    246819-BTG-H-0208 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE SPLIT - SYSTEM HEA T PUMPS 13 SEER – R-22 MODELS: E*BD-F018 THRU 060 (1.5 THRU 5 NOMINAL T ONS, 1 PHASE) E*BD-(T ,W)036 THRU 060 (2.5 THRU 5 NOMINAL T ONS, 3 PHASE) Due to continuo us product imp rovement, speci fications are subject to chan ge without notice. Vi ...

  • York W)036 THRU 060 - page 2

    246819-BTG-H-0208 2 Unitary Products Group All dimensions are in inches. They are subject to cha nge without notice. Ce rtif ied dimensio ns will be provide d upon request. Physical and Electrical Dat a - 1 Phase MODEL EABD-F018S EABD-F024S EABD-F030S EABD-F036S EABD-F042S EABD-F048S EABD-F060S Unit Supply V oltage 208-230V , 1 φ, 60Hz Normal V ol ...

  • York W)036 THRU 060 - page 3

    246819-BTG-H-0208 Unitary Products Group 3 Additional R-22 Charge / Orifice Size for V arious Matched Syste ms - 1 Phase Outdoor Unit EABD-F018S EABD-F024S EABD-F030S EAB D-F036S EABD-F042S EABD-F048S EABD-F060S Required TXV 1 TVM2A1 1 TVM2A1 1 TVM2A1 1 TVM2A1 1 TVM2C1 1 TVM2C1 1 TVM2C1 Factory Charge, lbs-oz 7 - 1 6 - 9 8 - 9 8 - 7 8 - 7 12 - 8 16 ...

  • York W)036 THRU 060 - page 4

    246819-BTG-H-0208 4 Unitary Products Group * This loose coil match does not achieve 13 SEER. PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes re frigerant for the condenser , the smallest evaporator and 15 feet of inter- connecting line tubing. 2. V erify the orifice size and the additional charge required for t he specific ...

  • York W)036 THRU 060 - page 5

    246819-BTG-H-0208 Unitary Products Group 5 All dimensions are in inche s. Th ey are su bject to change with- out notice. Certified dimensions will be pro vided upon request. Physical and Elect rical Dat a - 3 Ph ase MODEL EABD- T030S EABD- T036S EABD- T042S EABD- T048S EABD- T060S EABD- W030S EABD- W036S EABD- W042S EABD- W048S EABD- W060S Unit Sup ...

  • York W)036 THRU 060 - page 6

    246819-BTG-H-0208 6 Unitary Products Group PROCEDURES: 1. U nit factory charge listed on the unit nameplate includes refr igerant for the condenser , the smallest evaporator and 15 feet of inter-con- necting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using th e above table. 3. Additional ...

  • York W)036 THRU 060 - page 7

    246819-BTG-H-0208 Unitary Products Group 7 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 1 & 3 PH 13 SEER HP WITH MA EABD-F018S MA08B 17 FC/MC18B 600 18 .0 12.4 13 .00 1 1.00 EABD-F024S MA08B 17 FC/MC24B 800 23.2 16.8 13.00 1 1.00 MA08B 17 FC/MC30B 800 23 ...

  • York W)036 THRU 060 - page 8

    246819-BTG-H-0208 8 Unitary Products Group — = Not Applicable. Go to www.ari. org/aridirectory for the latest additiona l matches. 1 PH 13 SEER AC WITH A V / SV - V ARIABLE SPEED EABD-F018S A V24 17 – 600 18.0 12.6 14.00 12.00 EABD-F024S A V24 17 – 800 23.8 16.7 14.00 12.00 EABD-F030S A V36 17 – 1000 29.2 20.1 14 .00 12.00 EABD-F036S A V36 ...

  • York W)036 THRU 060 - page 9

    246819-BTG-H-0208 Unitary Products Group 9 COOLING CAP ACITY - Upflow , Downflow , and Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. EABD-F018S 450 750 14,17 FC/MC/PC/UC18 600 18.0 12 .4 13.00 1 1.00 14 HC18 600 17.8 12 .1 13.00 1 1.00 EABD-F024S 600 1000 14 ...

  • York W)036 THRU 060 - page 10

    246819-BTG-H-0208 10 Unitary Products Group COOLING CAP ACITY - With V ariable S peed Furnac es UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER T OTAL SENS. 1 PH 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 EABD-F018S (F ,L)L8V A12 FC/MC/PC18A 14 600 18.0 12.5 14.00 12.00 FL9V A12 FC/MC/PC18A 14 600 18.0 12 ...

  • York W)036 THRU 060 - page 11

    246819-BTG-H-0208 Unitary Products Group 11 EABD-F048S FL9(C,V)D20 FC/MC/PC60D 24 1600 46.0 35 .5 13.25 1 1.00 (F ,L)L8VC16 FC/PC60C 21 1500 45.5 35.1 13 .25 1 1.00 (F ,L)L8VC20 FC/PC60C 21 1600 46.0 35.4 13 .25 1 1.00 FL9(C,V)C16 FC/PC60C 21 1600 46.0 35 .5 13.25 1 1.00 FL9(C,V)C20 FC/PC60C 21 1600 46.0 34 .5 13.25 1 1.00 FL9(C,V)D20 HC60 24 1600 ...

  • York W)036 THRU 060 - page 12

    246819-BTG-H-0208 12 Unitary Products Group HEA TING PERFORMANCE - With Air Handler UNIT MODEL* AIR HANDLER COIL 1 MODEL ARI HEA T ING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD 1 & 3 PH 13 SEER HP WITH MA EABD-F018S MA08B FC/MC18B 18.0 3.62 1.46 10.5 2.28 1 .35 8.00 EABD-F024S M A 0 8 B F C / M C 2 4 B 2 3 . 03 . 4 41 . 9 61 3 . 12 . 3 ...

  • York W)036 THRU 060 - page 13

    246819-BTG-H-0208 Unitary Products Group 13 CP equals MBH output divided by (t otal KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating ou tput during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. 1 PH 13 SEER HP WITH A V - V ARIABLE SP ...

  • York W)036 THRU 060 - page 14

    246819-BTG-H-0208 14 Unitary Products Group CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. HEA TING PERFOR MANCE - Upflow Furnace C ...

  • York W)036 THRU 060 - page 15

    246819-BTG-H-0208 Unitary Products Group 15 HEA TING CAP ACITY - W ith V ariable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE COIL 1 MODEL ARI HEA T ING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD EABD-F018S (F ,L)L8V A12 FC/MC/PC18A 17.5 3.88 1.32 10 .0 2.42 1.21 8.60 FL9V A12 FC/MC/PC18A 17.6 3.82 1.35 10 .1 2.40 1.23 8.40 FL9(C,V)B12 ...

  • York W)036 THRU 060 - page 16

    246819-BTG-H-0208 16 Unitary Products Group CP equals MBH output divided by (to tal KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. EABD-F042S ( F , L ) L 8 V C 2 0 F C / ...

  • York W)036 THRU 060 - page 17

    246819-BTG-H-0208 Unitary Products Group 17 ACCESSORIES Refer to Price Manual for specific model numbers. St art Assist Kit (2SA067*) Blower Time Delay - A vailable to increase efficiency when installed. Installs on indoor section and maintains blower for approximately one minute a fter cooling thermostat has been satisfied. Hard St art Kit s - Pro ...

  • York W)036 THRU 060 - page 18

    246819-BTG-H-0208 18 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree bel ...

  • York W)036 THRU 060 - page 19

    246819-BTG-H-0208 Unitary Products Group 19 Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York W)036 THRU 060 - page 20

    246819-BTG-H-0208 20 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree bel ...

  • York W)036 THRU 060 - page 21

    246819-BTG-H-0208 Unitary Products Group 21 Multipliers for determining th e performance with other indoor sections NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree below ...

  • York W)036 THRU 060 - page 22

    246819-BTG-H-0208 22 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree bel ...

  • York W)036 THRU 060 - page 23

    246819-BTG-H-0208 Unitary Products Group 23 Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York W)036 THRU 060 - page 24

    246819-BTG-H-0208 24 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree bel ...

  • York W)036 THRU 060 - page 25

    246819-BTG-H-0208 Unitary Products Group 25 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO EABD-F018S EV APORA T OR COIL MODEL NO FC /MC/PC/UC18 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 450 600 750 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTUH K ...

  • York W)036 THRU 060 - page 26

    246819-BTG-H-0208 26 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO EABD-F024S EV APORA T OR COIL MODEL NO FC /MC/PC/UC24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 600 800 1000 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTU H ...

  • York W)036 THRU 060 - page 27

    246819-BTG-H-0208 Unitary Products Group 27 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F030S, EABD-(T ,W)030S** EV APORA T OR COIL MODEL NO FC /MC/PC35 AIR TEMP . ENTERING OUTDOOR UNIT ...

  • York W)036 THRU 060 - page 28

    246819-BTG-H-0208 28 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E ABD-F036S, EABD-(T ,W)036S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC48 AIR TEMP . ENTERING OUTDOOR U ...

  • York W)036 THRU 060 - page 29

    246819-BTG-H-0208 Unitary Products Group 29 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F042S, EABD-(T ,W)042S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC48 AIR TEMP . ENTERING OUTDOOR U ...

  • York W)036 THRU 060 - page 30

    246819-BTG-H-0208 30 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E ABD-F048S, EABD-(T ,W)048S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC60 AIR TEMP . ENTERING OUTDOOR U ...

  • York W)036 THRU 060 - page 31

    246819-BTG-H-0208 Unitary Products Group 31 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F060S, EABD-(T ,W)060S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC60 AIR TEMP . ENTERING OUTDOOR U ...

  • York W)036 THRU 060 - page 32

    Subject to change without notice. Printed in U.S.A. 246819-BTG-H-0208 Copyright © by Unitary Products Group. 2008. Al l rights reserved. Supersedes: 246819-BTG-G-0607 Unitary 5005 Norman Product Y ork OK Group Drive 73069 NOTES ...

Fabbricante York Categoria Heat Pump

I documenti che otteniamo dal fabbricante del dispositivoYork W)036 THRU 060 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici York
- manuali per l’uso W)036 THRU 060
- schede prodotto York
- opuscoli
- o etichette energetiche York W)036 THRU 060
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso York W)036 THRU 060.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione York W)036 THRU 060, manuali di manutenzione, brevi manuali o manuali utente York W)036 THRU 060. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto York W)036 THRU 060.

Manuali per l’uso simili

Manuale completo del dispositivo York W)036 THRU 060, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare York W)036 THRU 060 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti York W)036 THRU 060.

Il manuale per l’uso completo York, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale York W)036 THRU 060 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice York W)036 THRU 060, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per York W)036 THRU 060 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo York W)036 THRU 060 - che ci dovrebbe aiutare nei primi passi durante l'uso York W)036 THRU 060
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del York W)036 THRU 060
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio York W)036 THRU 060 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su York W)036 THRU 060?

Utilizza il modulo sottostante

Se non hai risolto il problema con York W)036 THRU 060 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con York W)036 THRU 060 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)