combinations of verti ...

  • Regency P33R-LP2 - page 15

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 15 INST ALLA TION • Vent must be supported at offsets • Firestops are required at each floor level and whenever passing through a wall. • Maintain a 1-1/4" clearance to combustibles Note: Must use optional flue adapter when using Simpson Dura-Vent pipe (Part # 510-994). VE ...

  • Regency P33R-LP2 - page 16

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 16 VERTICAL TERMINA TION WITH CO-LINEAR FLEX SYSTEM THE APPLIANCE MUST NOT BE CONNECTED TO A CHIMNEY FLUE SERVING A SEPARATE SOLID FUEL BURNING APPLIANCE. This appliance is designed to be attached to two 3" (76mm) co-linear aluminium flex running the full length of the chimney. ...

  • Regency P33R-LP2 - page 17

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 17 Venting Arrangements - Vertical Terminations with Co-linear Flex System for both Residential & Manufactured Homes into Masonry Fireplaces The shaded area in the diagrams show the allowable vertical terminations. INST ALLA TION ...

  • Regency P33R-LP2 - page 18

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 18 INST ALLA TION Diagram 3 HORIZONT AL INST ALLA TIONS Diagram 1 b) Horizontal runs of vent must be sup- ported every three feet. Wall straps are available for this purpose. 5) Mark the wall for a 10" x 10" square hole. The center of the square hole should line up with the ...

  • Regency P33R-LP2 - page 19

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 19 INST ALLA TION GAS LINE INST ALLA TION The gas line can be brought through either the right or the left side of the appliance. The gas valve is situated on the right hand side of the unit and the gas inlet is on the right hand side of the valve. Note: If the gas line is being inst ...

  • Regency P33R-LP2 - page 20

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 20 P33R-2 System Data For 0 to 4500 feet altitude Burner Inlet Orifice Sizes: Natural Gas Propane Burner #45 #54 Max. Input Rating - Natural Gas 21,000 Btu/h - Propane 21,000 Btu/h Min. Input Rating -Natural Gas 10,500 Btu/h -Propane 10,500 Btu/h Output Capacity with blower Off Natur ...

  • Regency P33R-LP2 - page 21

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 21 INST ALLA TION Conversion Kit from Natural Gas to Propane Model #431-969 for P33R-2 using SIT 820 NOV A Gas V alve THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !! Remove the 2 screws, push Burner Assem- bly to the left and lift out. ...

  • Regency P33R-LP2 - page 22

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 22 INST ALLA TION Note: The logs must not be in the unit. 3) Insert the back brick panel by carefully slipping it between the back wall of the firebox and the rear log bracket. OPTIONAL BRICK P ANELS 1) Undo the bottom 2 door latches and open and remove glass door. Remove logs. 2) At ...

  • Regency P33R-LP2 - page 23

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 23 Diagram 1 Diagram 3 ST ANDARD FLUSH DOOR The standard flush door comes with a black frame. To install the frame, simply hook the top door flange onto the top of the unit and swing the door towards the unit, diagram 1. Be careful that the glass gasket does not roll up; there must b ...

  • Regency P33R-LP2 - page 24

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 24 OPTIONAL BA Y DOOR The Bay louvers MUST be used with the Bay glass option. The optional Bay door is an overlay on the flush front. The standard flush door and glass must remain on the unit. 1 ) Hook the top of the bay door over the flush door flange and swing the bottom against th ...

  • Regency P33R-LP2 - page 25

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 25 INST ALLA TION OPTIONAL W ALL THERMOST A T A wall thermostat may be installed if desired, connect the wires as per the wiring diagram. Use table below to determine the maximum wire length. Note: Preferable if the thermostat is in- stalled on an interior wall. Regency offers an opt ...

  • Regency P33R-LP2 - page 26

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 26 INST ALLA TION CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Caution: Ensure that the wires do not touch any hot surfaces and are away from sharp edges. WIRING DIAGRAM This heater does not require ...

  • Regency P33R-LP2 - page 27

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 27 INST ALLA TION INST ALLING THE OPTIONAL F AN 120 Volt AC power is needed for the fan switch and blower. The fan can be hard wired if desired. The receptacle box should be installed on the left hand side of the unit by a qualified electrician. The neutral (wider) slot of the po- la ...

  • Regency P33R-LP2 - page 28

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 28 OPERA TING INSTRUCTIONS COPY OF THE LIGHTING PLA TE INSTRUCTIONS TO TURN OFF GAS APPLIANCE FOR YOUR SAFETY READ BEFORE LIGHTING This appliance must be installed in accordance with local codes, if any; if not, follow the current CAN1-B149/ANSI Z 223.1 (Australia: AG601, New Zealand ...

  • Regency P33R-LP2 - page 29

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 29 AERA TION ADJUSTMENT The air shutter can be adjusted by moving the adjusting wire up or down. The wire is ac- cessed through the bottom louver opening. Open the air shutter for a blue flame or close for a yellower flame. The burner aeration is factory set but may need adjusting du ...

  • Regency P33R-LP2 - page 30

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 30 MAINTENANCE MAINTENANCE INSTRUCTIONS 1) Always turn off the gas valve before clean- ing. For relighting, refer to lighting instruc- tions. Keep the burner and control compart- ment clean by brushing and vacuuming at least once a year. When cleaning the logs, use a soft clean paint ...

  • Regency P33R-LP2 - page 31

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 31 MAINTENANCE THERMOPILE/ THERMOCOUPLE 1) Open the bottom louvers. 2) Loosen the thermocouple or thermopile with a 7/16" wrench. 3) Disconnect thermocouple by loosening nut from the valve with a 9mm wrench. Discon- nect thermopile by loosening 2 screws marked TP on the valve. 4 ...

  • Regency P33R-LP2 - page 32

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 32 gram 2) and then lift the entire assembly out (diagram 3). 10) Undo the pilot tube from the valve with a 7/16" wrench. REMOVING V AL VE 1 ) Shut off the gas supply. 2) Remove the louvers (and bay door if it is on). 3) Open the flush door and remove the door. 4) Remove the log ...

  • Regency P33R-LP2 - page 33

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 33 P ARTS LIST Main Assembly Part # Description Part # Description Part # Description 1 ) 948-247 Door Handle 2 ) * Thermodisc Bracket 7 ) 910-428 Duplex Receptacle 8 ) 910-429 Box - Receptacle 9 ) 910-430 Cover - Receptacle 10) 904-687 Clamp Connector 13) 948-045 #12 Jack Chain 14) ...

  • Regency P33R-LP2 - page 34

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 34 Burner & Log Assembly Part # Description 53) 430-055 Gasket - Valve Access Plate - NG/LP 54) 910-421 Pilot ON/OFF Extension Knob 55) 910-422 Flame HI/LOW Extension Knob 56) 910-190 Piezo Ignitor and Nut 432-574/P Valve Assy - Natural Gas 432-576/P Valve Assy - Propane 57) 910- ...

  • Regency P33R-LP2 - page 35

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 35 P ARTS LIST Flush Front & Louvers Part # Description Part # Description 117) 904-196 Magnet - 1' round 130) 430-924 Flush Glass Trim (set) - Gold (Option) 131) 430-926 Flush Glass Trim (set) - Brass (Option) 430-947 Flush Glass Trim (set) - Brushed Steel (Option) 430-918 ...

  • Regency P33R-LP2 - page 36

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 36 430-930 Bay Front Complete 106) 940-079/P Side Glass 107) 936-243 G lass Gasket 108) 940-078/P Center Glass 110) * Bay Door Frame 111) 902-322 Bay Brick Panel - Standard 432-905 Bay Bri ck P anel - Standard Brown 432-906 Bay Brick Panel - Standard Red 112) * Bay Brick Panel Spacer ...

  • Regency P33R-LP2 - page 37

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 37 _____________________________________________________________________________________ ____________________________________________________________ __________________________________________________________ ____________________________________________________________ ______________ ...

  • Regency P33R-LP2 - page 38

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 38 _____________________________________________________________________________________ ____________________________________________________________ __________________________________________________________ ____________________________________________________________ ______________ ...

  • Regency P33R-LP2 - page 39

    Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace 39 W ARRANTY Regency Fireplace Products, are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly before it leaves our door. Regency Industries Ltd. is pleased to extend this limited lifetime warran ...

  • Regency P33R-LP2 - page 40

    Installer: Please complete the following information Dealer Name & Address: ______________________________________________ __________________________________________________________________ Installer: ___________________________________________________________ Phone #: ___________________________________________________________ Date Installed: ...

Fabbricante Regency Categoria Indoor Fireplace

I documenti che otteniamo dal fabbricante del dispositivoRegency P33R-LP2 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Regency
- manuali per l’uso P33R-LP2
- schede prodotto Regency
- opuscoli
- o etichette energetiche Regency P33R-LP2
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Regency P33R-LP2.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Regency P33R-LP2, manuali di manutenzione, brevi manuali o manuali utente Regency P33R-LP2. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Regency P33R-LP2.

Manuali per l’uso simili

Manuale completo del dispositivo Regency P33R-LP2, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Regency P33R-LP2 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Regency P33R-LP2.

Il manuale per l’uso completo Regency, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Regency P33R-LP2 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Regency P33R-LP2, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Regency P33R-LP2 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Regency P33R-LP2 - che ci dovrebbe aiutare nei primi passi durante l'uso Regency P33R-LP2
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Regency P33R-LP2
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Regency P33R-LP2 in un dato paese, se il problema non può essere risolto da noi stessi.