    Model Programming Choices 1F95-1291 7 Day 5+1+1 Day Non-Programmab le www .white-rodgers .com www .emersonclimate .com Big Blue Humidity Univ er sal T her mostat with Humidity/Dehumidity Control and Automa tic Heat/Cool Changeo v er Option P ART NO . 37-7313B Replaces 37-7313A 1241 Single Stage, Multi-Stage, Heat Pump Installation and Operating Ins ...

  • Emerson Process Management 1F95-1291 - page 2

    2 Remove Old Thermostat Bef ore removing wires from old thermostat, mar k wires f or terminal identification so the proper connections will be made to the new thermostat. Installing New Thermostat 1. Pull the thermostat body off the ther mostat base. Forcing or pr ying on the thermostat will cause damage to the unit. 2. Place base ov er hole in wa ...

  • Emerson Process Management 1F95-1291 - page 3

    3 WIRING DIA GRAMS Figure 2 – Single Stage or Multi-Stage System (No Heat Pump) with Single T ransformer Single Stage 1 (SS1) Multi Stage 2 (MS2) System RC RH CY Y2 W/E W2 G O/B 6L CLASS II TRANSFORMER HO T 24V AC NEUTRAL 120V AC Call for heat Heat mode-1st stage Heat mode-2nd stage No output 24 vo lt po wer f or cooling 24 vo lt po wer f or heat ...

  • Emerson Process Management 1F95-1291 - page 4

    4 If you ha v e a single stage compressor system see the dia- gram belo w . A relay (customer provided) should be installed as shown in Fig 7 to s witch the fan speed to the ne xt lower speed on a call f or dehumidification from the ther mostat. The reduction in air flow allo ws the coil to remov e more humidity from the air . The rela y should b ...

  • Emerson Process Management 1F95-1291 - page 5

    5 Programming and Configuration Items 1 Displa ys and "Keypad Loc kout" when in ke ypad lock out mode. Displa ys and "T emperature Limit" and "Keypad Lock out" when limited range is activ ated and lock ed. Displa ys only "T emperature Limit" when limited range is activated. 2 Indicates per iod of da y being ...

  • Emerson Process Management 1F95-1291 - page 6

    6 INST ALLER/CONFIGURA TION MENU T o enter the menu: Press the Menu touch k ey . Press and hold f or 5 seconds the Installer Config touch ke y . This displays screen ref erence #1 in the table belo w . Screen Reference numbers appear in top right corner of display . Press to advance to the ne xt menu item or to return to a previous men u item. Pre ...

  • Emerson Process Management 1F95-1291 - page 7

    7 INST ALLER/CONFIGURA TION MENU 1. This control can be configured for: MS2 – Multi-Stage System (2 heat/2 cool) HP1 – Heat Pump with one stage of compressor (2 heat/1 cool) HP2 – Heat Pump with two stage compressor or two compressor system, Gas or Electric backup; (Dual Fuel see screen ref erence number 33) (4 heat/2 cool) SS1 – Single St ...

  • Emerson Process Management 1F95-1291 - page 8

    8 a time dela y built in and do not require this f eature to be activated in the thermostat. Y our compressor manuf actur- er can tell you if this loc kout f eature is already present in their system. When the ther mostat compressor time dela y is activated, it will flash the set point f or up to five minutes . 12. Select Continuous Displa y Ligh ...

  • Emerson Process Management 1F95-1291 - page 9

    9 Skip this step and continue through the remainder of the configuration menu if y ou require an Air Filter Change out indicator or Humidifier P ad Change out indicator by pressing the key to adv ance. Return to this point when you are ready to star t your selected lock-out and contin ue by: Pressing or k eys to select y our ke ypad lock out comb ...

  • Emerson Process Management 1F95-1291 - page 10

    10 “HM” terminal) if the actual humidity is below the humid- ity set point. The display indicates AH . Pressing the ke y will cycle the displa y from OFF to H (f eature enabled in Heat mode) to C (f eature enabled in Cool mode) to A (f eature enabled to A uto mode) and back to OFF . 42. Cycle Humidifier (CH) – This f eature provides an op- t ...

  • Emerson Process Management 1F95-1291 - page 11

    11 Emergency Mode Applies only to Heat Pump Systems Emergency Heat (System EM P osition) bypasses the Heat Pump to use the heat source wired to terminal W/E, W2 on the thermostat. EM is typically used when compressor opera- tion is not desired, or you pref er back-up heat only . 1. Press SYSTEM key to select EM . “EM Heat Mode” will flash on t ...

  • Emerson Process Management 1F95-1291 - page 12

    12 PR OGRAMMING Set Current Time and Day 1. Press Menu ke y to enter installer menu. Then press Set Time once to indicate hour & AM or PM designation in clock displa y . 2. Press and hold either the or touch k ey until y ou reach the correct hour and AM or PM designation. 3. Press Set Time again to displa y minutes only in clock displa y . 4. P ...

  • Emerson Process Management 1F95-1291 - page 13

    13 PR OGRAMMING Planning Y our Program – Important The Heating and Cooling Program schedules belo w allow y ou to pencil in your o wn program times and temper atures. The 1F95-1291 comes configured f or 7 day prog ramming and can also be configured f or 5+1+1 programming (see configur a- tion section). F actor y settings are listed on Monday , ...

  • Emerson Process Management 1F95-1291 - page 14

    14 PR OGRAMMING Cooling Program W ake Up (Morning) Fan Leave For W ork (Day) Fan Return Home (Evening) Fan Go T o Bed (Night) Fan MON 6:00 AM 75°F A uto 8:00 AM 83°F A uto 5:00 PM 75°F Auto 10:00 PM 78°F A uto TUE WED THU FRI S AT 6:00 AM 75°F A uto 8:00 AM 83°F A uto 5:00 PM 75°F Auto 10:00 PM 78°F A uto SUN 6:00 AM 75°F A uto 8:00 AM 83? ...

  • Emerson Process Management 1F95-1291 - page 15

    15 PR OGRAMMING TR OUBLESHOO TING A veraging or Weighting Remote Sensor s The thermostat will weight or av erage the temperature of the indoor remote sensor with the local sensor in the thermostat f or each program period. The av eraging will be active only when the local sensor and the indoor remote sensor are both functional and enabled in the In ...

  • Emerson Process Management 1F95-1291 - page 16

    White-Rodgers is a business of Emerson Electric Co. The Emerson logo is a trademark and ser vice mark of Emerson Electric Co. HOMEO WNER HELP LINE: 1-800-284-2925 Symptom P ossible Cause Corrective Action No Heat/No Cool/No Fan (common problems) 1. Blown fuse or tripped circuit breaker . 2. Fur nace power s witch to OFF . 3. Fur nace blo wer compar ...

Fabbricante Emerson Process Management Categoria Thermostat

I documenti che otteniamo dal fabbricante del dispositivoEmerson Process Management 1F95-1291 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Emerson Process Management
- manuali per l’uso 1F95-1291
- schede prodotto Emerson Process Management
- opuscoli
- o etichette energetiche Emerson Process Management 1F95-1291
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Emerson Process Management 1F95-1291.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Emerson Process Management 1F95-1291, manuali di manutenzione, brevi manuali o manuali utente Emerson Process Management 1F95-1291. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Emerson Process Management 1F95-1291.

Manuale completo del dispositivo Emerson Process Management 1F95-1291, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Emerson Process Management 1F95-1291 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Emerson Process Management 1F95-1291.

Il manuale per l’uso completo Emerson Process Management, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Emerson Process Management 1F95-1291 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Emerson Process Management 1F95-1291, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Emerson Process Management 1F95-1291 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Emerson Process Management 1F95-1291 - che ci dovrebbe aiutare nei primi passi durante l'uso Emerson Process Management 1F95-1291
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Emerson Process Management 1F95-1291
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Emerson Process Management 1F95-1291 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Emerson Process Management 1F95-1291?

Utilizza il modulo sottostante

Se non hai risolto il problema con Emerson Process Management 1F95-1291 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Emerson Process Management 1F95-1291 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)