Manuale per l’uso APC 3000T

33 pagine 0.46 mb
Scarica

Vai alla pagina of 33

Summary
  • APC 3000T - page 1

    990 - 7031D, Revision 5 5/01 APC Smart - UPS Uninterruptible Power Supply Models 1400XLT, 2200XLT, 3000T, 5000T User’s Manual ...

  • APC 3000T - page 2

    Entire contents copyright ©1999 by American Power Conversion. All rights reserved. Reproduction in whole or in part without permission is prohibited. Smart - UPS is a registered trademark of APC. All other trademarks are the property of their respective owners. 990 - 7031D, Revision 5 5/01 ...

  • APC 3000T - page 3

    990 - 7031D, Revision 5 5/01 Smart UPS Safety Guide English This Safety Guide contains important instructions that should be followed durin g installation and maintenance of the APC equipment and batteries. It is intended for APC customers who setup, install, relocate, or maintain APC equipment. Handling Safety • Be careful. Do not lift heavy loa ...

  • APC 3000T - page 4

    990 - 7031D, Revision 5 5/01 2 ...

  • APC 3000T - page 5

    990 - 7031D, Revision 5 5/01 Table of Contents Introduction ............................................................................................................................................................................................... 1 Unpacking ...................................................................................... ...

  • APC 3000T - page 6

    ...

  • APC 3000T - page 7

    990 - 7031D, Revision 5 5/01 1 Introduction This Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brownouts, sags and surges from reaching your computer and other valuable electronic equipment. This UPS also filters out small utility line fluctuations and isolates your equipment from large disturbances by internally disconnectin ...

  • APC 3000T - page 8

    990 - 7031D, Revision 5 5/01 2 Installing your UPS requires five steps: 1. Position the UPS in the desired location. For rack mount units this may include installing the rails into the rack. 2. Connect the batteries. All UPSs ship with the batteries disconnected. In 5000 VA units you must also install the batteries in the UPS. 3. Connect equipment ...

  • APC 3000T - page 9

    990 - 7031D, Revision 5 5/01 3 * * Caution: Check the rack to make sure it won’t tip after moving the mounting brackets. 1. Determine where in the r ack you’ll mount the UPS. The SU5000 requires a space of 5U. Some racks have tick marks to indicate the U - spaces. 2. Using the mounting template provided (part number 990 - 0195), identify and ma ...

  • APC 3000T - page 10

    990 - 7031D, Revision 5 5/01 4 3 Expand the rails so that it spans from the front rack post to the back rack post. Replace the two screws (removed in step 1) t hat hold the rail sections together. 4 Back Attach the rail to the back rack post using the same hardware (10 - 32 flat head screws and conical washers) used in step 2. Repeat the process fo ...

  • APC 3000T - page 11

    990 - 7031D, Revision 5 5/01 5 2. Connect the Ba tteries Note: All UPSs ship with the batteries disconnected. In addition, 5000 VA units have the batteries shipped outside the UPS case so you must install the batteries before connecting them. If you need to ship the UPS you must disconnect the batteri es prior to shipment in order to comply with U. ...

  • APC 3000T - page 12

    990 - 7031D, Revision 5 5/01 6 3U Rack Mount Units 1. Reach into the finger pull and open the front cover. Swing the cover open as shown. 2. Unhook the side of the cover from the chassis and lift it away to expose the battery door. 3. Use a flat - blade or Phillips screwdriver or a coin to remove the two battery door screws an d open the door. 4. C ...

  • APC 3000T - page 13

    990 - 7031D, Revision 5 5/01 7 3. Connect Power and Equipment to the UPS • Connect the UPS line cord (L6 - 30 plug) into the electrical outlet. • Use your equipment’s powe r cords to connect to the UPS. Caution: DO NOT use a standard serial interface cable to connect to the Computer Interface Port on the UPS. Standard serial interface cables ...

  • APC 3000T - page 14

    990 - 7031D, Revision 5 5/01 8 Connect Computer Interface Port (Optional) Power management software and interface kits can be used with this UPS. Use only kits supplied or approved by the manufacturer. If used, connect the interface cable to the 9 - pin computer interface port on the back panel of the U PS. Secure the connector’s screws to comple ...

  • APC 3000T - page 15

    990 - 7031D, Revision 5 5/01 9 With the UPS plugged in, press and release the large upper on/test button to supply power to the loads. The loads are immediately powered while the UPS beeps and performs a self - test. Press and release the small, lower off button to turn off power to the loads. It may be convenient to use the UPS as a master on/off ...

  • APC 3000T - page 16

    990 - 7031D, Revision 5 5/01 10 The SmartTrim LED comes on to indicate that the UPS is compensating for a high voltage. SmartBoost The SmartBoost LED comes on to indicate that the UPS is compensating for a low voltage. Low Battery When the UPS is operating on - battery and the energy reserve of the battery runs low, the UPS beeps continuously until ...

  • APC 3000T - page 17

    990 - 7031D, Revision 5 5/01 11 Storage Storage Conditions Store the UPS covered and upright in a cool, dry location, with its battery fully charged. Before storing, charge the UPS for at least two hours. Remove any accessories in the accessory slot and disc onnect any cables connected to the computer interface port to avoid unnecessarily draining ...

  • APC 3000T - page 18

    990 - 7031D, Revision 5 5/01 12 Battery Replacement Procedure - Tower Units 5000 VA 1. Grasp the top edge of the bottom front cover and tilt it out. For the 5000 VA unit: Remove the front bezel by grasping the finger clips on the side of the bezel and carefully loosening the four (4) snaps. Skip to step 3. 1400 - 3000 VA 5000 VA 2. Unhoo k the bott ...

  • APC 3000T - page 19

    990 - 7031D, Revision 5 5/01 13 Battery Replacement Procedure - 3U Rack Mount Units 1. Reach into the finger pull and open the front cover. Swing the cover open as shown. 2. Unhook the side of the cover from the chassis and lift it away to expose the battery door. 3. Use a flat - blade or Phillips screwdriver or a coin to remove the two battery doo ...

  • APC 3000T - page 20

    990 - 7031D, Revision 5 5/01 14 Battery Replacement Procedure - 5U Rack Mount Units 5000 VA 1. Reach into the finger pull and open the front cover. Swing the cover open as shown. For 5000 VA units: Remove the front bezel by grasping the finger clips on the side of the bezel and carefully loosening the four (4) snaps. Skip to step 3. 2. Unhook the s ...

  • APC 3000T - page 21

    990 - 7031D, Revision 5 5/01 15 Batteries must be recycled . Deliver the battery to an appropriate recycling facility or ship it to the supplier in the new battery’s packing material. See the new battery instructions for more information. ...

  • APC 3000T - page 22

    990 - 7031D, Revision 5 5/01 16 User Configuration Items Note: Setting these items requires optional software or hardware. Function Factory Default User Selectable Choices Description Automatic Self - Test Every 14 days (336 hours) Every 7 days (168 hours), On Startup Onl y, No Self - Test Sets the interval at which the UPS will execute a self - te ...

  • APC 3000T - page 23

    990 - 7031D, Revision 5 5/01 17 2200 0.13 0.35 0.63 0.93 1.25 1.67 2.00 2.42 2.83 3.17 3.58 ...

  • APC 3000T - page 24

    990 - 7031D, Revision 5 5/01 18 Tower and 5U Rack Mount Models - 3000 & 5000 VA Models Typical On - Battery Run Time Versus Load, in Hours Load 3000 VA Internal Battery 3000 VA w/ 1 Battery Pack 5000 VA Internal Battery 100 VA 3.80 8.18 7.17 150 VA 3.05 6.57 5.95 200 VA 2.35 5.42 5.04 300 VA 1.83 4.08 3.88 400 VA 1.40 3.22 2.96 500 VA 1.12 2.62 ...

  • APC 3000T - page 25

    990 - 7031D, Revision 5 5/01 19 Specifications 1400 VA 2200 VA 3000 VA 5000 VA Acceptable input voltage 0 - 325 VAC Input voltage (on - line operation)* 160 - 253 VAC 208 volt output range* 1 77 - 229 VAC 120 volt output range * with 400 VA load with no load 95 - 130 VAC 100 - 135 VAC Nominal input frequency 50 or 60 Hz, autosensing Input protectio ...

  • APC 3000T - page 26

    990 - 7031D, Revision 5 5/01 20 Troubleshooting Use the chart below to solve minor UPS installation problems. Contact APC Technical Support Staff for assistance with complex UPS problems. See APC Contact Information , page 21 , for a location near you. Problem and Possible Cause Solution UPS will not tur n on. • ON button not pushed. Press the ON ...

  • APC 3000T - page 27

    990 - 7031D, Revision 5 5/01 21 • Weak batteries. Do another self test to see if it clears. • Replacement batteries not connected properly. Confirm the battery connections. Service If the UPS requires service do not return it to the dealer! Follow these steps: 1. Review the problems discussed in Troubleshooting , page 20 , to eliminate common p ...

  • APC 3000T - page 28

    990 - 7031D, Revision 5 5/01 22 EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL APC BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PROD UCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, APC is not liable for any costs, such as lost profits or revenue, loss of equipment, lo ...

  • APC 3000T - page 29

    990 - 7031D, Revision 5 5/01 23 Appendix A: XL Information When used with external battery packs, the extended run (XL) UPS offers longer run times than a standard UPS and extra load protection during battery replacement. When replacing the batteries either in the UP S or battery pack(s), the UPS can still respond to a power disturbance using the r ...

  • APC 3000T - page 30

    990 - 7031D, Revision 5 5/01 24 Smart - UPS XL models are not designed to know how many external battery packs are connected to them. You must program the Smart - UPS XL with the appropriate number of external batteries in one of four ways. Note: It is important to follow these instructions. The number of batteries affects the run time calculations ...

  • APC 3000T - page 31

    990 - 7031D, Revision 5 5/01 25 Use the HyperTerminal Program to Change the Number of External Battery Packs HyperTerminal is used for Windows 95, Windows 98, and Windows NT 4.0 1. EXIT out of the PowerChute plus Server. In the case of Windows NT, the UPS service must be stopped. 2. From t he Desktop, go to: Start => Programs => Accessories = ...

  • APC 3000T - page 32

    990 - 7031D, Revision 5 5/01 26 Appendix B: Types of Racks and Mounting Hardware This appendix describes the hardware required for the different types of racks and describes the type of racks that may be used in your industry. All APC rack mount units are shipped ready for 19 - inch wide EIA/IEC rack cabinets. Some rack mount UPSs ship with rails i ...

  • APC 3000T - page 33

    990 - 7031D, Revision 5 5/01 27 Appendix C: Transporting Your Smart - UPS Follow these guidelines if you need to ship the UPS to another location. These guidelines apply whether you are transporting the UPS alone, ra ck mounted in an equipment cabinet, or installed in a system. Caution: Always DISCONNECT THE BATTERIES before shipping the UPS to avo ...

Fabbricante APC Categoria Power Supply

I documenti che otteniamo dal fabbricante del dispositivoAPC 3000T possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici APC
- manuali per l’uso 3000T
- schede prodotto APC
- opuscoli
- o etichette energetiche APC 3000T
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso APC 3000T.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione APC 3000T, manuali di manutenzione, brevi manuali o manuali utente APC 3000T. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto APC 3000T.

Manuali per l’uso simili

Manuale completo del dispositivo APC 3000T, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare APC 3000T dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti APC 3000T.

Il manuale per l’uso completo APC, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale APC 3000T - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice APC 3000T, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per APC 3000T che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo APC 3000T - che ci dovrebbe aiutare nei primi passi durante l'uso APC 3000T
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del APC 3000T
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio APC 3000T in un dato paese, se il problema non può essere risolto da noi stessi.