    SSZ 16 SEER S plit System Heat Pumps • Refer to Service Manual RS6200005 for installation, op- eration, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. RT6214002 Rev. 2 September 2007 TECHNICAL INFORMA TION MANUA ...

  • Goodman Mfg SSZ160601A - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to d ...

  • Goodman Mfg SSZ160601A - page 3

    PRODUCT IDENTIFICA TION 3 WARNING WARNING WARNING WARNING To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance. Do not connect or use any device that is not design certified by Goodman for use with this unit. Serio ...

  • Goodman Mfg SSZ160601A - page 4

    PRODUCT DESIGN 4 SSZ16 models are available in 2, 3, 4 and 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet. These units are designed for f ...

  • Goodman Mfg SSZ160601A - page 5

    HEA T PUMP SPECIFICA TIONS 5 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...

  • Goodman Mfg SSZ160601A - page 6

    6 COOLING PERFORMANCE DA T A SSZ160241A* EXPA NDED PERFORMA NCE DA TA COOLIN G OPERA TION MO DE L: SSZ160241A* / CA *F3636 *6A * + TXV / MBE1600* *- 1 Design Sub cooling 7 ± 2 °F @ the liqui d ser vice valv e, A RI 95 test con di tions Outd oor A mbient Temper atur e 65 75 85 95 105 115 Ente ring Indo or W et Bulb Tem pera ture IDB A i rflow 59 6 ...

  • Goodman Mfg SSZ160601A - page 7

    7 COOLING PERFORMANCE DA T A SSZ160241A* EXPA NDED PERFO RMA NCE DA T A COOLI NG O PERATI ON MODEL: SSZ160 24 1A* / CA *F3636* 6A * + TXV / MBE1600* *-1 Design S ubco oling 7 ± 2 °F @ the liquid service valve, A RI 95 test condi ti ons Outdoor Ambient Tempera ture 65 75 85 95 105 115 Entering I ndoor W et Bulb Temperature I D B * A i r f l o w 5 ...

  • Goodman Mfg SSZ160601A - page 8

    8 COOLING PERFORMANCE DA T A EXPA NDED PERFORM A NCE DA TA COOLI NG O PERATI ON MODEL: SSZ160361A * / CA*F4860*6A * + TXV / MBE2000**- 1 Design Subcooling 9 ± 3 °F @ the liqui d service valve, A RI 95 test condit i ons Outdoo r Ambient Temperat u re 65 75 85 95 105 115 Ente ring Indoo r Wet Bulb Tempe rature IDB A ir flow 59 63 67 71 59 6 3 67 71 ...

  • Goodman Mfg SSZ160601A - page 9

    9 COOLING PERFORMANCE DA T A EXPA NDED PERFORM A NCE DA TA COOLI NG O PERATI ON MODEL: SSZ160361A * / CA*F4860*6A * + TXV / M BE2000**-1 Design Subcooli ng 9 ±3 °F @ the liqu id servi ce valve, A RI 95 test condit i ons Outdoo r Ambient Temperat u re 65 75 85 95 105 115 Ente ring Indoo r Wet Bulb Tempe rature I D B * A i r f l o w 5 9 6 3 6 77 1 ...

  • Goodman Mfg SSZ160601A - page 10

    10 COOLING PERFORMANCE DA T A SSZ160481A* EXPANDED PERFORMANCE DA TA COOLIN G OPERA TION M ODEL: SSZ160481A * / CA* F4860*6A * + TXV / MBE200 0**-1 Design Su bcoolin g 7 ± 2 ° F @ t he liqu id service valv e, A RI 95 test condi tion s Outdoor Ambient Temper ature 65 75 85 95 105 115 Ente ring Indo or W et Bulb T emperat ure I D B * A i r f l o w ...

  • Goodman Mfg SSZ160601A - page 11

    11 COOLING PERFORMANCE DA T A SSZ160481A* EXPANDED PERFORMANCE DA TA COOLIN G OPERA TION M ODEL: SSZ160481A* / CA*F4860*6A * + TXV / MBE2000**- 1 Design Su bcooling 7 ± 2 ° F @ the liquid service valve, A R I 95 test condi tion s Outdoor Ambient Temperature 65 75 85 95 105 115 Ente ring Indo or Wet Bulb T empera ture I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg SSZ160601A - page 12

    12 COOLING PERFORMANCE DA T A SSZ160601A* EXPA NDED PERFORMANCE DA TA COOLING OP ERA TIO N MODEL: SSZ160601A* / CA *F 4860*6A* + T XV / MBE2000**-1 Design Subcool in g 7 ± 2 °F @ the liquid service valve, ARI 95 test condi tions Outdoor Ambient Temperature 65 75 85 95 105 115 Enter ing In door W et Bulb Tem perature I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg SSZ160601A - page 13

    13 COOLING PERFORMANCE DA T A SSZ160601A* EXPA NDED PERFORMANCE DA TA COOLIN G OPERATION MODEL: SSZ160601A* / CA *F 4860*6A* + T XV / MBE2000**-1 Design Subcool in g 7 ± 2 °F @ the liquid service valv e, A RI 95 test condi tions Outdoor Ambient Temperature 65 75 85 95 105 115 Enter ing In door W et Bulb Tem perature I D B * A i r f l o w 5 96 36 ...

  • Goodman Mfg SSZ160601A - page 14

    14 PERFORMANCE DA T A Outdoor Temp. ° F. Total Btuh Sensible Btuh Laten t Btuh Total Watts 75° 25,200 18,540 6,660 1,645 80° 24,900 18,553 6,347 1,697 85° 24,600 18,559 6,041 1,749 90° 24,300 18,628 5,672 1,795 95° 24,000 18,690 5,310 1,841 100° 23,400 18, 568 4,832 1,880 105° 22,800 18, 428 4,372 1,919 110° 21,960 17, 824 4,136 1,952 115? ...

  • Goodman Mfg SSZ160601A - page 15

    15 SPLIT SYSTEM HEA TING PERFORMANCE High pres sure is m easured a t the liquid service valve (the smaller valve). AMPS = Outdoor un it am ps (comp. +fan) Low pressure is mea sured at t he gauge port connecti on. KW = Total system power Calculat ions ar e based on n ominal CFM and 70 ° F indoor d ry bulb. *Note: Shaded area is ARI Rating Condition ...

  • Goodman Mfg SSZ160601A - page 16

    16 HEA TING SPECIFICA TIONS *To obtain BTU capacity of unit with KW of auxiliary heat, multiply by 1000 (Example: 39.01 x 1000 = 39,010 BTU) capacit y btuh c.o. p. 4.8 9. 6 14.4 19.2 65 30.17 4.93 46.55 62.93 79.32 95.70 60 28.56 4.76 44.94 61.32 77.71 94.09 55 26.88 4.57 43.26 59.64 76.03 92.41 50 25.13 4.37 41.51 57.89 74.28 90.66 45 23.26 4.13 3 ...

  • Goodman Mfg SSZ160601A - page 17

    17 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...

  • Goodman Mfg SSZ160601A - page 18

    WIRING DIAGRAMS 18 WA RNI NG HIGH V OLTAGE! DISCONNECT AL L POWER BEFO RE SERVICING OR INST ALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERT Y DAMAGE, P ERSONAL INJURY O R DEATH. Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. SSZ160[24-48]1A* COM ...

  • Goodman Mfg SSZ160601A - page 19

    WIRING DIAGRAMS 19 WA RNI NG HIGH V OLTAGE! DISCONNECT AL L POWER BEFO RE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERT Y DAMAGE, P ERSONAL INJURY O R DEATH. SSZ160[60]1AA U S E N.E. C . CL A SS 2 WIRE N O TE S : 1) T O IND OO R UNIT LO W V OL TAGE TER M INA L B LOC K & IND OO R T H ...

  • Goodman Mfg SSZ160601A - page 20

    WIRING DIAGRAMS 20 WA RNI NG HIGH V OLTAGE! DISCONNECT AL L POWER BEFO RE SERVICING OR INST ALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERT Y DAMAGE, P ERSONAL INJURY O R DEATH. SSZ160[60]1AB/AC Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. USE ...

Fabbricante Goodman Mfg Categoria Heat Pump

I documenti che otteniamo dal fabbricante del dispositivoGoodman Mfg SSZ160601A possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Goodman Mfg
- manuali per l’uso SSZ160601A
- schede prodotto Goodman Mfg
- opuscoli
- o etichette energetiche Goodman Mfg SSZ160601A
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Goodman Mfg SSZ160601A.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Goodman Mfg SSZ160601A, manuali di manutenzione, brevi manuali o manuali utente Goodman Mfg SSZ160601A. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Goodman Mfg SSZ160601A.

Manuale completo del dispositivo Goodman Mfg SSZ160601A, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Goodman Mfg SSZ160601A dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Goodman Mfg SSZ160601A.

Il manuale per l’uso completo Goodman Mfg, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Goodman Mfg SSZ160601A - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Goodman Mfg SSZ160601A, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Goodman Mfg SSZ160601A che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Goodman Mfg SSZ160601A - che ci dovrebbe aiutare nei primi passi durante l'uso Goodman Mfg SSZ160601A
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Goodman Mfg SSZ160601A
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Goodman Mfg SSZ160601A in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Goodman Mfg SSZ160601A?

Utilizza il modulo sottostante

Se non hai risolto il problema con Goodman Mfg SSZ160601A con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Goodman Mfg SSZ160601A è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)