    & H OOX OD U $ 5 8 3UR7 DO N INSTRUCTION MANUAL 1272M001 Manual Revision: 7 - July 2002 ...

  • Barnett Engineering ARU CV2 - page 2

    Contents 1. Operations Overview Cv2 capabilities ........................... 1 - 1 What constitutes an alarm? ................. 1 - 1 How are alarms processed? ................. 1 - 2 What actions should occur when an a l a r m i s d e t e c t e d ? ................... 1 - 3 How do you want to respond to an a l a r m c a l l ? ..................... ...

  • Barnett Engineering ARU CV2 - page 3

    Operations Overview 1-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 1. Operations Overview The purpose of this chapter is to provide an overview of the Cv2 capabilities. Chapter topics are organized in the same order that you would follow in setting up the system. Read this chapter carefully before proceeding with the installation and programmin ...

  • Barnett Engineering ARU CV2 - page 4

    Operations Overview 1-2 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 HA RDWA RE IN PU T S 8 IN PU T S 8 OUTPUTS POINTS UP TO 30 I NPU TS OR OU TPUTS GROUP 1 TEL EPH ONE PORT HA RDWA RE OUTPUTS GROUP 6 DI RECTOR Y A DI RECTOR Y F DI A LOUT COM MANDS CONT ROL COM MANDS Figure 1 Cv2 Block Diagram Analog inputs convert the voltage level to a digital ...

  • Barnett Engineering ARU CV2 - page 5

    Operations Overview 1-3 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 The hardware input and output ports are activated in the Points section to become part of the monitoring and control process. There are 30 points which can be referenced to any of the I/O ports. This allows an analog input to be used by more than one point and monitored for mult ...

  • Barnett Engineering ARU CV2 - page 6

    Operations Overview 1-4 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 For example, to call four telephone numbers, the directory would appear as: 1. [DIAL]2458829 [VOICE] 2. [DIAL]2336700 [VOICE] 3. [DIAL]9842121 [VOICE] 4. [DIAL]9843316 [VOICE] If you want an alert tone to precede the voice message the directory line would look like this: 1. [DIA ...

  • Barnett Engineering ARU CV2 - page 7

    Operations Overview 1-5 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 1.6 What if an alarm is not acknowledged? When the last line in the directory has been completed without receipt of an Acknowledge Code, a two-stage timer is used to determine when the directory sequence is repeated again. This timer has two sections: a Short Timer which operate ...

  • Barnett Engineering ARU CV2 - page 8

    Operations Overview 1-6 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 1.9 Indicators The Cv2 has four LED indicators to show the operation of the unit and assist in troubleshooting. When the Cv2 is initially powered up, the four LEDs will do the following: & All will turn on for approximately one second. & Hook will flash on and off for on ...

  • Barnett Engineering ARU CV2 - page 9

    Operations Overview 1-7 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Are the inputs connected properly? For digital inputs that are programmed for standard digital operation, create an alarm condition on the input and confirm that the Alarm LED com es on. Make sure the input is applied long enough for the debounce to time out. If the Alarm indica ...

  • Barnett Engineering ARU CV2 - page 10

    Installation 2-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Figure 3 Packaged Cv2 2 Installation The Cv2 can be installed before or after the configuration has been transferred from the PC to the unit. If the Cv2 is configured in the shop before it is installed in the field, all of the programmed parameters and voices will remain unchanged in t ...

  • Barnett Engineering ARU CV2 - page 11

    Installation 2-2 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Figure 3 Stand-alone Cv2 Figure 4 Ground Closure Input Wiring 2.2.2 Stand-alone model The stand-alone Cv2 can be mounted on a flat surface. Make sure that there is enough room around the unit to make connections. The environment should be clean and dry, with an ambient temperature that ...

  • Barnett Engineering ARU CV2 - page 12

    Installation 2-3 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Figure 5 +12 Volt Input Wiring Figure 6 +5 VDC Input Wiring Figure 8 Analog (unfiltered) Input Wiring Figure 7 Analog (filtered) Input Wiring 2.3.2 +12 volt alarm signal The input will accept an alarm signal that switches between 0 and +12 volts with the wiring arrangement shown in Fig ...

  • Barnett Engineering ARU CV2 - page 13

    Installation 2-4 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Figure 9 Output Wiring Figure 10 Serial Cable 2.4 Output port connections The output ports are open collector drivers that can sink up to 500 mA through a load connected to a voltage of up to +50 VDC. If an inductive load such as a relay is connected to an output, install a protective ...

  • Barnett Engineering ARU CV2 - page 14

    Installation 2-5 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Figure 11 Stand-alone Cv2 Figure 12 Packaged Cv2 ...

  • Barnett Engineering ARU CV2 - page 15

    Configuration using the PC 3-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 3 Configuration using the PC This chapter describes how to install the programming software and configure the operation of the Cv2. When the configuration is complete, it can be viewed through the Sum mary command found on the File pull-down menu. In the summ ary, Warning ...

  • Barnett Engineering ARU CV2 - page 16

    Configuration using the PC 3-2 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 3.4.1 File Operations File Open If you do not want to edit the default database, use the File Open button to select a different configuration file. This will bring up the standard Windows File Open dialog box where you can open another .dat file. File Save As To save the ...

  • Barnett Engineering ARU CV2 - page 17

    Configuration using the PC 3-3 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 3.4.6 Directories When an alarm is detected, the Cv2 will perform a specific sequence of events determined by the entries in the directory. Six directories are available, providing different actions for different groups. 3.4.7 Programming The programming section is used t ...

  • Barnett Engineering ARU CV2 - page 18

    Configuration using the PC 3-4 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 debounce times, use the seconds timer to avoid the inaccuracy introduced by the one minute resolution. Default Debounce time: 0.05 sec A Digital input port can also be used to perform special functions in the Cv2. In the Groups section, it can be selected for the Local Ac ...

  • Barnett Engineering ARU CV2 - page 19

    Configuration using the PC 3-5 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Analog Input Setting the input port type to Analog allows measurement of voltages between 0 and +5 volts. As with the other input types, the definition of an analog input is completed in the Points section where the range, setpoints and units are assigned. An Analog port ...

  • Barnett Engineering ARU CV2 - page 20

    Configuration using the PC 3-6 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Each point can be placed into one of the six groups. If a port is used for one of the special functions, the Group section sets the ports. To access a point for configuration, select the Points button to bring up the summary of the settings. Status of the 30 points will b ...

  • Barnett Engineering ARU CV2 - page 21

    Configuration using the PC 3-7 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Enabled When a point is enabled, alarm activities will be reported and it can be interrogated for its current status. A disabled point does not produce alarms and cannot be interrogated. Changing the enable flag does not alter any of the other settings for this point. Def ...

  • Barnett Engineering ARU CV2 - page 22

    Configuration using the PC 3-8 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 When the message is spoken, the digits to the left of the decim al (represented by X) and the digits to the right of the decimal (represented by Y) are spoken with the word ‘point’ between them. The format with the decim al at the far right with no ‘Y’ component i ...

  • Barnett Engineering ARU CV2 - page 23

    Configuration using the PC 3-9 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Calibrate Calibration of an analog allows the conversion of the input voltage reading to a value that is expressed in engineering units. Setpoints are then assigned to the actual corresponding measurement, and when the point is interrogated, the reading is announced in en ...

  • Barnett Engineering ARU CV2 - page 24

    Configuration using the PC 3-10 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 0 as the minimum , 10 as the maximum, with Units set to read ‘thousand’ as the prefix before gallons. Once the range of the decimal scale has been entered, then the high and low setpoints can follow. Both setpoints can be used within a single point. If the low setpoi ...

  • Barnett Engineering ARU CV2 - page 25

    Configuration using the PC 3-11 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 DTMF Off Code When the Cv2 receives the DTMF Off code, it sets the output port to the Off state. After the Off code has been received and the output port cleared, the Cv2 announces the current status of the output. This code can be 1 to 7 digits in length and may use any ...

  • Barnett Engineering ARU CV2 - page 26

    Configuration using the PC 3-12 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 conditions. If a different type of activity is required, such as after hours or weekends, the change can be quickly made by using another shift to control the Cv2 operation. There are also a number of special function settings that enable outputs and inputs to operate as ...

  • Barnett Engineering ARU CV2 - page 27

    Configuration using the PC 3-13 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Enable Ack Request At the completion of an alarm announcem ent sequence, the Cv2 will query the called party with the phrase “Enter Acknowledge Code’. If this prompt is not required, clear the enable setting. Default Ack Request: enabled Timers The Cv2 uses a two-sta ...

  • Barnett Engineering ARU CV2 - page 28

    Configuration using the PC 3-14 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Special Function Outputs Outputs can be assigned to indicate certain conditions within the Cv2. The three special function outputs are: Alarm Active This control allows any one of the eight output ports to be used as an indicator that an alarm is present in this group. T ...

  • Barnett Engineering ARU CV2 - page 29

    Configuration using the PC 3-15 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Only Digital inputs can be used for this purpose. The selection shown in the list box is restricted to inputs that are set to digital in the Hardware section. To use this feature, the input must be selected in the Points section and enabled. Default Special Function Inpu ...

  • Barnett Engineering ARU CV2 - page 30

    Configuration using the PC 3-16 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Auto Ack If enabled for the group using this directory, the Auto Ack command causes the Cv2 to automatically acknowledge its alarms without receipt of any other code or signal. This command is used when it is anticipated that the called party will have no m eans of ackno ...

  • Barnett Engineering ARU CV2 - page 31

    Configuration using the PC 3-17 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Signal If a DTMF tag is programmed for a point and the Signal com mand is set, then only the DTMF tag for this point will be sent and the voice message will not be spoken. Signal must be preceded by a Dial comm and; it cannot be the first entry in the list. It can be use ...

  • Barnett Engineering ARU CV2 - page 32

    Configuration using the PC 3-18 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 programming is always available if there is no Access code in the unit. This code can be 1 to 7 digits in length and may use any of the 16 DTMF digits including A, B, C, and D. Default Access Code: an empty string. Shift Change Code The shift that is being used at any pa ...

  • Barnett Engineering ARU CV2 - page 33

    Configuration using the PC 3-19 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 operational. Data is transferred in four-kilobyte packets at 9600 baud. The configuration database will take two packets to transfer; the number of packets in a voice data transfer will vary depending on how many points are used and how long the messages are. Configurati ...

  • Barnett Engineering ARU CV2 - page 34

    Voice Storage and Configurat ion with the Telset 4-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 4 Voice Storage and Configuration with the Telset 4.1 Setup After the configuration database has been transferred to the Cv2, it is ready to accept the voice messages that will be used in the alarm reporting process and it is possible to change some ...

  • Barnett Engineering ARU CV2 - page 35

    Voice Storage and Configurat ion with the Telset 4-2 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 directory menu. The choices at this point are: 0 UU - Speak the Directory Codes These codes correspond to buttons found in the Directory Editor dialog box used for PC programming. They are used to enter the new configuration. #0 DIAL Initiate a phone ...

  • Barnett Engineering ARU CV2 - page 36

    Voice Storage and Configurat ion with the Telset 4-3 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 If a sequence is entered without a Voice command, the Cv2 will add the word “Warning” when it speaks the line. 3 UU Delete current entry Cv2: “beep” This command will rem ove the selected line from the directory. If there are any lines follow ...

  • Barnett Engineering ARU CV2 - page 37

    Voice Storage and Configurat ion with the Telset 4-4 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Pauses between words may cause the recording to terminate. If the message is acceptable, press UU to advance to the next voice. If it is not, keep using 2 UU and repeat the message until it is satisfactory, then press UU to accept the current recordi ...

  • Barnett Engineering ARU CV2 - page 38

    Voice Storage and Configurat ion with the Telset 4-5 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 8 UU - Received Signal Strength Cv2: “Code Eight is One, One, Two, One, ...” The Cv2 speaks a number from One to Thirteen. Each increm ent corresponds to approximately 5 dBm, with 0 representing roughly -121 dBm and 13 representing -56 dBm. The L ...

  • Barnett Engineering ARU CV2 - page 39

    Voice Storage and Configurat ion with the Telset 4-6 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2  Cv2: "Enter Program Code" Cv2: "Enter Directory Code" Edit Directories  Speak Directory Codes Cv2: Speaks the list of Directory Codes described previously  ,  ...  Cv2: "Directory ...

  • Barnett Engineering ARU CV2 - page 40

    Voice Storage and Configurat ion with the Telset 4-7 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2  Exit Cv2: "Group One is Electrical " Cv2: "beep" Record Cv2: "Group One is Mechanical "  Accept Cv2: "beep"  Enable Groups " Electrical On" or " Electrical Off" ? ...

  • Barnett Engineering ARU CV2 - page 41

    Voice Storage and Configurat ion with the Telset 4-8 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2  Query NAM Cv2: "Code Four is One" or "Code Four is Two"  - call placed  Query MIN Cv2: "Code Five is Two Three Eight ..."  Query ESN Cv2: "Code Six is Nine Four Four. ...

  • Barnett Engineering ARU CV2 - page 42

    Specifications 6-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 5 Specifications 5.1 General Alarm Inputs • 8 inputs: analog or digital, latching or m omentary; plug in screw terminal block. • analog: 0 to 5 VDC, 100k input im pedance • digital: norm ally open or normally closed, ground closure or +10 to +30 VDC input; optionally configured ...

  • Barnett Engineering ARU CV2 - page 43

    Specifications 6-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 Alarm Groups • Alarm s can be assigned to one of 8 groups. All alarms in a group use the same directory when calling out. Shifts • Up to 4 shifts can be used. The current setting of the shift instructs a group to use one of the six directories. Interval Timer • Two-stage tim er ...

  • Barnett Engineering ARU CV2 - page 44

    Specifications 6-1 B1272M001 BARNETT ENGINEERING LTD. ProTalk Cv2 6 Warranty Barnett Engineering Ltd. warrants that all equipment supplied shall be free from defects in material or workmanship at the tim e of delivery. Such warranty shall extend from the time of delivery for a period of one year. Buyer must provide written notice to Barnett Enginee ...

Fabbricante Barnett Engineering Categoria Home Security System

I documenti che otteniamo dal fabbricante del dispositivoBarnett Engineering ARU CV2 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Barnett Engineering
- manuali per l’uso ARU CV2
- schede prodotto Barnett Engineering
- opuscoli
- o etichette energetiche Barnett Engineering ARU CV2
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Barnett Engineering ARU CV2.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Barnett Engineering ARU CV2, manuali di manutenzione, brevi manuali o manuali utente Barnett Engineering ARU CV2. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Barnett Engineering ARU CV2.

Manuale completo del dispositivo Barnett Engineering ARU CV2, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Barnett Engineering ARU CV2 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Barnett Engineering ARU CV2.

Il manuale per l’uso completo Barnett Engineering, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Barnett Engineering ARU CV2 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Barnett Engineering ARU CV2, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Barnett Engineering ARU CV2 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Barnett Engineering ARU CV2 - che ci dovrebbe aiutare nei primi passi durante l'uso Barnett Engineering ARU CV2
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Barnett Engineering ARU CV2
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Barnett Engineering ARU CV2 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Barnett Engineering ARU CV2?

Utilizza il modulo sottostante

Se non hai risolto il problema con Barnett Engineering ARU CV2 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Barnett Engineering ARU CV2 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)