    TECHNICAL GUIDE SPLIT -SYSTEM A IR CONDITIONERS 13 SEER – R-22 MODELS: TCGD12 THRU 60 (1 THRU 5 NOMINA L TONS, 1 PHASE) Due to continuous produc t impr ovement, specifications are subject to change without notice. V isit us on th e web at www .york.com A dditional rating informa tion can be fo und at w ww .ahridirectory . org LISTED ISO 9001 Cert ...

  • York TCGD12 THRU 60 - page 2

    400034-YTG-B-0708 2 Johnson Controls Unitary Products All dimensions are in inches. They are subject to cha nge without notice. Ce rtif ied dimensio ns will be provide d upon request. Physical and Electr ical Dat a MODEL TCGD12 S21S2(H) TCGD18 S21S2(H) TCGD24 S21S2(H) TCGD30 S21S2( H) TCGD3 6 S21S2( H) TCGD4 2 S21S2(H) TCGD48 S21S2(H) TCGD60 S21S2 ...

  • York TCGD12 THRU 60 - page 3

    400034-YTG-B-0708 Johnson Controls Unitary Produ cts 3 Additional R-22 Charge / Orifice Size for V arious Matched Systems Outdoor Unit TCGD12 S21S2(H) TCGD18 S21S2(H) TCGD24 S21S2(H) TCGD30 S21S2(H) TCGD36 S21S2(H) TCGD42 S21S2(H) TCGD48 S21S2(H) TCGD60 S21S2 Required Orifice or TXV 1,2 0.041 / 2A 0.052 / 2A 0.059 / 0.061 / 2A 0.065 / 2A 0.073 / 2A ...

  • York TCGD12 THRU 60 - page 4

    400034-YTG-B-0708 4 Johnson Controls Unitary Products PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refr igerant for th e condenser , the smallest evaporator and 15 feet of inter- connecting line tubing. 2. V erify the TXV or orifice and additional charge required for s pecific evaporator coil in t he system using the abo ...

  • York TCGD12 THRU 60 - page 5

    400034-YTG-B-0708 Johnson Controls Unitary Produ cts 5 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT A L SENS. 13 SEER AC WITH MA TCGD18S21S2(H) MA08B 17 F C/MC18B 600 18.0 12.6 13.00 1 1.00 MA08B 17 FC/MC24B 600 18 .0 12.6 13.00 1 1.00 TCGD24S21S2(H) MA08B 17 F C/MC3 ...

  • York TCGD12 THRU 60 - page 6

    400034-YTG-B-0708 6 Johnson Controls Unitary Products — = Not applicable. 13 SEER AC WITH AHP / SHP / F*FP TCGD12S21S2(H) AHP18 17 – 450 12.0 8.9 13.00 1 1.00 TCGD18S21S2(H) AHP18 17 – 650 18.0 12.6 13.00 1 1.00 AHP24 17 – 650 18.0 12.6 13.00 1 1.00 F4FP024 18 – 600 18.0 12.6 1300 1 1.00 TCGD24S21S2(H) AHP30 17 – 795 24.0 17.3 13.00 1 1 ...

  • York TCGD12 THRU 60 - page 7

    400034-YTG-B-0708 Johnson Controls Unitary Produ cts 7 COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TED CFM NET MBH SEER 1 EER TOT A L SENS. TCGD12S21S2(H) 450 - 750 14,17 FC/MC/PC18 450 12.0 9.1 13.00 1 1.00 450 - 750 14 HC18 450 12.0 9.1 13.00 1 1.00 ...

  • York TCGD12 THRU 60 - page 8

    400034-YTG-B-0708 8 Johnson Controls Unitary Products 1 COOLING CAP ACITY - With V ariable Spe ed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT A L SENS. 13 SEER AC WITH V ARIABLE SPEED FUR NACES 2 TCGD18S21S2(H) PV8*A12 FC/MC/PC18A 14 600 18.0 13.0 14.00 12.00 PV9*A12 FC/MC/PC18A 14 600 18 ...

  • York TCGD12 THRU 60 - page 9

    400034-YTG-B-0708 Johnson Controls Unitary Produ cts 9 TCGD36S21S2(H) PV8*A12 FC/MC/PC37A 14 1200 35 .2 25.0 14.00 12.00 PV9*A12 FC/MC/PC37A 14 1200 35 .2 25.0 14.00 12.00 PV8*B16 FC/MC/PC43B 17 1200 35.4 25.0 14.00 12.00 PV8*C16 FC/MC/PC43C 21 1200 35 .4 25 .0 14.00 12.00 PV8*C20 FC/MC/PC43C 21 1200 35 .6 25 .0 14.00 12.00 P(C,V)9*B12 FC/MC/PC43B ...

  • York TCGD12 THRU 60 - page 10

    400034-YTG-B-0708 10 Johnson Controls Unitary Products ACCESSORIES Refer to Price Manual for specific model numbers. HARD ST ART KIT - Required when using TXV i ndoor coil. Also, provides increased starting torque for a reas with low voltage. OFF CYCLE TIMER DELA Y - Provides a 5-minute off cycle to prevent rapid recycling of the compressor . ROOM ...

  • York TCGD12 THRU 60 - page 11

    400034-YTG-B-0708 Johnson Controls Unitary Produ cts 11 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York TCGD12 THRU 60 - page 12

    400034-YTG-B-0708 12 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York TCGD12 THRU 60 - page 13

    400034-YTG-B-0708 Johnson Controls Unitary Produ cts 13 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York TCGD12 THRU 60 - page 14

    400034-YTG-B-0708 14 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York TCGD12 THRU 60 - page 15

    400034-YTG-B-0708 Johnson Controls Unitary Produ cts 15 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York TCGD12 THRU 60 - page 16

    400034-YTG-B-0708 16 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York TCGD12 THRU 60 - page 17

    400034-YTG-B-0708 Johnson Controls Unitary Produ cts 17 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York TCGD12 THRU 60 - page 18

    Subject to change without notice. Printe d in U.S.A. 400034-YTG-B-0708 Copyright © 2008 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 400034-YTG-A-0408 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif fere ...

Fabbricante York Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoYork TCGD12 THRU 60 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici York
- manuali per l’uso TCGD12 THRU 60
- schede prodotto York
- opuscoli
- o etichette energetiche York TCGD12 THRU 60
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso York TCGD12 THRU 60.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione York TCGD12 THRU 60, manuali di manutenzione, brevi manuali o manuali utente York TCGD12 THRU 60. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto York TCGD12 THRU 60.

Manuali per l’uso simili

Manuale completo del dispositivo York TCGD12 THRU 60, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare York TCGD12 THRU 60 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti York TCGD12 THRU 60.

Il manuale per l’uso completo York, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale York TCGD12 THRU 60 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice York TCGD12 THRU 60, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per York TCGD12 THRU 60 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo York TCGD12 THRU 60 - che ci dovrebbe aiutare nei primi passi durante l'uso York TCGD12 THRU 60
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del York TCGD12 THRU 60
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio York TCGD12 THRU 60 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su York TCGD12 THRU 60?

Utilizza il modulo sottostante

Se non hai risolto il problema con York TCGD12 THRU 60 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con York TCGD12 THRU 60 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)