Manuale per l’uso Dimplex SI 7CS

40 pagine 1.57 mb
Scarica

Vai alla pagina of 40

Summary
  • Dimplex SI 7CS - page 1

    1 MOUNTING and OPERA TING MANUAL Brine-to-W ater Heat Pump for Indoor Installation SI 14CS SI 17CS SI 21CS SI 5CS SI 7CS SI 9CS SI 1 1CS CE Order No.: 452230.67.01 FD 8404 ...

  • Dimplex SI 7CS - page 2

    2 CONTENTS 1 READ IMMEDIA TEL Y 3 1.1 Important Information 1.2 Legal Provisions and Directives 1.3 Energy-Efficient Use of the Heat Pump 2 PURPOSE OF THE HEA T PUMP 4 2.1 Application 2.2 Principle of Operation 3 BASELINE UNIT 4 4 ACCESSORIES 5 4.1 Brine Manifold 5 TRANSPORT 5 6 INST ALLA TION 6 6.1 General Information 6. 2 Sound Emissions 7 MOUNTI ...

  • Dimplex SI 7CS - page 3

    3 READ IMMEDIA TEL Y 1.1 Important Information The heat pump is not attached to the wooden pallet. The heat pump must not be tilted more than max. 45 ° (in either direction). Do not lift unit by the holes in the panel assemblies! Flush the heating system prior to connecting the heat pump. The supplied strainer is to be fitted in the heat source in ...

  • Dimplex SI 7CS - page 4

    4 BASELINE UNIT The baseline unit consists of a heat pump, ready for connection, for indoor installation, complete with sheet metal cabinet, control panel and integrated controller . The refrigeration cycle contains the refrigerant R407C. Refrigerant R407C is CFC-free, non-ozone depleting and non-combustible. All components required for the operati ...

  • Dimplex SI 7CS - page 5

    5 5 4 ACCESSORIES 4.1 Brine Manifold The brine manifold ties the individual collector loops of the heat source system into a single main line which is connected to the heat pump. Integrated ball valves allow individual brine circuits to be shut off for venting purposes. ACCESSORIES TRANSPORT TRANSPORT A lift truck is suited for transporting the uni ...

  • Dimplex SI 7CS - page 6

    6 INST ALLA TION 6.1 General Information As a rule, the unit must be installed indoors on a level, smooth and horizontal surface. The entire base frame should thereby make close contact with the surface in order to ensure adequate sound insulation. Failing this, additional sound insulation measures may become necessary . The heat pump should be loc ...

  • Dimplex SI 7CS - page 7

    7 CAUTION! MOUNTING 7.4 Electrical Connection The following electrical connections must be established on the heat pump: - Connection of the control wire to the control panel of the heat pump via terminals X1: L/N/PE. - Connection of the load wire to the control panel of the heat pump via terminals X5: L1/L2/L3/PE. - Connection of the brine pump (t ...

  • Dimplex SI 7CS - page 8

    8 COMMISSIONING 8.1 General Information T o ensure proper commissioning it should be carried out by an after-sales service authorized by the manufacturer . Only then can an extended warranty period of 3 years in total be granted (cf. Warranty service). 8.2 Preparation Prior to commissioning, the following items need to be checked: - All connections ...

  • Dimplex SI 7CS - page 9

    9 Caution - Heating T echnicians ! Depending on the filling water quality and quantity , in particular in the case of mixed installations and plastic pipes, mineral deposits (rust sludge, lime) may form, impairing the pro- per functioning of the heating installation. A reason for this is the water hardness and oxygen dissolved in the filling waters ...

  • Dimplex SI 7CS - page 10

    10 DECOMMISSIONING 1 1.1 Shutdown in Summer Shutting down the heating system in summer is effected by switching the heat pump controller to the "Summer" operating mode. 1 1.2 End-of-Life Decommissioning/ Disposal Before removing the heat pump, disconnect the machine from the power source and close all valves. Environment-relevant requirem ...

  • Dimplex SI 7CS - page 11

    11 APPENDIX 12 12.1 Dimensioned Drawings 12.1.1 Dimens'ddrawing .. 5CS - 14CS 12 12.1.2 Dimens'd drawing .. 17CS - 21CS 13 12.2 Equipment Data 14 12.3 Performance Curves/Pressure Losses 12.3.1 Performance Curves .. 5CS 15 12.3.2 Pressure Losses .. 5CS 16 12.3.3 Performance Curves .. 7CS 17 12.3.4 Pressure Losses .. 7CS 18 12.3.5 Performan ...

  • Dimplex SI 7CS - page 12

    12 APPENDIX: 12.1 DIMENSIONED DRAWINGS 12.1.1 Dimensioned Drawing .. 5CS - 14CS Heating water supply Heat pump outlet Heating water return Heat pump inlet Heat source supply Heat pump outlet Heat source return Heat pump inlet Connections on heating side 1" internal / 1" external thread Connections on heat source side 1 1/4" internal ...

  • Dimplex SI 7CS - page 13

    13 APPENDIX: 12.1 DIMENSIONED DRAWINGS 12.1.2 Dimensioned Drawings .. 17CS - 21 CS Heating water return Heat pump inlet Heating water supply Heat pump outlet Heat source supply Heat pump outlet Heat source return Heat pump inlet Connections on heating side 1 1/4" internal / 1" external thread Connections on heat source side 1 1/2" in ...

  • Dimplex SI 7CS - page 14

    14 APPENDIX: 12.2 EQUIPMENT D A T A Equipment Data EQUIPMENT DATA for brine-to-water heat pumps for heating purposes 1 TYPE AND COMMERCIAL DESCRIPTION ..5CS ..7CS ..9CS ..11CS ..14CS ..17CS ..21CS 2 MODEL 2.1 Enclosure type acc. to EN 60 529 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 2.2 Installation site indoors indoors indoors indoors indoors indo ...

  • Dimplex SI 7CS - page 15

    15 12.3.1 Performance Curves .. 5CS APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES 0 2 4 6 8 10 12 14 16 Heizleistung in [kW] Wasseraustrittstemperatur in [°C] 0 1 2 3 4 5 6 7 8 Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen) 35 50 0 1 2 3 4 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 Soleeintrittstemperatur in [° ...

  • Dimplex SI 7CS - page 16

    16 12.3.2 Pressure Losses .. 5CS APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES 0 5000 10000 15000 20000 25000 30000 35000 40000 0 0,5 1 1,5 2 2,5 3 3,5 4 Soledurchfluß in [m³/h] Druckverluste Verdampfer bei Sole -5°C ohne Solezubehör Druckverlust 6,5 kPa bei Sole-Nenndurchfluß 1,2 m³/h Druckverlust in [Pa] 0 5000 10000 15000 20000 25000 0 ...

  • Dimplex SI 7CS - page 17

    17 12.3.3 Performance Curves .. 7CS APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES 0 2 4 6 8 10 12 14 16 Heizleistung in [kW] Wasseraustrittstemperatur in [°C] 0 1 2 3 4 5 6 7 8 Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen) 35 50 0 1 2 3 4 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 Soleeintrittstemperatur in [° ...

  • Dimplex SI 7CS - page 18

    18 12.3.4 Pressure Losses .. 7CS APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES 0 5000 10000 15000 20000 25000 30000 35000 40000 0 0,5 1 1,5 2 2,5 3 3,5 4 Soledurchfluß in [m³/h] Druckverluste Verdampfer bei Sole -5°C ohne Solezubehör Druckverlust 10 kPa bei Sole-Nenndurchfluß 1,7 m³/h Druckverlust in [Pa] 0 5000 10000 15000 20000 25000 0 ...

  • Dimplex SI 7CS - page 19

    19 12.3.5 Performance Curves .. 9CS APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES 0 2 4 6 8 10 12 14 16 Heizleistung in [kW] Wasseraustrittstemperatur in [°C] 0 1 2 3 4 5 6 7 8 Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen) 35 50 0 1 2 3 4 5 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 Soleeintrittstemperatur in [ ...

  • Dimplex SI 7CS - page 20

    20 12.3.6 Pressure Losses .. 9CS APPENDIX: 12.3 PERFORMANCE CURVES/DPRESSURE LOSSES 0 5000 10000 15000 20000 25000 30000 35000 40000 0 0,5 1 1,5 2 2,5 3 Soledurchfluß in [m³/h] Druckverluste Verdampfer bei Sole -5°C ohne Solezubehör Druckverlust 16 kPa bei Sole-Nenndurchfluß 2,3 m³/h Druckverlust in [Pa] 0 5000 10000 15000 20000 25000 0 0,2 0 ...

  • Dimplex SI 7CS - page 21

    21 12.3.7 Performance Curves .. 1 1CS APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES 0,0 2,0 4,0 6,0 8,0 10,0 12,0 14,0 16,0 18,0 20,0 22,0 24,0 Heizleistung in [kW] Wasseraustrittstemperatur in [°C] 0 1 2 3 4 5 6 7 8 Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen) 35 50 0 1 2 3 4 5 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 ...

  • Dimplex SI 7CS - page 22

    22 12.3.8 Pressure Losses .. 1 1CS APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES 0 5000 10000 15000 20000 25000 30000 35000 40000 0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 Soledurchfluß in [m³/h] Druckverluste Verdampfer bei Sole -5°C ohne Solezubehör Druckverlust 13 kPa bei Sole-Nenndurchfluß 3,0 m³/h Druckverlust in [Pa] 0 2000 4000 6000 8000 100 ...

  • Dimplex SI 7CS - page 23

    23 12.3.9 Performance Curves .. 14CS APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Heizleistung in [kW] Wasseraustrittstemperatur in [°C] 0 1 2 3 4 5 6 7 8 Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen) 35 50 0 1 2 3 4 5 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 Soleei ...

  • Dimplex SI 7CS - page 24

    24 12.3.10 Pressure Losses .. 14CS APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES 0 5000 10000 15000 20000 25000 30000 0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 Soledurchfluß in [m³/h] Druckverluste Verdampfer bei Sole -5°C ohne Solezubehör Druckverlust 13 kPa bei Sole-Nenndurchfluß 3,5 m³/h Druckverlust in [Pa] 0 2000 4000 6000 8000 10000 12000 140 ...

  • Dimplex SI 7CS - page 25

    25 12.3.1 1 Performance Curves .. 17CS APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Heizleistung in [kW] Wasseraustrittstemperatur in [°C] 0 1 2 3 4 5 6 7 8 Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen) 35 50 0 1 2 3 4 5 6 7 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 ...

  • Dimplex SI 7CS - page 26

    26 12.3.12 Pressure Losses .. 17CS APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES 0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 0123456 Soledurchfluß in [m³/h] Druckverluste Verdampfer bei Sole -5°C ohne Solezubehör Druckverlust 9 kPa bei Sole-Nenndurchfluß 3,8 m³/h Druckverlust in [Pa] 0 2000 4000 6000 8000 10000 1 ...

  • Dimplex SI 7CS - page 27

    27 12.3.13 Performance Curves .. 21CS APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 Heizleistung in [kW] Wasseraustrittstemperatur in [°C] 0 1 2 3 4 5 6 7 8 Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen) 35 50 0 1 2 3 4 5 6 7 -10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 1 ...

  • Dimplex SI 7CS - page 28

    28 12.3.14 Pressure Losses .. 21CS APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES 0 2000 4000 6000 8000 10000 12000 14000 16000 18000 20000 22000 24000 012345678 Soledurchfluß in [m³/h] Druckverluste Verdampfer bei Sole -5°C ohne Solezubehör Druckverlust 12 kPa bei Sole-Nenndurchfluß 6,0 m³/h Druckverlust in [Pa] 0 2000 4000 6000 8000 1000 ...

  • Dimplex SI 7CS - page 29

    29 12.4.1 Control .. 5CS to .. 17CS APPENDIX: 12.4 WIRING DIAGRAMS Mains system ...

  • Dimplex SI 7CS - page 30

    30 12.4.2 Load .. 5CS to .. 17CS APPENDIX: 12.4 WIRING DIAGRAMS Mains system No soft starter fitted in brine-to-water units 5C and 7C Sheet 1/N1 Remove wire jumper A3 prior to connecting M1 1 circulating pump motor protection (F15) (from –9CS to –17CS). A3 is the „M1 1 fault“ jumper ...

  • Dimplex SI 7CS - page 31

    31 12.4.3 T erminal Diagram .. 5CS to .. 17CS APPENDIX: 12.4 WIRING DIAGRAMS Mains system Contact open = HP disabled Function E10 is selectable 2 nd disable input Contact open = HP disabled Lines to be field-connected, if required Mains system 230 V AC - 50 Hz ...

  • Dimplex SI 7CS - page 32

    32 12.4.4 Legend .. 5CS to .. 17CS APPENDIX: 12.4 WIRING DIAGRAMS A 1 Wire jumper , must be removed if a utility company disable contactor is used A 2 Wire jumper , must be removed if 2nd disable input is used A 3 Wire jumper , must be removed if a motor protection contact for primary pump is used A 4 Wire jumper , must be removed if a motor protec ...

  • Dimplex SI 7CS - page 33

    33 12.4.5 Control .. 21CS APPENDIX: 12.4 WIRING DIAGRAMS Mains system ...

  • Dimplex SI 7CS - page 34

    34 12.4.6 Load .. 21CS APPENDIX: 12.4 WIRING DIAGRAMS Mains system ...

  • Dimplex SI 7CS - page 35

    35 12.4.7 T erminal Diagram .. 21CS APPENDIX: 12.4 WIRING DIAGRAMS Mains system Mains system 230 V AC - 50 Hz Utility company disable contactor Contact open = HP disabled The function of the suppl. heating system can be selected 2 nd disable input Contact open = HP disabled ...

  • Dimplex SI 7CS - page 36

    36 12.4.8 Legend .. 21CS APPENDIX: 12.4 WIRING DIAGRAMS A 1 Wire jumper , must be removed if a utility company disable contactor is used A 2 Wire jumper , must be removed if 2nd disable input is used B2 * Pressostat low pressure, brine B3 * Thermostat, hot water B4 * Thermostat, swimming pool water E9 * Electr . immersion heater, hot water E10* Sup ...

  • Dimplex SI 7CS - page 37

    37 Hydraulic Block Diagram APPENDIX: 12.5 HYDRAULIC BLOCK DIAGRAM Heat pump Buffer tank Heat pump controller Electric distribution Hot water storage tank Ground collectors Ground loops Brine manifold Brine collector Shut-off valve Shut-off valve with drain Overflow valve Safety valve Circulating pump Expansion vessel Thermostat/manual valve Shut-of ...

  • Dimplex SI 7CS - page 38

    38 APPENDIX: 12.6 EC DECLARA TION OF CONFORMITY EC Declaration of Conformity Declaration of Conformity The undersigned KKW Kulmbacher Klimageräte-W erk GmbH, Division Dimplex Am Goldenen Feld 18 D-95326 Kulmbach her eby confirm that the design and construction of the pr oduct(s) listed below , in the version(s) placed on the market by us, conform ...

  • Dimplex SI 7CS - page 39

    39 Notes ...

  • Dimplex SI 7CS - page 40

    40 KKW Kulmbacher Klimageräte-Werk GmbH Subject to technical modifications Division Dimplex Fax (0 92 21) 709-589 Am Goldenen Feld 18 ww w .dimplex.de D-95326 Kulmbach ...

Fabbricante Dimplex Categoria Heat Pump

I documenti che otteniamo dal fabbricante del dispositivoDimplex SI 7CS possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Dimplex
- manuali per l’uso SI 7CS
- schede prodotto Dimplex
- opuscoli
- o etichette energetiche Dimplex SI 7CS
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Dimplex SI 7CS.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Dimplex SI 7CS, manuali di manutenzione, brevi manuali o manuali utente Dimplex SI 7CS. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Dimplex SI 7CS.

Manuali per l’uso simili

Manuale completo del dispositivo Dimplex SI 7CS, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Dimplex SI 7CS dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Dimplex SI 7CS.

Il manuale per l’uso completo Dimplex, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Dimplex SI 7CS - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Dimplex SI 7CS, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Dimplex SI 7CS che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Dimplex SI 7CS - che ci dovrebbe aiutare nei primi passi durante l'uso Dimplex SI 7CS
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Dimplex SI 7CS
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Dimplex SI 7CS in un dato paese, se il problema non può essere risolto da noi stessi.