    07/1 1 506645−01 *2P0711* *P506645-01* Page 1  201 1 Lennox Industries Inc. Dallas, T exas, USA RET AIN THESE INSTRUCTIONS FOR FUTURE REFERENCE These instructions are intended as a general guide and do not supersede local codes in any way . Consult authorities who have jurisdiction before inst allation. W ARNING Improper installation, adjustme ...

  • Lennox International Inc. CONDENSING UNITS - page 2

    Page 2 506645−01 Unit Dimensions − Inches (mm) SUCTION AND LIQUID LINE CONNECTION DISCHARGE AIR SIDE VIEW OUTDOOR COIL F AN COMPRESSOR A B A OPTIONAL UNIT ST ANDOFF KIT (4) (FIELD INST ALLED) SIDE VIEW Model Numbers A B 14ACX−018−230 24−1/4 (616) 29−1/4 (743) 14ACX−024−230 28−1/4 (724) 33−1/4 (845) 14ACX−030−230 28−1/4 (72 ...

  • Lennox International Inc. CONDENSING UNITS - page 3

    Page 3 14ACX SERIES T ypical Unit Parts Arrangement COMPRESSOR HARNESS CONNECTION LIQUID LINE SERVICE V AL V E SUCTION LINE SERVICE V AL VE OUTDOOR COIL DISCHARGE LINE HIGH PRESSURE SWITCH (S4) COMPRESS0R (B1) GROUND LUG CONT ACT OR (K1) CONTROL DUAL RUN CAP ACIT OR (C12) CONTROL WIRE LOOP CUTOUT FOR HIGH VOL TAGE CONDUIT NOTE  Plumbing layout a ...

  • Lennox International Inc. CONDENSING UNITS - page 4

    Page 4 506645−01 CAUTION Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury . Be aware of, and use caution when working near these areas during installation or while servicing this equipment. Operating Manifold Gauge Set and Service V alves These instructions are intended as ...

  • Lennox International Inc. CONDENSING UNITS - page 5

    Page 5 14ACX SERIES (V AL VE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE SERVICE PORT CORE SER VICE PORT CAP ANGLE−TYPE SERVICE V AL VE (FRONT−SEA TED CLOSED) SER VICE PORT CORE TO OUTDOOR UNIT STEM CAP (V AL VE STEM SHOWN OPEN) INSER T HEX WRENCH HERE TO INDOOR UNIT ANGLE−TYPE SERVICE VALVE (BACK−SEATED OPENED) BALL (SHOWN CLOSED) SER VICE P ...

  • Lennox International Inc. CONDENSING UNITS - page 6

    Page 6 506645−01 Recovering Refrigerant from Existing System Use the following procedure to recover refrigerant from an existing system (indoor coil, line set and outdoor unit). SER VICE DISCONNECT SWITCH MAIN FUSE BOX/BREAKER P ANEL Disconnect all power to the existing outdoor unit at the service disconnect switch or main fuse box/breaker panel. ...

  • Lennox International Inc. CONDENSING UNITS - page 7

    Page 7 14ACX SERIES 6 (152) 36 (914) 12 (305) 30 (762) LINE SET CONNECTIONS 24 (610) LINE SET CONNECTIONS ACCESS P ANEL 48 (1219) MINIMUM CLEARANCE BETWEEN TWO UNITS CLEARANCE ON ALL SIDES  INCHES (MILLIMETERS) ACCESS P ANEL MINIMUM CLEARANCE ABOVE UNIT NOTES:  Clearance to on e of the o ther three sides must be 36 inches (914mm).  Clearan ...

  • Lennox International Inc. CONDENSING UNITS - page 8

    Page 8 506645−01 PLACING UNIT ON SLAB When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 5, detail B. ROOF MOUNTING Install the unit at a minimum of 4 inches (102 mm) above the su ...

  • Lennox International Inc. CONDENSING UNITS - page 9

    Page 9 14ACX SERIES New or Replacement Line Set This section provides information on new installation or replacement of existing line set. If a new or replacement line set is not required, then proceed to Brazing Connections on p age 1 1. Field refrigerant piping consist s of liquid and suction lines from the out door un it (braze connections) to t ...

  • Lennox International Inc. CONDENSING UNITS - page 10

    Page 10 506645−01 ANCHORED H EA VY NYLON WIRE TIE OR AUT OMOTIVE MUFFLER-TYPE HANGER STRAP LIQUID LINE TO V APOR LINE W ALL STUD LIQUID LINE NON−CORROSIVE MET AL SLEEVE V APOR LINE − WRAPPED IN ARMAFLEX AUT OMOTIVE MUFFLER-TYPE HANGER REFRIGERANT LINE SET  TRANSITION FROM VERTICAL TO HORIZONT AL Line Set Isolation  The following illustr ...

  • Lennox International Inc. CONDENSING UNITS - page 11

    Page 1 1 14ACX SERIES Brazing Connections Use the procedures outline in figures 9 and 1 0 for brazing line set connections to service valves. IMPORT ANT Polyol ester (POE) oils used wit h HFC−410A refr igerant absorb moisture very quickly . It is very important that the refrigerant sys tem be kept closed as much as possible. DO NOT remove li ne s ...

  • Lennox International Inc. CONDENSING UNITS - page 12

    Page 12 506645−01 A TT ACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / V APOR LINE SER VICE V AL VES OUTDOOR UNIT LIQUID LINE V APOR LINE LIQUID LINE SERVICE VA LV E SUCTION / V APOR LINE SER VICE VA LV E A TTACH GAUGES INDOOR UNIT SUCTION / V APOR SER VICE POR T MUST BE OPEN TO ALLOW EXIT POINT FOR NITROGEN A Connect gauge set low pr ...

  • Lennox International Inc. CONDENSING UNITS - page 13

    Page 13 14ACX SERIES WHEN BRAZING LINE SET TO SER VICE V AL VES, POINT FLAME A W A Y FROM SER VICE V A L VE. LIQUID LINE SERVICE V AL VE LIQUID LINE BRAZE LINE SET W rap both service valves with water saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set . W ater saturated cloths must remain water saturated thr ...

  • Lennox International Inc. CONDENSING UNITS - page 14

    Page 14 506645−01 Flushing Line Set and Indoor Coil Flushing is only required if existing indoor coil and line set are to be used. Otherwise proceed to Installing Indoor Metering Device on page 15 . SENSING LINE TEFLON ® RING FIXED ORIFICE BRASS NUT LIQUID LINE ASSEMBL Y (INCLUDES STRAINER) LIQUID LINE ORIFICE HOUSING DISTRIBUT OR TUBES DISTRIBU ...

  • Lennox International Inc. CONDENSING UNITS - page 15

    Page 15 14ACX SERIES Installing Indoor Metering Device This outdoor unit is designed for use in systems that use either an fixed orifice (RFC) (included with outdoor unit), or exp ansion valve metering device (purchased sep arately) at the indoor coil. See the Lennox 14ACX Engineering Handbook for approved e x pansion valve kit matc h u ps. The exp ...

  • Lennox International Inc. CONDENSING UNITS - page 16

    Page 16 506645−01 IMPORT ANT The Environmental Protection Agency (EP A) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery , recycling or reclaiming must be followed. IMPORT ANT If this unit is being matc hed with an approved line set or indoor unit coi ...

  • Lennox International Inc. CONDENSING UNITS - page 17

    Page 17 14ACX SERIES Evacuating Line Set and Indoor Coil A Open both manifold valves and start the vacuum pump. B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury). NOTE  During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in ...

  • Lennox International Inc. CONDENSING UNITS - page 18

    Page 18 506645−01 W ARNING Danger of Equipm ent Damage. A void deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compress or failure. Damage caused by deep vacuum operat ion will void warranty . CAUTION Brazing alloys and flux cont ain materials which are hazardous to your heal ...

  • Lennox International Inc. CONDENSING UNITS - page 19

    Page 19 14ACX SERIES Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. T o facilitate a conduit, a cutout is located in the bottom of the control panel. Connect conduit to the control panel using a proper conduit fitting. ROUTING HIGH VOL T AGE/ GROUND AND CONTROL WIRING HIGH VOL T AGE FIELD ...

  • Lennox International Inc. CONDENSING UNITS - page 20

    Page 20 506645−01 HIGH PRESSURE SWITCH (S4)  LIQUID LINE CRANKCASE THERMOST A T (S40) CRANKCASE HEA TER (HR1) Figure 16. T ypical Factory Wiring Diagram (Copeland Compressor) ...

  • Lennox International Inc. CONDENSING UNITS - page 21

    Page 21 14ACX SERIES CRANKCASE HEA TER (HR1) HIGH PRESSURE SWITCH (S4)  LIQUID LINE CRANKCASE THERMOST A T (S40) THERMAL PROTECTION SWITCH (S5 OR S173) Figure 17. T ypical Factory Wiring Diagram (Interlink Compressor) ...

  • Lennox International Inc. CONDENSING UNITS - page 22

    Page 22 506645−01 Servicing Units Delivered V oid of Charge If the out door unit is void of refrigerant, clean the system using the procedure described below . 1. Leak check system using procedure outlined in this instruction. 2. Evacuate the system using procedure outlined in this instruction. 3. Use nitrogen to break the vacuum and install a ne ...

  • Lennox International Inc. CONDENSING UNITS - page 23

    Page 23 14ACX SERIES CHECKING AIR FLOW A T INDOOR COIL Check airflow using the Delta−T ( D T) process using the illustration in figure 19. 1. Determine the desired D T Measure entering air temper- ature using dry bulb ( A ) and wet bulb ( B ). D T is the intersect- ing value of A and B in the t able (see triangle). 2. Find temperature drop acr ...

  • Lennox International Inc. CONDENSING UNITS - page 24

    Page 24 506645−01 Liquid Line Set Diameter Ounces per 5 feet (g per 1.5 m) adjust from 15 feet (4.6 m) line set* 3/8" (9.5 mm) 3 ounce per 5’ (85 g per 1.5 m) *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount. Refrigerant Charge per Line Set Length NOTE  The ...

  • Lennox International Inc. CONDENSING UNITS - page 25

    Page 25 14ACX SERIES 1. Confirm proper airflow across coil using figure 19. 2. Compare unit pressures with table 4, Normal Operating Pressures . USE WEIGH-IN METHOD Weigh-in or remove refrigerant based upon line length SCº (Subcooling) V alues (F:+/−1.0° [C: +/−0.6°]) BLOCK OUTDOOR COIL: [sometimes necessary with lower temperatures] Use card ...

  • Lennox International Inc. CONDENSING UNITS - page 26

    Page 26 506645−01 ST ART : Measure outdoor ambient temperature NOTE − Do not attempt to charge system where a dash appears, system could be overcharged. Superheat is taken at suction line service port. Suction line superheat must never be less than 5ºF at the suction line service port. USE WEIGH-IN METHOD Weigh-in or remove refrigerant based u ...

  • Lennox International Inc. CONDENSING UNITS - page 27

    Page 27 14ACX SERIES T able 4. HFC−410A Normal Operating Pressures (Liquid +10 and Suction +5 psig) IMPORT ANT Use this t able to perform maintenance checks; it is not a procedur e for charging the system. Minor variations in these pressures may be due to differences in instal lations. Significant deviations could mean that the sy stem is not pro ...

  • Lennox International Inc. CONDENSING UNITS - page 28

    Page 28 506645−01 System Operation UNIT COMPONENTS IMPORT ANT Some scroll compressor have internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system is raised above 40 psig. DO NOT REPLACE COMPR ...

  • Lennox International Inc. CONDENSING UNITS - page 29

    Page 29 14ACX SERIES Indoor Unit 1. Clean or change filters. 2 . Lennox blower mot ors are prelubricat ed and permanent ly sealed. No more lubr ication is needed. 3 . Adjust blower speed for cooling. Meas ure the pressure drop over the coil to determ ine the corr ect blower CFM. Refer t o the u nit i nfor mat ion s ervic e manual f or p ressur e dr ...

  • Lennox International Inc. CONDENSING UNITS - page 30

    Page 30 506645−01 S tart−Up and Performance Checklist Job Name Job no. Date Job Location City S tate Installer City S tate Unit Model No. Serial No. Service T echnician Nameplate V olt age Rated Load Ampacity Compressor Outdoor Fan Maximum Fuse or Circuit Breaker Electrical Connections T ight?  Indoor Filter clean?  Supply V olt age (Unit ...

Fabbricante Lennox International Inc. Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoLennox International Inc. CONDENSING UNITS possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Lennox International Inc.
- manuali per l’uso CONDENSING UNITS
- schede prodotto Lennox International Inc.
- opuscoli
- o etichette energetiche Lennox International Inc. CONDENSING UNITS
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Lennox International Inc. CONDENSING UNITS.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Lennox International Inc. CONDENSING UNITS, manuali di manutenzione, brevi manuali o manuali utente Lennox International Inc. CONDENSING UNITS. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Lennox International Inc. CONDENSING UNITS.

Manuale completo del dispositivo Lennox International Inc. CONDENSING UNITS, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Lennox International Inc. CONDENSING UNITS dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Lennox International Inc. CONDENSING UNITS.

Il manuale per l’uso completo Lennox International Inc., dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Lennox International Inc. CONDENSING UNITS - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Lennox International Inc. CONDENSING UNITS, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Lennox International Inc. CONDENSING UNITS che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Lennox International Inc. CONDENSING UNITS - che ci dovrebbe aiutare nei primi passi durante l'uso Lennox International Inc. CONDENSING UNITS
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Lennox International Inc. CONDENSING UNITS
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Lennox International Inc. CONDENSING UNITS in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Lennox International Inc. CONDENSING UNITS?

Utilizza il modulo sottostante

Se non hai risolto il problema con Lennox International Inc. CONDENSING UNITS con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Lennox International Inc. CONDENSING UNITS è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)