Manuale per l’uso Carrier 38AKS013-024

24 pagine 0.52 mb
Scarica

Vai alla pagina of 24

Summary
  • Carrier 38AKS013-024 - page 1

    Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS ...................1 INST ALLA TION ............................. 1-12 Step 1 — Complete Pre-Installation Checks ....................................1 Step 2 — Rig and Mount the Unit .............8 Step 3 — Complete Refrigerant Piping Connections ............ ...

  • Carrier 38AKS013-024 - page 2

    NOTE: Service areas — Allow 3 ft (914 mm) on both sides and 2 ft (610 mm) on both ends of unit for servicing. Fig. 1 — Dimensions 2 ...

  • Carrier 38AKS013-024 - page 3

    13 2 4567 8 12 9 10 11 LEGEND 1— No. 1 Fan 5— No. 2 Fan 9— Compressor 2— High-Pressure Switch 6— T erminal Block 1 (Unit Power) 1 0— Low-Pressure Switch 3— Circuit Breaker — Control Circuit 7— T erminal Block 2 (Control Power) 11 — Hot Gas Bypass Piping Stub ( 3 ⁄ 8 -in. ODM) 4— Circuit Breakers — Power Circuits 8— W rap ...

  • Carrier 38AKS013-024 - page 4

    T able 1A — Physical Data (English, 60 Hz) UNIT 38AKS 013 014 016 024 OPERA TING WEIGHT (lb) With Aluminum-Fin Coil 732 779 789 900 With Copper-Fin Coil 825 919 929 1040 REFRIGERANT* R-22 Shipping Charge (lb) 2.1 3.1 3.1 3.1 Operating Charge, T ypical (lb)† 22 23 23 28 COMPRESSOR Reciprocating, Semi-Hermetic Model 06DD824 06DD328 06DD537 06EA25 ...

  • Carrier 38AKS013-024 - page 5

    T able 1B — Physical Data (SI, 60 Hz) UNIT 38AKS 013 014 016 024 OPERA TING WEIGHT (kg) With Aluminum-Fin Coil 332 353 358 408 With Copper-Fin Coil 374 417 421 472 REFRIGERANT* R-22 Shipping Charge (kg) 0.95 1.40 1.40 1.40 Operating Charge, T ypical (kg)† 10.0 10.4 10.4 12.7 COMPRESSOR Reciprocating, Semi-Hermetic Model 06DD824 06DD328 06DD537 ...

  • Carrier 38AKS013-024 - page 6

    T able 1C — Physical Data (English, 50 Hz) UNIT 38AKS 013 014 016 024 OPERA TING WEIGHT (lb) With Aluminum-Fin Coil 732 779 789 900 With Copper-Fin Coil 825 919 929 1040 REFRIGERANT* R-22 Shipping Charge (lb) 2.1 3.1 3.1 3.1 Operating Charge, T ypical (lb)† 22 23 23 28 COMPRESSOR Reciprocating, Semi-Hermetic Model 06DD824 06DD328 06DD537 06EA25 ...

  • Carrier 38AKS013-024 - page 7

    T able 1D — Physical Data (SI, 50 Hz) UNIT 38AKS 013 014 016 024 OPERA TING WEIGHT (kg) With Aluminum-Fin Coil 332 353 358 408 With Copper-Fin Coil 374 417 421 472 REFRIGERANT* R-22 Shipping Charge (kg) 0.95 1.40 1.40 1.40 Operating Charge, T ypical (kg)† 10.0 10.4 10.4 12.7 COMPRESSOR Reciprocating, Semi-Hermetic Model 06DD824 06DD328 06DD537 ...

  • Carrier 38AKS013-024 - page 8

    Step 2 — Rig and Mount the Unit Be sure unit panels are securely in place prior to rigging. RIGGING — These units are designed for overhead rigging only . For this purpose, the transverse base channels extend beyond the sides of the unit, with holes provided in the end plates to attach cables or hooks. Rig with top skid packaging assembly in pl ...

  • Carrier 38AKS013-024 - page 9

    T able 4A — Refrigerant Piping Sizes — 60 Hz Units UNIT 38AKS LENGTH OF INTERCONNECTING PIPING, FT (M) 0-15 (0-4.5) 15-25 (4.5-7.5) 25-50 (7.5-15) 50-75 (15-23) 75-100 (23-30) Line Size (in. OD) L S L SLS LSLS 013 1 ⁄ 2 1 1 ⁄ 8 1 ⁄ 2 1 1 ⁄ 8 5 ⁄ 8 1 3 ⁄ 8 5 ⁄ 8 1 3 ⁄ 8 5 ⁄ 8 1 5 ⁄ 8 * 014 1 ⁄ 2 1 1 ⁄ 8 1 ⁄ 2 1 3 ⁄ 8 ...

  • Carrier 38AKS013-024 - page 10

    INST ALL FIL TER DRIER(S) AND MOISTURE INDICA- TOR(S) — Every unit should have a filter drier and liquid- moisture indicator (sight glass). In some applications, depending on space and convenience requirements, it may be desirable to install 2 filter driers and sight glasses. One filter drier and sight glass may be installed at A locations in ...

  • Carrier 38AKS013-024 - page 11

    T able 6A — Electrical Data (3 Ph/60 Hz) UNIT 38AKS UNIT COMPR F AN MOT ORS (Single Phase) Model V olts MCA ICF MOCP (Fuse Only) RLA LRA T otal Fans FLA (ea) Fan No. kW Nameplate Supplied* Min Max 1 2 013 501 208-230 187 253 62.5 178 100 43.6 170 2 4.3 3.7 1.41 201 380 342 418 35.0 101 50 24.0 93 4.3 3.7 601 460 414 528 29.1 81 40 20.0 77 2.3 1.9 ...

  • Carrier 38AKS013-024 - page 12

    T able 6B — Electrical Data (3 Ph/50 Hz) UNIT 38AKS UNIT COMPR F AN MOT ORS 230 v (Single Phase) Model V olts MCA ICF MOCP (Fuse Only) RLA LRA T otal Fans FLA (ea) Fan No. kW Nameplate Supplied* Min Max 1 2 013 803 230 198 264 47.5 134 75 32.9 128 2 2.9 3.5 1.20 903 400 342 457 31.4 80 50 20.0 74 014 803 230 198 264 51.0 149 75 35.7 143 2 2.9 3.5 ...

  • Carrier 38AKS013-024 - page 13

    ST ART -UP Compressor crankcase heater must be on for 24 hours before start-up. After the heater has been on for 24 hours, the unit can be started. If no time has elapsed since the pre- liminary charge step has been completed, it is unnecessary to wait the 24-hour period. Preliminary Checks 1. Ensure that compressor service valves are backseated. 2 ...

  • Carrier 38AKS013-024 - page 14

    Fig. 10 — 38AKS013 and 38AKS024 Charging Chart 14 ...

  • Carrier 38AKS013-024 - page 15

    Fig. 1 1 — 38AKS014 Charging Chart 15 ...

  • Carrier 38AKS013-024 - page 16

    Fig. 12 — 38AKS016 Charging Chart 16 ...

  • Carrier 38AKS013-024 - page 17

    OPERA TING SEQUENCE Cooling — When the first stage (TC1) of the cooling ther- mostat closes, the timer starts. After approximately 3 seconds, the timer expires, energizing the compressor and fan motor no. 1. When the liquid pressure builds to approxi- mately 257 psig (1772 kPa), fan motor no. 2 is energized. On demand for additional cooling capa ...

  • Carrier 38AKS013-024 - page 18

    Winter Start Control (If Required) — Install Ac- cessory Package 38AE900021. Crankcase Heater — The heater prevents refrigerant migration and compressor oil dilution during shutdown when- ever compressor is not operating. It is wired to cycle with the compressor; the heater is of f when compressor is run- ning, and on when compressor is of f. B ...

  • Carrier 38AKS013-024 - page 19

    Fig. 15 — Outdoor Fan Fig. 16 — Pivot and Support T op Cover Fig. 17 — Coil Cleaning (T ypical) 19 ...

  • Carrier 38AKS013-024 - page 20

    TROUBLESHOOTING PROBLEM SOLUTION COMPRESSOR DOES NOT RUN Contactor Open 1. Power off. 1. Restore power . 2. Fuses blown in field power circuit. 2. After finding cause and correcting, replace with correct size fuse. 3. No control power . 3. Check control circuit breaker; reset if tripped or replace if defective. 4. Thermostat circuit open. 4. Chec ...

  • Carrier 38AKS013-024 - page 21

    TROUBLESHOOTING (cont) PROBLEM SOLUTION COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH (cont) Airflow Restricted 1. Coil iced up. 1. Check refrigerant charge. 2. Coil dirty . 2. Clean coil fins. 3. Air filters dirty . 3. Clean or replace filters. 4. Dampers closed. 4. Check damper operation and position. Indoor-Air Fan Stopped 1. Electrical connectio ...

  • Carrier 38AKS013-024 - page 22

    Copyright 1998 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 Ta b 3 a 2 a PC 1 1 1 Catalog No. 563-701 Printed in U.S.A. Form 38AKS-3SI Pg 22 9-98 Replaces: 38AKS-2SI ...

  • Carrier 38AKS013-024 - page 23

    ST ART -UP CHECKLIST A. Preliminary Information OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES B. Pre-Start-Up OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y . DOES IT AGREE WITH UNIT? (Y/N) HAS THE GROUND ...

  • Carrier 38AKS013-024 - page 24

    C. Start-Up CHECK INDOOR UNIT F AN SPEED AND RECORD. CHECK OUTDOOR UNIT F AN SPEED AND RECORD. AFTER A T LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING OUTDOOR UNIT AIR TEMP LEA VING OUTDOOR UNIT AIR TEMP INDOOR UNIT ENTERING-AIR DB (d ...

Fabbricante Carrier Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoCarrier 38AKS013-024 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Carrier
- manuali per l’uso 38AKS013-024
- schede prodotto Carrier
- opuscoli
- o etichette energetiche Carrier 38AKS013-024
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Carrier 38AKS013-024.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Carrier 38AKS013-024, manuali di manutenzione, brevi manuali o manuali utente Carrier 38AKS013-024. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Carrier 38AKS013-024.

Manuale completo del dispositivo Carrier 38AKS013-024, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Carrier 38AKS013-024 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Carrier 38AKS013-024.

Il manuale per l’uso completo Carrier, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Carrier 38AKS013-024 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Carrier 38AKS013-024, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Carrier 38AKS013-024 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Carrier 38AKS013-024 - che ci dovrebbe aiutare nei primi passi durante l'uso Carrier 38AKS013-024
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Carrier 38AKS013-024
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Carrier 38AKS013-024 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Carrier 38AKS013-024?

Utilizza il modulo sottostante

Se non hai risolto il problema con Carrier 38AKS013-024 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Carrier 38AKS013-024 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)