    CATALOG NO. 6200.51O Effective: 04-09-07 Replaces: 05-15-05 Models 2100-4001 P/N 240251 Rev. 16 INST ALLA TION AND OPERA TING INSTRUCTIONS RA YTHERM TM COMMMERCIAL SWIMMING POOL HEA TER Models P-926 to P-1826 and P-2100 to P-4001 This manual should be maintained in legible condition and kept adjacent to the heater or in a safe place for future refe ...

  • Raypak 1287-1758, 2100-4001 - page 2

    Content s SECTION 1: RECEIVING EQUIPMENT SECTION 2: GENERAL SPECIFICATIONS SECTION 3: INSTALLATION INSTRUCTIONS Code Requirements Base Installation Clearances Combustion Air Venting Connections Gas Supply Connections Water connections Controls Wiring Diagrams SECTION 4: SERVICING INSTRUCTIONS General Location of Controls Start-Up Procedures Inspect ...

  • Raypak 1287-1758, 2100-4001 - page 3

    12" Minimu m 12" M inimum 4" Minimum HEA TER Sheet Metal 24 Gauge IMPORTANT NOTICE These instructions are intended for the use of qualified personnel only, specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by som ...

  • Raypak 1287-1758, 2100-4001 - page 4

    4 Fig. #8245 CLEARANCES ALL HEATERS For clearances from combustible surfaces, see chart below. We require a minimal vertical clearance of three feet between the upper surface of the flue outlet to a non- combustible material. MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTION INDOOR HEATERS Top - 24" *Vent - 6" Back - 24" Right Side - ...

  • Raypak 1287-1758, 2100-4001 - page 5

    5' MIN 2' MIN 10' OR LESS 2' MIN VENT CAP VENT PIPE DRAFT HOOD HEA TER For protection against rain or blockage by snow, the vent pipe must terminate with a vent cap which complies with the local codes or, in the absence of such codes, to the latest edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54. The discharge opening ...

  • Raypak 1287-1758, 2100-4001 - page 6

    (a) Seal any unused openings in the common venting system. (b) Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. (c) Insofar as is practical, close all building doors and windows and all doors be ...

  • Raypak 1287-1758, 2100-4001 - page 7

    GAS PRESSURE REGULATOR The gas pressure regulator is preset and sealed at 4 in. WC for natural gas, and 11 in. WC for propane gas. Between the gas valve and the burners is a 1/8" pipe plug. The pressure at this point, taken with a manometer, should be about 3.7 in. WC natural gas and 10.5 in. WC propane gas. If an adjustment is needed, remove ...

  • Raypak 1287-1758, 2100-4001 - page 8

    When local codes permit the use of less than four feet high temperature piping or two elbows, provisions should be made to always shut the heater off a minimum of 15 minutes prior to pump shut down in order to carry away residual heat and prevent damage to the low temperature piping. A fireman switch included in the time clock may be used for this ...

  • Raypak 1287-1758, 2100-4001 - page 9

    9 MODELS 1287/1336 - 1758/1826 Inlet/Outlet Header 2-1/2" Inlet 2-1/2" Outlet 1-1/2" Slip Ball Valve 2" Slip Ball Valve 3" Outlet Fig. #9270 Fig. #9200 Pump 3" Inlet 2 H.P. Pump Inlet/Outlet Header MODELS 2100-4001 FLOW RATES/WATER CONNECTIONS MODEL CONNECTION SIZE MIN GPM MAX GPM 926-1223 * 6 0 120 1287-1826 2-1/2&quo ...

  • Raypak 1287-1758, 2100-4001 - page 10

    10 Raypak recommends the installation of an air bleed vent at a suitable location (usually the highest point) to remove air from the piping system. These units should be available at your local wholesale supplier. Raypak does not provide this item. CAUTION: Power to the heater should be interlocked with the main system pump to make sure the heater ...

  • Raypak 1287-1758, 2100-4001 - page 11

    Note: The drawings and instructions above show only one of several acceptable ways of installing the dry well into main system loop. The use of saddle clamps and “Weld O Lets” (shown in Fig. 10) are acceptable. Follow clamp manufacturer’s instructions. MOUNTING WELL INTO SYSTEM RETURN LOOP PIPE - FRONT-MOUNTED LOOP: Note: For more detail on p ...

  • Raypak 1287-1758, 2100-4001 - page 12

    4. If the heater inlet temperature remains less than 100°F and Valve "A" is fully open, leave Valve "A" fully open and throttle Valve "B" until the heater inlet temperature rises to within the range of 100°F-105°F. 5. The resultant heater outlet temperature should be in the range of 120-130°F. 6. As the pool temper ...

  • Raypak 1287-1758, 2100-4001 - page 13

    Models 2100 thru 4001 13 PIPING CONFIGURATIONS FOR RAYTHERM COMMERCIAL POOL HEATERS Fig # 9268 Fig # 9269 BLENDED WATER TEMPERATURE (THERMOMETER AT HEATER INLET) HEATER OUTLET TEMPERATURE THERMOMETER HEATER THERMOSTAT RECOMMENDED FIELD INSTALLED ISOLATION VALVES FOR SERVICE T I T o T c ...

  • Raypak 1287-1758, 2100-4001 - page 14

    14 EXTERNAL AUXILIARY BYPASS VALVE (Where Required) 926-1223 Models only An auxiliary bypass valve should be used when flow rates exceed 120 GPM (usually a high performance pump size larger than two HP will exceed this flow rate). This valve is required to complement the function of the automatic bypass valve, particularly when starting the heater ...

  • Raypak 1287-1758, 2100-4001 - page 15

    15 HIGH & LOW GAS PRESSURE SWITCHES Pressure switches sense either high or low gas pressure and automatically shut down burners if abnor- mal pressures exsist. Standard on Models 3001-4001. PRESSURE SWITCH GAS MANIFOLD Fig. #8236 ELECTRICAL WIRING CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause i ...

  • Raypak 1287-1758, 2100-4001 - page 16

    16 WIRING DIAGRAM MODELS 926 - 1223 ...

  • Raypak 1287-1758, 2100-4001 - page 17

    17 WIRING DIAGRAM MODELS 1287-1826 ...

  • Raypak 1287-1758, 2100-4001 - page 18

    WIRING DIAGRAM MODELS 2100-2500 18 ...

  • Raypak 1287-1758, 2100-4001 - page 19

    WIRING DIAGRAM MODELS 3001-4001 19 ...

  • Raypak 1287-1758, 2100-4001 - page 20

    TEMPERATURE CONTROL The pool water temperature is controlled by the pool thermostat. The heater water temperature high limit is controlled by the manual reset high limit. PRESSURE SWITCH The pressure switch, or heater actuator, ensures that the heater operates only when the filter pump is in operation. It is factory set at 1.75 PSI for deck level i ...

  • Raypak 1287-1758, 2100-4001 - page 21

    ADJUSTMENT KNOB Fig. # 8069.1 PRESSURE SWITCH ADJUSTMENT RANGE HEAT EXCHANGER HEIGHT 5' Max 5' Max Fig. # 8152.0 NOTE: If heater is installed outside of the limits shown, a flow switch must be used in place of the pressure switch when mounted and wired adjacent to the heater. TWO-SPEED PUMPS In some cases, the flow on the low speed is ins ...

  • Raypak 1287-1758, 2100-4001 - page 22

    AFTER START-UP Pilot System Checkout Procedure 1. Turn on power to the ignition systems and turn gas supply off. 2. Check ignition module as follows: a. Set the thermostat above pool water temperature to turn heater on. b. Watch for continuous spark at the pilot burner. c. Time the spark operation. Time must be within the lockout timing period (15 ...

  • Raypak 1287-1758, 2100-4001 - page 23

    SERVICING PROCEDURES TUBE CLEANING PROCEDURE (TYPICAL) Establish a regular inspection schedule, the fre- quency depending on the local water condition and severity of service. Do not let the tubes clog up solidly. Clean out deposits over 1/16" in thickness. Although the illustration shows the mechanical clean- ing procedure of a small boiler, ...

  • Raypak 1287-1758, 2100-4001 - page 24

    5. Remove heat exchanger corner brackets. 6. Remove combustion chamber clips at the four corners of the heat exchanger. 7. Lift heat exchanger straight up using caution not to damage refractory. HEAT EXCHANGER REASSEMBLY 1. Heat exchanger header O-rings should be replaced with new ones. 2. Install inlet-outlet and return water headers and install h ...

  • Raypak 1287-1758, 2100-4001 - page 25

    CONTROL WELL REPLACEMENT Remove top, sensing bulb and clip. Collapse well tube at the open end and with a chisel, push through into the header, and remove the well through header. Insert a new well and roll into place. If a roller is not available, solder the well in place with silver solder. IMMERSION WELL 25 Fig. #8126.0 TUBE REPLACEMENT PROCEDUR ...

  • Raypak 1287-1758, 2100-4001 - page 26

    MODELS 926-1223 UNITHERM GOVERNOR INLET/OUTLET HEADER OUTLET INLET Fig. #8224.0 GASKET UNITHERM GOVERNOR WITH POWER ELEMENT MODELS 1287-1826 (Models prior to Jan. '95) DOUBLE EXTERNAL U.G. MODELS 2100-4001 (Models prior to Jan. '95) EXTERNAL U.G. To test operation of Unitherm Governor, place in hot water and watch for movement against spr ...

  • Raypak 1287-1758, 2100-4001 - page 27

    SECTION 5 / TROUBLESHOOTING GUIDE IMPORTANT NOTICE These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by some states to be licensed. Persons not qualif ...

  • Raypak 1287-1758, 2100-4001 - page 28

    Outer jacket very hot (paint blistered) *Broken refractory caused by shipping damage or improper combustion………………………….. Excessive sooting of heat exchanger…………………………... Calculate temperature in °F/hr……... Filter not running long enough…….... Dirty filter…………………………….. Gas line or ...

  • Raypak 1287-1758, 2100-4001 - page 29

    WARNING HIGH VOLTAGE For qualified Technicians ONLY NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater. NOTE: Before troubleshooting, familiarize yourself with the start-up and checkout procedure. Check line voltage power, low voltage transformer, limit co ...

  • Raypak 1287-1758, 2100-4001 - page 30

    SECTION 6 / REPLACEMENT PARTS LIST NOTE: To supply the correct part it is important that you state the model number, serial number and type of gas when applicable. Any part returned for replacement under standard company warranties must be properly tagged with RAYPAK return parts tag, completely filled in with the heater serial number, model number ...

  • Raypak 1287-1758, 2100-4001 - page 31

    MODELS: 926/962, 1083/1125, 1178/1223, 1287/1336, 1414/1468, 1571/1631, 1758/1826 31 2-C ...

  • Raypak 1287-1758, 2100-4001 - page 32

    32 ...

  • Raypak 1287-1758, 2100-4001 - page 33

    33 ...

  • Raypak 1287-1758, 2100-4001 - page 34

    MODELS: 2100, 2500, 3001, 3500, 4001 34 ...

  • Raypak 1287-1758, 2100-4001 - page 35

    35 ...

  • Raypak 1287-1758, 2100-4001 - page 36

    36 ...

  • Raypak 1287-1758, 2100-4001 - page 37

    37 LIMITED W ARRANTY RA YTHERM TYPE P SIZES 0926-4001 SCOPE: Raypak, Inc. (“Raypak”) warrants to the original owner that all parts of this heater which are actually manufactured by Raypak will be free from failure under normal use and service for the specified warranty periods and subject to the conditions set forth in this W arranty . Labor ch ...

  • Raypak 1287-1758, 2100-4001 - page 38

    Raypak, Inc. , 2151 Eastman Avenue, Oxnard, CA 913030 (805) 278-5300 FAX (800) 872-9725 Raypak Canada LTD , 2805 Slough Street, Mississauga, Ontario, Canada L4T 1G2 (905) 677-7999 FAX (905) 677-8036 Litho in U.S.A. www .raypak.com ...

Fabbricante Raypak Categoria Swimming Pool Heater

I documenti che otteniamo dal fabbricante del dispositivoRaypak 1287-1758, 2100-4001 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Raypak
- manuali per l’uso 1287-1758, 2100-4001
- schede prodotto Raypak
- opuscoli
- o etichette energetiche Raypak 1287-1758, 2100-4001
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Raypak 1287-1758, 2100-4001.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Raypak 1287-1758, 2100-4001, manuali di manutenzione, brevi manuali o manuali utente Raypak 1287-1758, 2100-4001. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Raypak 1287-1758, 2100-4001.

Manuali per l’uso simili

Manuale completo del dispositivo Raypak 1287-1758, 2100-4001, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Raypak 1287-1758, 2100-4001 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Raypak 1287-1758, 2100-4001.

Il manuale per l’uso completo Raypak, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Raypak 1287-1758, 2100-4001 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Raypak 1287-1758, 2100-4001, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Raypak 1287-1758, 2100-4001 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Raypak 1287-1758, 2100-4001 - che ci dovrebbe aiutare nei primi passi durante l'uso Raypak 1287-1758, 2100-4001
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Raypak 1287-1758, 2100-4001
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Raypak 1287-1758, 2100-4001 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Raypak 1287-1758, 2100-4001?

Utilizza il modulo sottostante

Se non hai risolto il problema con Raypak 1287-1758, 2100-4001 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Raypak 1287-1758, 2100-4001 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)