    Quick Start Guide 00825-0100-4007, Rev CB February 2015 Note Bef ore installin g the transmitt er , con firm the c orrect Devic e Drive r is loaded on the host systems. See page 3 for Syst em R eadine ss. R osemount 3051 Pressure T ransmitt er and R osemount 3051CF Series Flowmet ers with 4-20 mA HART ® Re vision 5 and 7 prot ocol ...

  • Emerson Process Management 3051 - page 2

    February 2015 2 Quick Start Guide NO TICE This guide provi des basic guide lines f or Rose mount 305 1 T ransmitters. It doe s not provide instructions for con figuration, diagnostics, m ainte nance , service , troublesh ooting, Explo sion-proof , Flameproof , or intrinsically sa fe (I.S.) inst alla tions. Ref er to the R osemount 3051 HA RT 7 Re f ...

  • Emerson Process Management 3051 - page 3

    Quick Start Guide 3 February 2015 System re adiness Confirm HART R evision capability  If using HART based control or asset management systems, please confirm the HART capability of those systems prior to transmitte r instal lation. Not all systems are capa ble of communicating with HART Revision 7 pro tocol. This transmitter can be configured f ...

  • Emerson Process Management 3051 - page 4

    February 2015 4 Quick Start Guide T ransmitt er installation St ep 1: Mount the transmitter Liquid applications Coplanar In-line 1. Plac e taps t o the side o f the line . 2. Mount besid e or below th e taps. 3. Mount the transmitter so that the drain/vent valves are oriented up ward. Ga s applications 1. Plac e taps in the top or side of the line. ...

  • Emerson Process Management 3051 - page 5

    Quick Start Guide 5 February 2015 Figure 1. Panel and P ipe Mounting Panel m ount (1) 1. 1. 5 / 16 ⫻ 1 1 / 2 Panel Bolts are cu stomer supp lied. Pipe mount Coplanar fl ange T raditional f lange Rosemount 3051T ...

  • Emerson Process Management 3051 - page 6

    February 2015 6 Quick Start Guide Bolting consider ations If the transmi tter installation re quires assembly of th e process flanges, ma nifolds, or flange adapt ers, follow the assembly guide lines to ensure a tight seal for optimal performa nce characteris tics of the transmit ters. Use only bolts su pplied with the transm itter or sold by Emers ...

  • Emerson Process Management 3051 - page 7

    Quick Start Guide 7 February 2015 In-line gage transmitt er orientation The low side pressure port (atmospher ic refere nce) on the in-line gage transmitter is located in the neck of t he transmitter, behind the housing. The vent path is 360° arou nd the transmitter bet ween the housi ng and sensor. (See Figur e 3 .) Keep the vent pa th free of an ...

  • Emerson Process Management 3051 - page 8

    February 2015 8 Quick Start Guide St ep 2: Consider housing rotation To improve field ac cess to wiring or to better view the optional L CD display: 1. Loosen the housing rotati on set scre w using a 5/64-in. hex wre nch. 2. T ur n the housing lef t or right maximum up to 18 0° from its o riginal position (1) . Please note that over rot ati ng c a ...

  • Emerson Process Management 3051 - page 9

    Quick Start Guide 9 February 2015 Figure 5. T ransmitter Electronics Board A. A l ar m B. Security St ep 4: Connec t the wiring and power up Figure 6. T ransmitter Wiring Diagrams (4–20 mA) A. 24 Vdc supply B. R L ≥ 250 C. Current Meter (Optional) Shielded twiste d pair cable should be used for best resu lts. Use 24 AWG or larger wire that does ...

  • Emerson Process Management 3051 - page 10

    February 2015 10 Quick Start Guide 3. Ground hou sing t o fulfill local grounding regu lation s. 4. Ensure prope r grounding . It is important that the instrume nt cable shield : a. Be trimmed close and insulated from touching the transmitter hou sing b. Be c onnec ted to the next shield if cable is routed through a junction box c. Be connec ted to ...

  • Emerson Process Management 3051 - page 11

    Quick Start Guide 11 February 2015 St ep 5: V erif y configur ation Verify the config uration using any HA RT capable c onfiguration tool or Local Operator Interface ( LOI) - option code M4. Confi guration instructions for a Field Communicator and LOI are incl uded in this step. See Rosemount 3051 reference manual (008 09-0100-4007) for con figurat ...

  • Emerson Process Management 3051 - page 12

    February 2015 12 Quick Start Guide V erif ying co nfigura tion with Local Ope rat or Int erface (L OI) The optional LO I can be used for commission ing the device. The LOI is a two button design with internal and external bu ttons. The internal buttons a re located on the display o f the transmitter, while the extern al buttons are loca ted underne ...

  • Emerson Process Management 3051 - page 13

    Quick Start Guide 13 February 2015 Note See Figure 10 on page 15 to confirm E xternal Bu tton F unctionality . Figure 9. LOI Menu Swit ch HAR T revision mode If the HART configurat ion tool is not capa ble of communic ating with HART Revision 7, the 305 1 will load a generic men u with limited cap ability. The following procedures will switch the H ...

  • Emerson Process Management 3051 - page 14

    February 2015 14 Quick Start Guide St ep 6: T rim the transmitter Devices are calibra ted by the factory. Once in stalled, it is recommended to perform a zero trim on g age and differentia l pressure transmitters to el iminate error due to mounting position or static pressure effe cts. A zero trim can be performed using e ither a Field Commu nicato ...

  • Emerson Process Management 3051 - page 15

    Quick Start Guide 15 February 2015 T rimming with configuration buttons A zero trim is to be perform ed using one of the three possib le sets of external configuration butto ns located under the top tag. To access the con figuration butt ons, loosen the screw a nd slide the ta g on the top of the transmitter. Confirm the fun ctionality using Figure ...

  • Emerson Process Management 3051 - page 16

    February 2015 16 Quick Start Guide Safet y instrum ented systems installation For Safety Certified in stallations, re fer to product manua l (00809-0100- 4007) for installation procedure a nd system requirements. ...

  • Emerson Process Management 3051 - page 17

    Quick Start Guide 17 February 2015 Produc t Cer tific ations European Direc tive Information A copy of the EC Declarat ion of Conformity can be fou nd at the end of the Quick Start Guide. The most recent revision of the EC Declar ation of Conformity can be found at www.rosemount.com. O rd in ary Lo ca ti on Ce rti fi c ation from FM Approvals As st ...

  • Emerson Process Management 3051 - page 18

    February 2015 18 Quick Start Guide Europe E8 A TE X Flameproof and Du st Certificate: KEMA00A TE X2013X; Baseefa11A TE X0275X Standar ds: EN60079-0:2012, E N60079-1:2007, EN6007 9-26:2007, EN60079-31:2009 Marking s: II 1/2 G Ex d IIC T6/T5 Ga /Gb, T6(- 50 °C ≤ T a ≤ +65 °C), T5(-50 °C ≤ T a ≤ +80 °C); II 1 D Ex ta IIIC T95 °C T 500 105 ...

  • Emerson Process Management 3051 - page 19

    Quick Start Guide 19 February 2015 N1 AT E X Ty p e n a n d D u s t Certificate: BAS00A TE X3105X; Baseefa11A TE X0275X Standards : EN60079-0:2012, EN60079 -15:2010, EN60079-31:20 09 Markings : II 3 G Ex nA IIC T5 Gc (–40 °C ≤ T a ≤ +70 °C); II 1 D Ex ta IIIC T95 °C T 500 105 °C Da (-20 °C ≤ T a ≤ +85 °C) Special Condition s for Saf ...

  • Emerson Process Management 3051 - page 20

    February 2015 20 Quick Start Guide Special Condition s for Safe Use (X ): 1. If the apparatus is fitted with op tional 90 V transient suppressor , it is not capable of withstanding the 500 V insulation te st required by IEC60079-11. This must be take n into acc ount when installin g the apparatus. 2. The enclosure m ay be made of aluminum alloy and ...

  • Emerson Process Management 3051 - page 21

    Quick Start Guide 21 February 2015 2. In case of re pair , contact the manufac turer for inf ormation on the dimensions o f the flameproof joints. 3. The capacitance of the wrap around label, be ing 1.6 nF , exceeds the limit in T able 9 of ABNT NBR IE C 60079-0. The user sh all dete rmine suitabilit y for the specific application. I2 INMETRO Intri ...

  • Emerson Process Management 3051 - page 22

    February 2015 22 Quick Start Guide Japan E4 Japan Flameproo f Certificate: T C20577, T C20578, T C20583, TC20584 Marking s: Ex d IIC T5 T echnical Re gulations C ustoms Union (EAC) EM EAC Flameproof Certificate: R U C-US.Gb05.B.00400 Markings : Ga/Gb Ex d I IC T5/T6 X, T5(-60 °C ≤ T a ≤ +80 °C), T6(-60 °C ≤ T a ≤ +65 °C ) Special Condit ...

  • Emerson Process Management 3051 - page 23

    Quick Start Guide 23 February 2015 Special Condition s for Safe Use (X): 1. When the thread ad apte r is used with an enc losure in t ype of protection increased saf et y “e” the e ntry thread shall be suitably s ealed in orde r to main tain the ingress protection rating (IP) of the enclosure . 2. The blanking plug shall not be u sed with an ad ...

  • Emerson Process Management 3051 - page 24

    February 2015 24 Quick Start Guide Figure 11. Rosemount 3051 EC Declaration of Conformity ...

  • Emerson Process Management 3051 - page 25

    Quick Start Guide 25 February 2015 ...

  • Emerson Process Management 3051 - page 26

    February 2015 26 Quick Start Guide ...

  • Emerson Process Management 3051 - page 27

    Quick Start Guide 27 February 2015 ...

  • Emerson Process Management 3051 - page 28

    Rosemount W orld Headquarters Emerson Process Management 6021 Innovation Blvd Shakopee, MN 553 79, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@EmersonProcess.com North America Regional Offic e Emerson Process Management 8200 Market Blvd. Chanhassen, MN 553 17, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCR ...

Fabbricante Emerson Process Management Categoria Pacemaker

I documenti che otteniamo dal fabbricante del dispositivoEmerson Process Management 3051 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Emerson Process Management
- manuali per l’uso 3051
- schede prodotto Emerson Process Management
- opuscoli
- o etichette energetiche Emerson Process Management 3051
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Emerson Process Management 3051.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Emerson Process Management 3051, manuali di manutenzione, brevi manuali o manuali utente Emerson Process Management 3051. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Emerson Process Management 3051.

Manuale completo del dispositivo Emerson Process Management 3051, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Emerson Process Management 3051 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Emerson Process Management 3051.

Il manuale per l’uso completo Emerson Process Management, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Emerson Process Management 3051 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Emerson Process Management 3051, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Emerson Process Management 3051 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Emerson Process Management 3051 - che ci dovrebbe aiutare nei primi passi durante l'uso Emerson Process Management 3051
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Emerson Process Management 3051
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Emerson Process Management 3051 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Emerson Process Management 3051?

Utilizza il modulo sottostante

Se non hai risolto il problema con Emerson Process Management 3051 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Emerson Process Management 3051 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)