Manuale per l’uso APC 2AP9604S

32 pagine 2.46 mb
Scarica

Vai alla pagina of 32

Summary
  • APC 2AP9604S - page 1

    APC Silcon 120-160kW400V UPS User Guide Copyright ©2001 APC Japan Information in this document is subject to change without notice and does not represent a commitment on the part of the vendor ...

  • APC 2AP9604S - page 2

    2 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Thank You Thank you for chosing APC Silcon. Please read this User Guide thoroughly prior to installing the system as it provides important information on safe and efficient installation and use. The installation and use of this product must comply with national, federal, state, municipal and local ...

  • APC 2AP9604S - page 3

    Introduction 990-4055 User Guide APC Silcon 120-160kW 400V UPS 3 1.0 Introduction This UPS system is designed to offer reliable and problem-free power supply for several years. The system requires only a minimum of maintenance, but we recommend you follow the maintenance guidelines described in section 6.0 Maintenance & Testing. 1.1 Display Uni ...

  • APC 2AP9604S - page 4

    4 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Stop/Start UPS and Operating the External Service Bypass 2.0 Stop/Start UPS and Operating the External Service Bypass Panel Only qualified electricians should start up or shut down APC Silcon UPS systems and instructions in the Installation Guide should be followed. Prior to being serviced, the AP ...

  • APC 2AP9604S - page 5

    Stop/Start UPS and Operating the External Service Bypass 990-4055 User Guide APC Silcon 120-160kW 400V UPS 5 2.3 Stop UPS (for complete power down) 2.3.1 Switching off the UPS CAUTION! If the UPS system is equipped with a Service Bypass Panel, and if the load must remain energized by mains, refer to the Operating Service Bypass Panel sections in th ...

  • APC 2AP9604S - page 6

    6 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Stop/Start UPS and Operating the External Service Bypass The UPS is now isolated. Maintenance/repair, disconnection or removal can now be carried out. 1. Open front doors 2. Note that step 3 will interrupt output v oltage and activate the alarm! The red LED alarm below the display will light up Th ...

  • APC 2AP9604S - page 7

    Stop/Start UPS and Operating the External Service Bypass 990-4055 User Guide APC Silcon 120-160kW 400V UPS 7 2.4 Start UPS (from complete power down) 2.4.1 UPS start-up CAUTION! Make sure all cable connections are in place prior to first start-up. NOTICE! After first system start-up, check that battery temperature is displayable (press and simultan ...

  • APC 2AP9604S - page 8

    8 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Stop/Start UPS and Operating the External Service Bypass System start-up now completed. NOTICE! One of the following display messages will appear by UPS start-up: • “ STD ” : Standard (single system) • “ PAR ” : Parallel System • “ ECO ” : Economy mode (single or parallel systems ...

  • APC 2AP9604S - page 9

    Stop/Start UPS and Operating the External Service Bypass 990-4055 User Guide APC Silcon 120-160kW 400V UPS 9 2.5 Operating the External Service Bypass Switch (single systems) 2.5.1 Bypassing the Single System UPS APC Silcon UPS Mains Load Service Bypass Switch Action 1. Press on the ke yboard 2. Press or on the ke yboard until 3. Press on the ke yb ...

  • APC 2AP9604S - page 10

    10 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Stop/Start UPS and Operating the External Service Bypass 2.5.2 Switching the Single System UPS from External Bypass into Normal UPS Operation CAUTION! Do not leave UPS out of service for more than 48 hours. Refer to section 2.3 Stop (for complete power down). APC Silcon UPS Load Service Bypass Sw ...

  • APC 2AP9604S - page 11

    Stop/Start UPS and Operating the External Service Bypass 990-4055 User Guide APC Silcon 120-160kW 400V UPS 11 NOTICE! If battery has been disconnected, please refer to section 2.4.1 UPS start-up. Action 1. Set the input s witch (Q001) to position 1 2. W ait 5 sec. Open the front door of the UPS and press the green ON k ey 3. Press on the k eyboard ...

  • APC 2AP9604S - page 12

    12 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Stop/Start UPS and Operating the External Service Bypass 2.6 Operating the External Service Bypass Switch (parallel systems) 2.6.1 Bypassing the Parallel UPS System (All UPSs) Service bypass switch Load Mains APC Silcon UPS APC Silcon UPS CAUTION! Do not leave UPS out of service for more than 48 ...

  • APC 2AP9604S - page 13

    Stop/Start UPS and Operating the External Service Bypass 990-4055 User Guide APC Silcon 120-160kW 400V UPS 13 Action Steps 1-4 apply to all the parallel systems. Note that this will switch all systems into bypass oper ation 1. Press on the ke yboard 2. Press or on the ke yboard until 3. Press on the ke yboard 4. Press on the ke yboard All systems s ...

  • APC 2AP9604S - page 14

    14 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Stop/Start UPS and Operating the External Service Bypass 2.6.2 Switching the Parallel System from External Bypass into Normal UPS Operation NOTICE! If battery has been disconnected, please refer to section 2.4.1 UPS start-up. Service bypass switch Load Mains APC Silcon UPS APC Silcon UPS ...

  • APC 2AP9604S - page 15

    Stop/Start UPS and Operating the External Service Bypass 990-4055 User Guide APC Silcon 120-160kW 400V UPS 15 Action 1. Check that the output s witch (Q004) is set to position 0 2. Check that all output s witches (Q002) are set to position 1 3. Set input switches (Q001) to position 1 4. W ait 10 secs. Open the UPS front door and press the green ON ...

  • APC 2AP9604S - page 16

    16 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Stop/Start UPS and Operating the External Service Bypass 2.7 Isolating one UPS in a Parallel Configuration for Service/Maintenance 2.7.1 Isolating one UPS in a Parallel/Redundant System In a redundant system one UPS may be isolated for service/maintenance without affecting other parallel UPS(s). ...

  • APC 2AP9604S - page 17

    Stop/Start UPS and Operating the External Service Bypass 990-4055 User Guide APC Silcon 120-160kW 400V UPS 17 NOTICE! With Q002 in position 0, the UPS can be operated and tested as a single system without affecting the other parallel UPS(s) if correct monitoring device has been installed. Applicable to all bypass panels. ...

  • APC 2AP9604S - page 18

    18 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Operation 3.0 Operation The display unit will read parameters, alarms/messages and measured values. LED alarm incorporates audible alarm, indicating unusual operating situations. The keyboard is used to program and control parameters and to display alarm messages and measured values. 3.1 Keyboard ...

  • APC 2AP9604S - page 19

    Operation 990-4055 User Guide APC Silcon 120-160kW 400V UPS 19 3.2 Display of Measured Values To read measurements, press one or two keys simultaneously as shown below. (Illustrated values are examples only). 3.3 Using the Remote Display The remote display is an inactive unit that is unable to influence the operation of the APC Silcon UPS. It is im ...

  • APC 2AP9604S - page 20

    20 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Operation 3.4 Economy Mode When the UPS is running in Economy Mode, the load will be supplied directly from mains and output voltages are UPS monitored. In the event of a mains disruption, the UPS will switch to battery mode without affecting the load. Prior to switching to bypass mode, leave the ...

  • APC 2AP9604S - page 21

    Parameter Settings 990-4055 User Guide APC Silcon 120-160kW 400V UPS 21 4.0 Parameter Settings Below tables show operating parameters programmable from keyboard. Only qualified users should alter programming parameters. See below examples. Parameter Settings * Factory settings in bold ** For systems with active Battery Monitor only *** Do not leave ...

  • APC 2AP9604S - page 22

    22 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Parameter Settings 4.1 Programming Keys 4.2 Switching to Bypass Operation Programming Example Scrolls up through list Scrolls down through list Stores parameters/enters parameter stack Silences the audible alarm Chooses or changes parameters Displays time Return to normal window Accesses the alar ...

  • APC 2AP9604S - page 23

    Parameter Settings 990-4055 User Guide APC Silcon 120-160kW 400V UPS 23 To return to normal operation Follow same procedure to program other parameters. Action 6. Press to enter parameter stac k 7. Press or until 8. Press until 9. Press to store 10. Press to exit Display sho ws Bypass operation : YES Bypass operation : N O Normal operation load pow ...

  • APC 2AP9604S - page 24

    24 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Alarms and Events 5.0 Alarms and Events Alarms are indicated by the red lamp (above the left hand corner of the keyboard) and a 30 seconds acoustic signal. An alarm is registered in the alarm stack as long as it is present, and if more in the same order as they arise. Certain alarms, such as batt ...

  • APC 2AP9604S - page 25

    Alarms and Events 990-4055 User Guide APC Silcon 120-160kW 400V UPS 25 5.3 Possible Alarms Alarms Description Action 1. Peak current limiter active Peak current limiter activated and UPS switched to bypass operation. System overload Check for blown fuses in installation 2. Bypass power supply fault Fault in redundant PSU for bypass. UPS still 100% ...

  • APC 2AP9604S - page 26

    26 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Alarms and Events Alarms Description Action 23. Main inverter failure Temperature of main inverter, too high or inverter fuse blown Check fan, check for airflow obstructions, check for overload, check fuse 24. High temperature of delta inverter Temperature of delta inverter, too high Check fan, c ...

  • APC 2AP9604S - page 27

    Alarms and Events 990-4055 User Guide APC Silcon 120-160kW 400V UPS 27 5.4 Rectifying Alarm Messages Following actions may rectify alarm: • Check local mains supply. Fuses may be blown or supply switched off accidentally • Check if UPS cooling air intake is blocked • Check if load exceeds maximum output capacity • If, with mains power switc ...

  • APC 2AP9604S - page 28

    28 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Maintenance & Testing 6.0 Maintenance & Testing UPS maintenance should be carried out by trained service engineers only. Service and maintenance contract is recommended. 6.1 Fan It is recommended to replace fans every 3 years. 6.2 Battery Monitoring Test Systems with built-in batteries ha ...

  • APC 2AP9604S - page 29

    Maintenance & Testing 990-4055 User Guide APC Silcon 120-160kW 400V UPS 29 If the UPS is to be taken out of operation for an extended period, disconnect the battery in order to prevent discharging. For details, refer to Installation Guide. Action 1. Press 2. Press or until 3. Press 4. Press 5. W ait about 1 sec. 6. W ait until backup times e xp ...

  • APC 2AP9604S - page 30

    30 User Guide APC Silcon 120-160kW 400V UPS 990-4055 Warranty 7.0 Warranty 7.1 APC Silcon UPS Limited Factory Warranty APC warrants that the unit, when properly installed and commissioned by APC or APC authorized service personnel, shall be free from defects in materials and workmanship for a period of (1) year from the date of installation or maxi ...

  • APC 2AP9604S - page 31

    How to Contact APC 990-4055 User Guide APC Silcon 120-160kW 400V UPS 31 8.0 How to Contact APC APC Corporate 132 Fairgrounds Road West Kingston, RI 02892 USA Telephone: 401 789-5735 Fax: 401 789-3710 PowerFax™: 800 347-FAXX Pre-sales Technical Support 877-474-5266 (1-877-4Silcon) Post-sales Technical Support 877-287-7835 (1-877-2UPS-TEK) E-mail: ...

  • APC 2AP9604S - page 32

    32 User Guide APC Silcon 120-160kW 400V UPS 990-4055 How to Contact APC ...

Fabbricante APC Categoria Power Supply

I documenti che otteniamo dal fabbricante del dispositivoAPC 2AP9604S possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici APC
- manuali per l’uso 2AP9604S
- schede prodotto APC
- opuscoli
- o etichette energetiche APC 2AP9604S
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso APC 2AP9604S.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione APC 2AP9604S, manuali di manutenzione, brevi manuali o manuali utente APC 2AP9604S. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto APC 2AP9604S.

Manuali per l’uso simili

Manuale completo del dispositivo APC 2AP9604S, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare APC 2AP9604S dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti APC 2AP9604S.

Il manuale per l’uso completo APC, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale APC 2AP9604S - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice APC 2AP9604S, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per APC 2AP9604S che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo APC 2AP9604S - che ci dovrebbe aiutare nei primi passi durante l'uso APC 2AP9604S
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del APC 2AP9604S
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio APC 2AP9604S in un dato paese, se il problema non può essere risolto da noi stessi.