    SSZ 14 SEER S plit System Heat Pump s • Refer to Service Manual RS6200005 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. • Models listed on page 3. RT6213005 Rev. 3 August 2010 Cop ...

  • Goodman Mfg SSZ 14 SEER - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause p ...

  • Goodman Mfg SSZ 14 SEER - page 3

    PRODUCT IDENTIFICA TION 3 The United States Environmental Protection Agency (“EPA”) has issued various regulations re- garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. These regulations may vary by ju ...

  • Goodman Mfg SSZ 14 SEER - page 4

    PRODUCT DESIGN 4 SSZ14 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet. These units are designed for ...

  • Goodman Mfg SSZ 14 SEER - page 5

    HEA T PUMP SPECIFICA TIONS 5 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...

  • Goodman Mfg SSZ 14 SEER - page 6

    HEA T PUMP SPECIFICA TIONS 6 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/ circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. S S Z 140181AF S S Z 140241AJ S S Z 140301AF S S Z 140361AH S S Z 140421AF S S Z 140481AF S S Z ...

  • Goodman Mfg SSZ 14 SEER - page 7

    7 COOLING PERFORMANCE DA T A SSZ140181A* EXP AN DE D PE RFORM ANCE DA T A C OOL I N G OP E R A TION M O DE L : S S Z 1 40181A* / CA*F 3131*6A* + TX V / M BR800** - 1 O ut door Am bi e nt Te m per at ure 65 75 8 5 95 105 115 E nter i ng I ndo or Wet B u lb Te m pe rat ure I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 ...

  • Goodman Mfg SSZ 14 SEER - page 8

    8 COOLING PERFORMANCE DA T A SSZ140181A* EXP AN DE D PERF O RM ANCE DA T A C OOL I N G OP E R ATION M O DE L : S S Z 1 40181A* / CA*F 3131* 6A* + T X V / M BR8 00**-1 O ut door Am bi e nt Tem pe ra ture 65 75 8 5 95 105 115 E nter i ng I ndoor W e t B u lb Te m pe rat ur e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 9 ...

  • Goodman Mfg SSZ 14 SEER - page 9

    9 COOLING PERFORMANCE DA T A SSZ140241A* EXPANDED PERF O RM ANCE DA T A C OOL I N G OP E R ATIO N M O DE L : S S Z 14 0241A* / CA*F3 636*6A*+ T X V / M B R800**-1 O utdoor Am bi e nt Te m pe r ature 65 75 85 95 105 1 15 E nte ring I ndoor We t B ulb Te m pe r ature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 ...

  • Goodman Mfg SSZ 14 SEER - page 10

    10 COOLING PERFORMANCE DA T A SSZ140241A* EX PANDED P ERF ORM ANCE DAT A C OOL IN G OP E R ATION M ODEL: S S Z 140241A* / CA*F3636*6A*+ T X V / M BR800**-1 O utdoor Am bi e nt Tem pe r ature 65 75 85 95 105 115 E nte r ing I ndoor We t B ul b Te m pe r ature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 15 96 3 ...

  • Goodman Mfg SSZ 14 SEER - page 11

    11 COOLING PERFORMANCE DA T A SSZ140301A* EXPA NDED PERFO RM ANC E DA T A C OOLI N G OP E R ATI O N M O D EL: S S Z 140301A* / CA*F 3642*6A*+T X V / M BR1600**- 1 O utdoo r Am bi e nt Te m pe ra ture 65 75 85 95 105 11 5 E nte r ing I ndoor We t B ul b Te m pe r a ture I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 96 ...

  • Goodman Mfg SSZ 14 SEER - page 12

    12 COOLING PERFORMANCE DA T A SSZ140301A* EX PANDED PERF O RM ANCE DAT A C O O L IN G O P E R A T IO N M O D EL: S S Z 140301A* / CA*F 3642*6A*+ TX V / M BR1600**-1 O utdoo r Am bi e nt T e m pe ra ture 65 75 85 95 105 115 E nte r i ng Indoo r We t B ul b Te m pe r at ure I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 ...

  • Goodman Mfg SSZ 14 SEER - page 13

    13 COOLING PERFORMANCE DA T A SSZ140361A* EXPA N DED PER FORM AN CE D ATA M ODEL: S S Z 140361A* / CA* F 4860*6A*+ TX V / M BR1600* *-1 O utdoo r Am bie nt Te m pe r a tur e 65 75 85 95 105 115 E n t e r in g In d o o r We t B u lb T e m pe r at u r e ID B Air flo w 5 9 63 67 71 59 6 3 67 71 59 63 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 M Bh 33. ...

  • Goodman Mfg SSZ 14 SEER - page 14

    14 COOLING PERFORMANCE DA T A SSZ140361A* EX PANDED PE RF O RM ANCE DATA C OOL IN G OP E R AT ION M ODEL: S S Z 140361A* / CA* F 4860*6A*+ TX V / M BR1600* *-1 O utdoor Am bie nt Te m pe r a tur e 65 75 85 95 105 115 E nter ing I nd oor Wet B u l b T e m pe r ature I D B * A i r f l o w 5 9 6 3 6 77 1 5 9 6 36 7 7 1 5 9 6 3 6 77 15 9 6 3 6 7 7 15 9 ...

  • Goodman Mfg SSZ 14 SEER - page 15

    15 COOLING PERFORMANCE DA T A SSZ140421A* EXPAN DED PERFORMAN CE DATA M ODEL : S S Z140421A* / CA*F 4860*6 A*+ T X V / M BR 2000**-1 O utdoor Am bi e n t Te m p e rature 65 75 85 95 105 115 E nte r ing I ndoo r We t B ulb Te m pe r atur e ID B A ir flo w 59 63 67 71 59 63 67 71 5 9 63 67 71 59 63 67 71 59 63 6 7 71 59 63 67 71 M Bh 39. 2 40.6 4 4.5 ...

  • Goodman Mfg SSZ 14 SEER - page 16

    16 COOLING PERFORMANCE DA T A SSZ140421A* EXPA NDED PER F O RM AN CE DA TA C OOL I N G OP E R AT I ON M O DE L : S S Z140421A* / CA*F 4860*6 A*+ TX V / M BR2000* *- 1 O u tdoor Am bi e n t Te m pe r ature 65 75 85 95 105 115 E nte r ing I ndoo r We t B ulb Te m pe r atur e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 15 ...

  • Goodman Mfg SSZ 14 SEER - page 17

    17 COOLING PERFORMANCE DA T A SSZ140481A* EXPA ND ED PER FOR M AN CE D ATA C OOL I N G OP E R ATIO N M O DEL: S S Z 14 0481A* / CA*F 4860*6A* + T X V / M BR20 00**-1 O u tdoor Am bi e n t Te m pe rature 65 75 85 95 105 115 E n te r ing Ind o o r We t Bulb T e m p e r at u r e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 7 7 ...

  • Goodman Mfg SSZ 14 SEER - page 18

    18 COOLING PERFORMANCE DA T A SSZ140481A* EXPA ND ED PER FO RM AN CE D ATA C OOLIN G OP E R AT I O N M O DEL: S S Z 14 0481A* / CA*F 4860* 6A*+ T X V / M BR2000* *-1 O utdoor Am bi e n t Te m pe rature 65 75 85 95 105 115 E n te r in g In d o o r W e t B u lb Te m p e r a t u r e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 9 6 3 6 77 15 9 6 3 6 ...

  • Goodman Mfg SSZ 14 SEER - page 19

    19 COOLING PERFORMANCE DA T A SSZ140601A* EXP AND E D PERF O RM A NCE DATA C OOL I N G OP E R ATION M O DE L: S S Z 140601 A* / CA*F4860*6 A*+ T X V / M BE2 000**- 1 O utdoor A m bi e nt Te m pe r a ture 65 75 8 5 95 105 115 E nter i ng I ndoor W e t B ul b Te m p e ra ture ID B Air flow 59 63 67 71 5 9 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 ...

  • Goodman Mfg SSZ 14 SEER - page 20

    20 COOLING PERFORMANCE DA T A SSZ140601A* EXP AND E D PERF ORM ANCE DAT A C OOL I N G OP E R ATION M ODEL: S S Z 140601A* / CA*F4860*6A *+ TX V / M BE 2000**- 1 O utd oor Am bi e nt Te m pe ra ture 65 75 8 5 95 105 115 E nter i ng I ndoor W e t B ul b Te m peratu r e I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 7 ...

  • Goodman Mfg SSZ 14 SEER - page 21

    21 PERFORMANCE DA T A Out door Temp. ° F . Total Btuh Sensible Btu h La te nt Btuh Total Wat ts 75° 36,330 24,713 11,617 2,662 80° 35,898 24,729 11,169 2,742 85° 35,465 24,738 10,727 2,822 90° 35,033 24,830 10,203 2,892 95° 34,600 24,912 9,688 2,963 100° 33,735 24,749 8,986 3,0 23 105° 32,870 24,563 8,307 3,0 83 110° 31,659 23,757 7,902 3, ...

  • Goodman Mfg SSZ 14 SEER - page 22

    22 EXPA NDED PERFORM A NCE DATA M ODEL: SSZ140361A * / CA*F4860C6A *+TXV / M BR1600**-1 HEATING O PERATION Outdoo r Ambient Tem p era ture 65 60 55 50 47 45 40 35 30 25 2 0 17 15 10 5 0 -5 -10 MBh 4 3.5 41.2 38.8 36.2 34.6 33.5 31 .1 28.7 28.8 26.6 24.5 23. 1 22 .3 20.0 17.7 1 5.5 13.2 10.8 Delta T 38.4 36.3 34.2 31.9 30.5 29. 6 27.5 25.3 2 5.4 23. ...

  • Goodman Mfg SSZ 14 SEER - page 23

    23 EXPANDED PERFORM ANCE DA TA MO DEL: SSZ140481A* / CA*F4860*6A *+TXV / MBR2000**-1 HEA T ING OPERATION Outdoor Ambie nt Temperat ure 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 - 5 -10 MBh 57.8 5 4.7 5 1.5 48. 2 46.0 4 4.6 41.4 38.2 36 .6 33.8 31.1 29. 4 28.3 25.4 22. 5 19.6 16.8 13. 7 D e l t a T 3 4 . 53 2 . 73 0 . 82 8 . 8 2 7 . 5 2 6 . 62 4 ...

  • Goodman Mfg SSZ 14 SEER - page 24

    24 HEA TING SPECIFICA TIONS capacit y btuh c.o.p. 4.8 9.6 1 4.4 19. 2 65 22.63 4.23 39.01 55.39 71.77 88.16 60 21.42 4.09 37.80 54.18 70.57 86.95 55 20.16 3.93 36.54 52.92 69.31 85.69 50 18.85 3.75 35.23 51.61 67.99 84.38 45 17.44 3.54 33.82 50.21 66.59 82.97 40 16.20 3.36 32.58 48.96 65.35 81.73 35 14.94 3.16 31.32 47.70 64.09 80.47 30 12.80 2.70 ...

  • Goodman Mfg SSZ 14 SEER - page 25

    25 HEA TING SPECIFICA TIONS capaci t y btuh c. o. p. 4 .8 9.6 14. 4 19. 2 65 51.5 4 4 .44 67 .92 84. 30 100. 68 117. 07 60 48.7 9 4 .28 65 .17 8 1. 55 97. 94 114. 32 55 45.9 2 4 .11 62 .30 7 8. 68 95. 07 111. 45 50 42.9 3 3 .92 59 .31 7 5. 69 92. 07 108. 46 45 39.7 3 3 .70 56 .11 7 2. 49 88. 88 105. 26 40 36.9 0 3 .50 53 .28 6 9. 66 86. 05 102. 43 ...

  • Goodman Mfg SSZ 14 SEER - page 26

    26 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...

  • Goodman Mfg SSZ 14 SEER - page 27

    WIRING DIAGRAMS 27 HIGH VOL T AGE! DIS CONNECT ALL POWER BEFORE SERVICING OR INST A LLIN G THIS UNIT . MUL T IPLE POW ER SOURCES MA Y BE PRESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAGE, PERSONAL I NJURY OR DEA TH . Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. SSZ140[18,30,42-60 ...

  • Goodman Mfg SSZ 14 SEER - page 28

    WIRING DIAGRAMS 28 HIGH VOL T A GE! DISCO NNECT A LL POWE R BEFORE SERVICI NG OR INS T A LLIN G THIS UNIT . M UL T IPLE POW ER SOURCES MA Y BE PRESENT . F AI LURE TO DO SO MA Y C AUS E PROP ERTY DAMAG E, PERSONAL I NJURY OR DE A TH . USE N.E .C. CL ASS 2 WI R E NOTES: 1) TO INDO OR UNI T LO W VOLT A GE TER M IN AL BLOC K & IN DO O R T H E R MO ...

Fabbricante Goodman Mfg Categoria Heat Pump

I documenti che otteniamo dal fabbricante del dispositivoGoodman Mfg SSZ 14 SEER possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Goodman Mfg
- manuali per l’uso SSZ 14 SEER
- schede prodotto Goodman Mfg
- opuscoli
- o etichette energetiche Goodman Mfg SSZ 14 SEER
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Goodman Mfg SSZ 14 SEER.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Goodman Mfg SSZ 14 SEER, manuali di manutenzione, brevi manuali o manuali utente Goodman Mfg SSZ 14 SEER. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Goodman Mfg SSZ 14 SEER.

Manuali per l’uso simili

Manuale completo del dispositivo Goodman Mfg SSZ 14 SEER, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Goodman Mfg SSZ 14 SEER dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Goodman Mfg SSZ 14 SEER.

Il manuale per l’uso completo Goodman Mfg, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Goodman Mfg SSZ 14 SEER - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Goodman Mfg SSZ 14 SEER, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Goodman Mfg SSZ 14 SEER che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Goodman Mfg SSZ 14 SEER - che ci dovrebbe aiutare nei primi passi durante l'uso Goodman Mfg SSZ 14 SEER
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Goodman Mfg SSZ 14 SEER
5. FAQ - domande più frequenti