    Manufacturer reserves the right to disco ntinue, or change at any time, specifications or de signs without notice and without inc urring obligations. Catalog No . 04-53500079-0 1 Printed in U. S.A. F orm 50PT -4SI Pg 1 7-10 Replaces: 50PT -3SI Installation, Star t-Up , and Ser vice Instr uctions CONTENTS Page SAFETY CONSIDERA TIONS . . . . . . . . ...

  • Carrier 50PTH - page 2

    2 components. Only trained a nd qualified service personnel should install, repair, or service air -conditioning equipment. Untrained personnel can perfor m basic maintenance func- tions such as cleaning coils and filters and replacing filters. All other operations should be pe rformed by trained service personnel. When working on ai r-conditioning ...

  • Carrier 50PTH - page 3

    3 8. Provide an unobstructed path to the unit within the closet or mechanical room. Space should be suf ficient to allow removal of unit if necessary . 9. Provide ready access to wa ter valves and fittings, and screwdriver access to unit si de panels, discharge collar , and all electrical connections. 10. Where access to side panels is limited, pre ...

  • Carrier 50PTH - page 4

    4 Y Confi g uration - Left Return/Back Di s char g e W Confi g uration - Left Return/Ri g ht Di s char g e - Air Coil Openin g W Confi g uration - Left Return/Ri g ht Di s char g e - Air Coil Openin g P Confi g uration - Ri g ht Return/Back Di s char g e - Air Coil Openin g N Confi g uration - Ri g ht Return/Left Di s char g e - Air Coil Openin g N ...

  • Carrier 50PTH - page 5

    5 Field-Supplied Electric Heat (if applicable) Filter Access Integral hanger support- pre-attached in factory Field-supplied transition to minimize pressure loss 3/8” threaded rods (by others) Return Air (Ductwork not shown) Thermostat Wiring Power Wiring Balancing V alve (field- installed accessory) Stainless steel braid hose with integral “J? ...

  • Carrier 50PTH - page 6

    6 K - Configuration - Right Return /T op Discharge (T op View) K - Configuration - Right Return - Air Coil Opening (Right Side View) J - Configuration - Left Return - Air Coil Opening (Left Side View) Front View Isometric View J - Configuration - Left Return /T op Discharge (T op View) ASP CSP Front Back Back Front C T U S R Air Coil U R S Air Coil ...

  • Carrier 50PTH - page 7

    7 NOTES: 1. Condensate connection is stainless steel 3 / 4 in. female pipe thread (FPT). 2. Unit shipped w ith top and botto m filter rac k and is not suitable f or duct connection without additional support. 3. Downflo w unit does not ha ve disch arge flange, and is r a ted f or zero clearan ce installation. 4. Shaded areas are re commended servic ...

  • Carrier 50PTH - page 8

    8 Step 3 — Locate Unit — The following guidelines should be considered when choosing a location for a WSHP: • Units are for indoor use only . • Locate in areas where ambient temperatures are between 39 F and 102 F and relative humidity is no greater than 75%. • Provide sufficient space for water , electrical and duct connections. • Loca ...

  • Carrier 50PTH - page 9

    9 5. Check refrigerant tubing for contact with other compo- nents. Adjust if necessary . 6. Reinstall top panel using screws set aside in Step 1. NOTE: Location for some screws at bottom of discharge panel may have to be changed. 7. Manually spin fan wheel to check for obstructions. Adjust for any obstruction found. 8. Replace access pane l. Back t ...

  • Carrier 50PTH - page 10

    10 Each unit must be installed with its own individual vent and means to flush or blow out the condensate drain line. Do not in- stall units with a common trap or vent. VE NT IN G — Install a vent in the condensate line of any application that may allow dirt or air to collect in the line. Con- sider the following: • Always install a vent where ...

  • Carrier 50PTH - page 11

    11 W ater Supply and Quantit y — Check water supply . W ater supply should be plentiful and of good quality . See T able 2 for water quality guidelines. In all applications, the quality of the water circulated through the heat exchanger must fall within the ranges listed in the W ater Quality Guidelines table. Consult a local water treat- ment fi ...

  • Carrier 50PTH - page 12

    12 Table 2 — Water Quality Guideline s LEGEND *Heat e xchanger materials considered are copper , cupronick el, 304 SS (stainless st eel), 316 SS, titanium . †Closed recirculating system is identified by a closed pressurized piping system. **Recirculating open w ells should obs erve the open recirculating design considerations . ††If the con ...

  • Carrier 50PTH - page 13

    13 conform to the Class II temperature limitations described in the NEC. Refer to unit wiring diagrams Fig. 15-24 for a schematic of the field connections, which must be made by the installing (or electrical) contractor . For Deluxe D with WSHP Open controls 3-phase units and Complete C with Open controls single-phase and 3-phase units contact Appl ...

  • Carrier 50PTH - page 14

    14 ECM Y GGGGR W O Y 2 Y 1 G R C Y 2 Y 1 G O W C R D H A L 1 A A A L 1 S W1 S W2 S W3 S W4 S W5 S W6 S W7 S W8 S W9 OF F ON G D E HU M C F M T B 1 J1 S 1 BM ECM ECM INTERFACE BOARD S W 1 S W 2 S W 3 S W 4 S W 5 S W 6 S W 7 S W 8 S W 9 OF F ON S 1 J1 BM ECM AL — Alarm Relay Contacts AST A T — Aquastat BM — Blower Motor BR — Blo wer Relay CB ...

  • Carrier 50PTH - page 15

    15 ECM INTERF ACE BOARD LA YOUT Y GGGGR W O Y2 Y1 G R C Y2 Y1 G O W C R DH AL 1 A A AL 1 SW 1 SW 2 SW 3 SW 4 SW 5 SW 6 SW 7 SW 8 SW 9 OFF ON G DEH UM C FM T B1 J 1 S 1 BM (ECM) ECM INTERFACE BOARD SW1 S W2 S W3 S W4 S W5 S W6 S W7 S W8 S W9 OF F O N BM (ECM) AL — Al arm Relay Cont acts AST A T — Aqu astat BM — Blow er Motor CAP — Capacitor ...

  • Carrier 50PTH - page 16

    16 ECM INTERF ACE BOARD LA YOUT Y GGGGR W O Y 2 Y 1 G R C Y 2 Y 1 G O W C R D H A L 1 A A A L1 S W1 S W2 S W3 S W4 S W5 S W6 S W7 S W8 S W9 OF F ON G D E HU M C F M T B 1 J1 S 1 BM (ECM) BM (ECM) SW1 S W2 S W3 S W4 S W5 S W6 S W7 S W8 S W9 OF F O N ECM INTERFACE BOARD AL — Alarm Relay Contacts AST A T — Aq uastat BM — Blower Motor BR — Blow ...

  • Carrier 50PTH - page 17

    17 ECM INTERF ACE BOARD LA YOUT Y GGGGR W O Y2 Y1 G R C Y2 Y1 G O W C R DH AL 1 A A AL 1 SW 1 SW 2 SW 3 SW 4 SW 5 SW 6 SW 7 SW 8 SW 9 OFF ON G DEH UM C FM T B1 J 1 S 1 BM (ECM) ECM INTERFACE BOARD SW1 S W2 S W3 S W4 S W5 S W6 S W7 S W8 S W9 OF F O N BM (ECM) AL — Alarm Relay Contacts AST A T — Aquastat BM — Blower Motor CB — Circuit Breaker ...

  • Carrier 50PTH - page 18

    18 ECM INTERF ACE BOARD LA YOUT Y GGGGR W O Y 2 Y 1 G R C Y 2 Y 1 G O W C R D H A L 1 A A A L 1 S W1 S W2 S W3 S W4 S W5 S W6 S W7 S W8 S W9 OF F ON G D E HU M C F M T B 1 J1 S 1 BM (ECM) ECM INTERFACE BOARD BM (ECM) SW1 S W2 S W3 S W4 S W5 S W6 S W7 S W8 S W9 OF F O N AL — Alarm Relay Contacts AST A T — Aquastat BM — Blower Motor BR — Blo ...

  • Carrier 50PTH - page 19

    19 ECM INTERF ACE BOARD LA YOUT Y GGGGR W O Y2 Y1 G R C Y2 Y1 G O W C R DH AL 1 A A AL 1 SW 1 SW 2 SW 3 SW 4 SW 5 SW 6 SW 7 SW 8 SW 9 OFF ON G DEH UM C FM T B1 J 1 S 1 BM (ECM) ECM INTERFACE BOARD BM (ECM) SW1 S W2 S W3 S W4 S W5 S W6 S W7 S W8 S W9 OF F O N AL — Alarm Rela y Contacts AST A T — Aquastat BM — Blowe r Motor BR — Blo wer Relay ...

  • Carrier 50PTH - page 20

    20 *Optional Wiring. AL — Alar m Rela y Contacts AST A T — Aquastat BM — Blo wer Motor BMC — Blow er Motor Capacitor BR — B lower Rela y CB — Cir c uit Break er CC — Comp ressor Contactor CO — Sensor, Condensate Ov erflow DTS — Discharge T emperature Swit ch ECM — Electronically Commutated Motor FP1 — Sensor , Water Coil F ree ...

  • Carrier 50PTH - page 21

    21 *Optional Wiring. AL — Alar m Rela y Contacts AST A T — Aquastat BM — Blo wer Motor BMC — Blow er Motor Capacitor BR — B lower Rela y CB — Cir c uit Break er CC — Comp ressor Contactor CO — Sensor, Condensate Ov erflow DTS — Discharge T emperature Swit ch ECM — Electronically Commutat ed Motor FP1 — Sensor , Water Coil F re ...

  • Carrier 50PTH - page 22

    22 LEGEND AL — Alar m Rela y Contacts AST A T — Aquastat BM — Blo wer Motor BMC — Blow er Motor Capacitor BR — B lower Rela y CB — Cir c uit Break er CC — Comp ressor Contactor DTS — Discharge T emperature Swit ch ECM — Electronically Commutated Motor FP1 — Sensor , Water Coil F reeze Protectio n FP2 — Sensor , Air Coil Freez ...

  • Carrier 50PTH - page 23

    23 012207-1BT4 8 5BT LED1 DB In s t a ll BT4 8 5 where device i s loc a ted a t the end of network s egment only. + 24v a c (If not in s t a lled, it m us t b e connected to DO-5) DEHUMIDIFY OUTPUT CONTACT (DO-6) (FACTORY OPTION) FAN S PEED (DO-7) (MED OR LOW) OA DAMPER (AO-2) FAN S PEED (DO- 8 ) (HIGH OR FAN ON ) LWT (Inp u t 6) S AT (LAT) (Inp u ...

  • Carrier 50PTH - page 24

    24 W SH P O PE N W I RI NG — The WSHP Open controller will be factory mounted to the unit control panel and wired to the Complete C or Deluxe D control board, however , the system wiring will need to be completed utilizing WSHP Open con- troller wiring diagrams and the Third Party Integration (TPI) Guide. Factory installation in cludes harness, L ...

  • Carrier 50PTH - page 25

    25 T o wire the SPT sensor to the controller : 1. Partially cut , then bend and pull of f the outer jacket of the Rnet cable(s), being careful not to nick the inner insulation. 2. Strip about 1 / 4 in. of the inner insulation from each wire. See Fig. 26. 3. W ire each terminal on the sensor to the same terminal on the controller . See Fig. 15-24. T ...

  • Carrier 50PTH - page 26

    26 T YPICAL W ATER V ALVE C A 24 V AC T ERMINAL STRIP P2 Fig. 27 — Low V oltage Field Wiring AQ UAZONE CONTROL (Complete C Shown) Fig. 28 — T ypical Aquazone™ Contr ol Board Jumper Loc ations Fig. 29 — T ypical Accessory Wir ing a50-8141 COMPLETE C CONTROL CAP ACITOR LINE LOAD COMPRE SS OR CONT ACTOR TRAN S FORMER Y GGGGR W O Y2 Y1 G R C Y2 ...

  • Carrier 50PTH - page 27

    27 Step 10 — Operate ECM Interface Boar d ST ANDALONE — NO DDC CONTROLS — Th e E CM fan is controlled by an interface board that converts thermostat inputs and field selectable cfm settings to signals used by the ECM (electronically commutated motor) controller . See Fig. 32. NOTE: Power must be off to the unit for at least three seconds befo ...

  • Carrier 50PTH - page 28

    28 Table 13 — Blower Performance Data WS HP OP E N C ON TR O LS — The ECM fan is controlled by an interface board that converts the fan speed outputs from the WSHP Open control board to the signal used by the ECM mo- tor (see Fig 35). The indicator LEDs allow the service techni- cian to view the airflow mode that the WSHP Ope n control is comma ...

  • Carrier 50PTH - page 29

    29 Table 14A — WSHP Open — Fan Only / Low Fan an d Med Fan Airflow NO TE : F actor y default setting shown bo ld . IMPORT ANT: The tap setting for high fan MUST equal or e xce ed the tap setting for f an only/low/med f an Table 14B — WSHP Open — High Fan Airflow NO TE : F actor y default setting shown bo ld . IMPORT ANT: The tap setting f o ...

  • Carrier 50PTH - page 30

    30 16. Air coil is clean. 17. Control field-selected settings are correct . AI R CO IL — T o obtain maximum performance, clean the air coil before starting the unit. A 10% solution of dishwasher detergent and water is recommended for both sides of the coil. Rinse thoroughly with water . FIELD SELECT ABLE INPUTS Jumpers and DIP (dual in-line packa ...

  • Carrier 50PTH - page 31

    31 Boilerless Changeover T emperature — Switch 8 on S1 provides selection of boilerles s changeo ver temperature set point. Select OFF for set point of 50 F or select ON for set point of 40 F . If switch 8 is set for 50 F , then the compressor will be used for heating as long as the FP1 is above 50 F . The compressor will not be used for heating ...

  • Carrier 50PTH - page 32

    32 ground loop systems will not experience overcooling of the supply-air temperature. If ove rcooling of the space is a con- cern (e.g., computer room well water application), auxiliary heating may be required to maintain space temperature when the unit is operati ng in the dehumidification mode. W ater source heat pumps with HWR should not be used ...

  • Carrier 50PTH - page 33

    33 ST ART -UP Use the procedure outlined below to initiate proper unit start-up. NOTE: This equipmen t is designed for indoor installation on ly . Operating Limits EN VI R ON ME N T — This equipment is designed for indoor installation ONL Y . Extreme variations in temperature, humidi- ty and corrosive water or air will adversely af fect the unit ...

  • Carrier 50PTH - page 34

    34 Scr oll Compressor Rotation — It is important to be certain compressor is rotating in the proper direction. T o determine whether or not compre ssor is rotating in the proper direction: 1. Connect service gages to suction and disch arge pressure fittings. 2. Energize the compressor . 3. The suction pressure s hould drop and the discharge press ...

  • Carrier 50PTH - page 35

    35 Table 21 — Typical 50PTH,PTV,PTD038 Unit Operating Pressu res and Temperatures LEGEND Table 22 — Typical 50PTH,PTV,PTD049 Unit Operating Pressu res and Temperatures LEGEND Table 23 — Typical 50PTH,PTV,PTD064 ,072 Unit Operati ng Pressures and Temper atures LEGEND ENTERING WATE R TEMP (F) (EWT) WATE R FLO W (Gpm/T o n) FULL LO AD COOLING WI ...

  • Carrier 50PTH - page 36

    36 Unit Start-Up with WSHP Open Contr ols — The WSHP Open is a multi-protocol (default BACnet*) con- troller with extensive features, flexible options and powerful capabilities. The unit comes from the factory pre-programmed and needs minimal set up to function in a BAS (Building Automation System) system or provide additional capabilities to Car ...

  • Carrier 50PTH - page 37

    37 f. Press OK to appl y and save to a particular day of the week. g. Continue to add the same or dif ferent schedule spe- cific days of the week. T o add exceptions to the schedule: i. Press Add softkey . ii. Select exception type from follow ing: • Date • Date Range • W eek-N-Day • Calender Reference 9. Go back to Home Screen. 10. Remove ...

  • Carrier 50PTH - page 38

    38 Table 25 — Approximate Fluid Volume (gal.) per 100 Ft of Pipe LEGEND NO TE : V o lume of heat exchanger is approximatel y 1.0 gallon. Table 26 — Antifr eeze Percentages by Volume Cooling T ower/Boiler Systems — Thes e systems typically use a common loop temperature maintained at 60 to 95 F . Carrier recommends using a closed circuit evapor ...

  • Carrier 50PTH - page 39

    39 Output EH1, EH2, Fan Enable, and Fan Speed will be ON if the G input is not active during Emergency Heat mode. COOLING ST AG E 1 — In Co oli ng St age 1 m ode , t he Fa n Enable, compressor and R V relays are turned on immediately . If configured as stage 2 (DIP switch set to OFF) then the com- pressor and fan will not turn on until there is a ...

  • Carrier 50PTH - page 40

    40 ured maximum heating SA T limit (110 F default). As the SA T approaches this value, the cont rol will increase the fan speed as required to ensure the SA T will remain within the limit. This feature provides the most quiet and efficient operation by oper- ating the fan at the lowest speed possible. Fan Speed Co ntrol (Dur ing Coolin g) — Whene ...

  • Carrier 50PTH - page 41

    41 Auxiliary Mod ulating Hot W ater/Steam Heating Re heat — The control can modulate a hot water or steam valve con- nected to a coil on the discharge side of the unit and supplied by a boiler in order to maintain the desired heating set point should the compressor capacity be insuf ficient or a compressor failure occurs. Unless a compressor faul ...

  • Carrier 50PTH - page 42

    42 vide cooling to the space when required. Should the capacity be insufficient for a period grea ter than 5 minutes, or should a high humidity condition occur , then the compressor will be started to satisfy the load. Should the SA T reach the minimum cooling SA T limit, the economi zer valve will close during compressor operation. Heating — Add ...

  • Carrier 50PTH - page 43

    43 WSHP Open T est Mode — T o enter WSHP Open test mode, navigate from the BAC view 6 home screen to the config- uration screen. Choose the servic e screen and enable unit test. The controller will then test the following: F AN T ES T — T ests all fan speeds, sequence s fan from low to high, and operates each speed for one minute. Resets to dis ...

  • Carrier 50PTH - page 44

    44 SER VICE Perform the procedures ou tlined below periodically , as indicated. Filter s — Filters must be clean for maximum performance. Inspect filters every month under normal operating conditions. Replace when necessary . W ater Coil — Keep all air out of the water coil. Check open loop systems to be sure the well head is not allowing air t ...

  • Carrier 50PTH - page 45

    45 Checkin g System Charge — Units are shipped with full operating charge. If rechar ging is necessary: 1. Insert thermometer bulb in insulating rubber sleeve on liquid line near filter drier . Use a digital thermometer for all temperature measurements. DO NOT use a mercury or dial-type thermometer . 2. Connect pressure gage to di schar ge line n ...

  • Carrier 50PTH - page 46

    46 WSHP Open Contr oller — W ith the WSHP Open con- troller option, the 100 most recent alarms can be viewed using the BAC view 6 alarm status and alarm history . T o view the alarms: 1. Navigate to the Alarm S tatus screen from the Home screen using the arrow softkeys. The screen will display the current alarm status , either normal or Alarm, an ...

  • Carrier 50PTH - page 47

    47 The bulb must be secured to the pipe using a copper strap. The use of heat transfer paste between the bulb and the pipe will also help ensure optimum performance. The bulb must also be properly insulated to eliminate any influence on valve operation by the surrounding conditions. Cork tape is the recommended insulation as it can be molded tight ...

  • Carrier 50PTH - page 48

    48 See T ables 30-32 for additional troubleshooting information. Table 30 — ECM Tro ubleshooting CA UTION Puron ® refrigerant (R-410A) requ ires the use of synthetic lubricant (POE oil). Do not use common tools on systems that contain R-22 refrigerants or mineral oil. Contamina- tion and failure of this equipment may result. IMPORTANT: Due to th ...

  • Carrier 50PTH - page 49

    49 Fig. 39 — ECM Pin Connector s a50-8448 ...

  • Carrier 50PTH - page 50

    50 Stopped or Malfunctioned ECM Motor — Refer to Fig. 40 to determine the possible cause of a stopped or mal- functioned ECM motor . Follow the instructions in the boxes. Fig. 40 — ECM T roubl eshooting Flow Dia gram a50-8447 ...

  • Carrier 50PTH - page 51

    51 Moisture Check — T o perform moisture check: • Check that connectors are orie ntated “down” (or as recom- mended by equipment manufacturer). • Arrange harnesses with “drip loop” under motor . • Check if condensate drain is plugged. • Check for low airflow (too much latent capacity). • Check for undercharged condition. • Che ...

  • Carrier 50PTH - page 52

    52 Table 32 — WSHP Troubleshoot ing (cont) LEGEND F A UL T HEA TING COOLING POSSIBLE CAUSE SOLUTION Over/Under V oltage — Code 7 (A uto Resetting) X X Under voltage Check power supply and 24 v a c v oltage bef ore and during operation. Check po wer supply wire size . Check compressor starting. Check 24 v ac and unit transf or mer tap f or corre ...

  • Carrier 50PTH - page 53

    53 Table 32 — WSHP Troubleshooting ( cont) LEGEND F A UL T HEA TING COOLING P OSSIBLE CA USE SOLUTION High Head Pressure X Reduced or no airflo w in heating Chec k for dirty air filter and clean or replace. Check f an motor operation and airflow restrictions . External static too high. Check b lower perf ormance per T ables 9-13. X Reduced or no ...

  • Carrier 50PTH - page 54

    54 APPENDIX A — WSHP OPEN SCREEN CONFIGURA TION LEGEND SCREEN NAME P OINT NAME PA SS WO RD LEVEL EDITABLE RANGE DEFAULT NOTES Equipment Status Operati ng Mode No P assword Required Off, F an Only , Economize , Cooling, Heating, Cont F an, T est, Start Delay , Dehumidify Display s unit operat ing mode SPT F Displa ys SPT SA T F Displays SA T Conde ...

  • Carrier 50PTH - page 55

    55 APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PA S SWO RD LEVEL EDITABLE RANGE DEFAULT NOTES Unit Maintenance Operating Mode No P assw o rd required Off, F an On ly ,Econom ize, Cooling, Heating, Cont F an, T est, Start Delay , Dehumidify Display s unit operating mode F an Operating Mode Auto /Continuous/Alwa ...

  • Carrier 50PTH - page 56

    56 APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont) LEGEND SCREEN NAME P OINT NA ME PAS SW ORD LEVEL EDITABLE RANG E DEFAULT NOTES Configuration Set Points Occupied Heating User/Admin P a ss word lev e l access X 40 - 90 F 72 F Defines the Occupied Heating Set P oint Occupied Cooling X 55 - 99 F 76 F Defines the Occupied Cooling Set P oint Unoc ...

  • Carrier 50PTH - page 57

    57 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PA S SWO RD LEVE L EDITABLE RANGE DEFAULT NOTES Configuration Unit Configuration F an Mode Admin P assword lev el access only X Aut o/Continuous/ Always On Continuous Aut o= Inter mittant oper ation during both occupied and unoccupied periods/ Continuou s = Interm ...

  • Carrier 50PTH - page 58

    58 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PAS SW OR D LEVEL EDITABLE RANGE DEFAULT NOTES Configuration Service Configuration # of F an Speeds Admin P assword lev el access only X 1,2,3 3 Us ed to set n umber of fan mot or speeds G Output T ype X F an On/F an Low F an On When set to F an On, G output is en ...

  • Carrier 50PTH - page 59

    59 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME P OINT NAME PA SS WOR D LEVEL EDITABLE RANGE DEFAULT NOT ES Configuration Alarm Configuration SPT Occupied Alarm Hysteresis Admin P assword lev el access only X2 - 2 0 F 5 F Defines the h ysteresis applied above the cooling and belo w the heatin g set points bef ore an alar ...

  • Carrier 50PTH - page 60

    ...

  • Carrier 50PTH - page 61

    ...

  • Carrier 50PTH - page 62

    Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No . 04-53500079-01 Printed in U. S.A. F orm 50PT -4SI Pg 62 7-10 Replaces: 50PT -3SI Copy right 2010 Carrier Cor poration ...

  • Carrier 50PTH - page 63

    CL-1 50PTH,PTV ,PTD ST ART -UP CHECKLIST CUSTOMER: ___________________________ JOB NAME: _______________________________________ MODEL NO.:___________________________ SERIAL NO.:____________________ DA TE: _________ I. PRE-ST ART -UP DOES THE UNIT VOL T AGE CORRESPOND WI T H THE SUPPL Y VOL T AGE A V AILABLE? (Y/N) HA VE THE POWER AND CONTROL WIRIN ...

  • Carrier 50PTH - page 64

    Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No . 04-53500079-01 Printed in U .S.A. Form 50PT -4SI Pg CL-2 7-10 Replaces: 50PT -3SI Copy right 2010 Carrier Cor poration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ...

Fabbricante Carrier Categoria Heat Pump

I documenti che otteniamo dal fabbricante del dispositivoCarrier 50PTH possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Carrier
- manuali per l’uso 50PTH
- schede prodotto Carrier
- opuscoli
- o etichette energetiche Carrier 50PTH
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Carrier 50PTH.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Carrier 50PTH, manuali di manutenzione, brevi manuali o manuali utente Carrier 50PTH. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Carrier 50PTH.

Manuali per l’uso simili

Manuale completo del dispositivo Carrier 50PTH, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Carrier 50PTH dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Carrier 50PTH.

Il manuale per l’uso completo Carrier, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Carrier 50PTH - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Carrier 50PTH, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Carrier 50PTH che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Carrier 50PTH - che ci dovrebbe aiutare nei primi passi durante l'uso Carrier 50PTH
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Carrier 50PTH
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Carrier 50PTH in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Carrier 50PTH?

Utilizza il modulo sottostante

Se non hai risolto il problema con Carrier 50PTH con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Carrier 50PTH è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)