    R-410A AFFINITY SERIES DNX024-048 2-4 Ton GZKDJRRJDGHZ2[JZFJR 279550-YIM-A-0207 TABLE OF CONTENTS General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • York AFFINITY SERIES R-410A - page 2

    279550-YIM-A-0207 2 Unitary Products Group Due to system pressure, movi ng parts, and electrical components, installation and servicing of air condition ing equipment can be hazardous. Only qualified, tra ined service personnel should install, repair, or service this equipment. Untrained personnel can perform basic maintenance functi ons of cleanin ...

  • York AFFINITY SERIES R-410A - page 3

    279550-YIM-A-0207 Unitary Products Group 3 3. For installation on combustible material and may be installed directly on combustibl e flooring or, in the U.S., on wood flooring or Class A, Class B or Class C roof covering materials. 4. For use with natu ral gas (convertible to LP with kit). Nomenclature Installation Installation Safety Information R ...

  • York AFFINITY SERIES R-410A - page 4

    279550-YIM-A-0207 4 Unitary Products Group In Canada: 1. Canadian El ectri cal Code, CSA C22.1 2. Installation C odes, CSA - B149.1. 3. Local plumbi ng and waste wate r codes, and 4. Other applica ble lo cal codes. Refer to unit appli cation da ta found in this documen t. After installation, gas fired units must be adjusted to obtain a temperature ...

  • York AFFINITY SERIES R-410A - page 5

    279550-YIM-A-0207 Unitary Products Group 5 Location Use the following guidel ines to se lect a suitable location for these units: 1. Unit is designed for outdoor installatio n only . 2. Condenser coils must have an unlimited supply of air. Where a choice of location is possible , po sition the unit on either north or east side of building. 3. Suita ...

  • York AFFINITY SERIES R-410A - page 6

    279550-YIM-A-0207 6 Unitary Products Group Figure 2: Unit 4 Point Load Weight ; &(17(52) *5$ 9,7<  )5217 2) 81,7 <  ' & % $ Table 2: Weights and Dimens ions Size (Tons) Weight (lbs.) Center of Gravi ty 4 Point Load Location (lb s.) S h i p p i n g O p e r a t i ...

  • York AFFINITY SERIES R-410A - page 7

    279550-YIM-A-0207 Unitary Products Group 7 Figure 3: Unit Dimensions $ %  9(17$,5287/(7+22' %/2:(56(59,&($&&(66 &203$570(173$1(/ *$66833/< ',$0(7(5+2/( 137,&211(&7,21 81,7&21'(16$7( &211(&7,21137,? ...

  • York AFFINITY SERIES R-410A - page 8

    279550-YIM-A-0207 8 Unitary Products Group Figure 4: Di men sions Front and Bottom Figure 5: Dimen sions Back and Bottom      )5217 *$66833/ < ',$.12&.287 137,&211(&7,21 /2:92/ 7 $*( &211? ...

  • York AFFINITY SERIES R-410A - page 9

    279550-YIM-A-0207 Unitary Products Group 9 Figure 6: Roof Curb 1 Ductwork These units are adaptable to downflow use as wel l as rear supply and return air duct openings. To convert to downflow, use the following steps: 1. Remove the duct covers fo und in the bottom re tu rn and supply air duct openings. There are four (4) screws securing each duct ...

  • York AFFINITY SERIES R-410A - page 10

    279550-YIM-A-0207 10 Unitary Products Group Service Acces s Access to all serviceable components is provided at the following locations: • Blower compartment access panel • Gas control/electrical access panel • Refrigerant connections Refer to Figure 3 for location of these access locations and minimum clearances in Table 5. Refer to Figure 2 ...

  • York AFFINITY SERIES R-410A - page 11

    279550-YIM-A-0207 Unitary Products Group 11 Figure 8: Ty pical Field Control W iring Diagra m Single Stage Thermostat - Two Stage Gas Hea t Figure 9: Ty pical Field Control W iri ng Diagram Two Stage Thermostat - Single Stage Gas Heat R G W R G C Y 1 Y W 2 W 1 C Y/Y 2 ** = Minimum wire size of 18 AWG wire should be used for all field installed 24 v ...

  • York AFFINITY SERIES R-410A - page 12

    279550-YIM-A-0207 12 Unitary Products Group Figure 10: Typi cal Field Control Wirin g Diag ram Two Stage Thermostat - Two Stage Gas Heat Figure 11: Typical Fiel d Power Wiring Diagram R G W 1 R G C Y 1 Y 1 W 1 C Y 2 Y/Y 2 W 2 W 2 ** = Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire. PROGRAMMABLE THERMOSTAT ONLY ...

  • York AFFINITY SERIES R-410A - page 13

    279550-YIM-A-0207 Unitary Products Group 13 DNX024-048 Single Stage Gas Heat Component Models DNX024 DNX036 DNX048 Nominal Tonnage 2.0 3.0 4.0 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) 24.6 38.4 50.0 ARI net capacity (Btu) 24.0 37.0 48.0 EER 11.5 12.3 11.2 SEER 15.0 16. 5 15.0 Nominal CFM 800 1275 1550 System power (KW) 2.1 3.0 4.3 ...

  • York AFFINITY SERIES R-410A - page 14

    279550-YIM-A-0207 14 Unitary Products Group DNX024-048 Two Stage Gas Heat Component Models DNX024 DNX036 DNX048 Nominal Tonnage 2.0 3.0 4.0 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) 24.6 38.4 50.0 ARI net capacity (Btu) 24.0 37.0 48.0 EER 11.5 12.3 11.2 SEER 15.0 16. 5 15.0 Nominal CFM 800 1275 1550 System power (KW) 2.1 3.0 4.3 Re ...

  • York AFFINITY SERIES R-410A - page 15

    279550-YIM-A-0207 Unitary Products Group 15 Compressors The scroll compressor used in this product is specifically designed to operate w ith R-410A Refrigerant and cannot b e interchanged. The compressor also uses a polyolester (POE oil), Mo bil 3MA POE. This oil is e xtremely hydroscopic, meaning it absorbs water readily. POE oil can absorb 15 tim ...

  • York AFFINITY SERIES R-410A - page 16

    279550-YIM-A-0207 16 Unitary Products Group 4. All piping should be cleane d of dirt and scale by hammering on the outside of the pipe and blo wing out the loose dirt and scale. Before init ial start-up, be sure that all of the gas lines external to the unit have been purged of air. 5. The gas supply should be a separate lin e and in stalled in acc ...

  • York AFFINITY SERIES R-410A - page 17

    279550-YIM-A-0207 Unitary Products Group 17 Table 9: Natural Gas Applic ation Data-Single Stage Available On Models Input (MBH) 1 1. Heating capacity valid for elevations up to 20 00 feet above sea level. For elevati ons above 2,000 feet, rated capacity should be r educed by 4% for each 1,000 feet above sea level. Output (MBH) Gas Rate 2 Ft. 3 /Hr. ...

  • York AFFINITY SERIES R-410A - page 18

    279550-YIM-A-0207 18 Unitary Products Group Airflow Performanc e Table 13: Side Duct Application Size (Tons) Mode Thermostat Input Speed Tap CFM External Static Pre ssure (Inch Water Gauge) 0 . 20 . 30 . 40 . 50 . 60 . 70 . 80 . 91 . 0 Watts Watts Watts Watts Watts Wat ts Watts Watts Watts 024 (2.0) Cool Low Y1 COOL-A 600 100 122 1 45 169 194 221 2 ...

  • York AFFINITY SERIES R-410A - page 19

    279550-YIM-A-0207 Unitary Products Group 19 048 (4.0) Heat N065 W1 HEAT-A 1200 330 373 416 461 507 554 - - - W1 HEAT-B 1300 394 439 484 531 579 629 - - - W1 H EAT-C 1400 466 513 561 611 663 715 - - - W1 H EAT-D 1500 544 596 648 702 758 815 - - - N090 W1 HEAT-A 1325 412 456 503 550 599 649 - - - W1 HEAT-B 1400 466 513 561 611 663 715 - - - W1 H EAT- ...

  • York AFFINITY SERIES R-410A - page 20

    279550-YIM-A-0207 20 Unitary Products Group 036 (3.0) Cool Low Y1 COOL-A 900 198 233 2 72 313 358 406 458 512 5 69 Y1 COOL-B 760 166 190 2 22 262 310 366 431 503 5 84 Y1 CO OL-C 830 180 210 245 286 332 384 441 503 571 Y1 CO OL-D 970 221 260 302 344 388 434 481 530 579 High Y1+Y2 COOL-A 1250 361 408 454 501 548 594 640 687 733 Y1+Y2 COOL-B 1050 253 ...

  • York AFFINITY SERIES R-410A - page 21

    279550-YIM-A-0207 Unitary Products Group 21 Blower Speed Select ion The variable speed blowe rs are designed to deliver constant CFM regardless of the external static pressure (ESP) in the ductwork. Therefore, if too many supply registers are closed, a filter becomes clogged, or there is a restriction in the ductwork, the motor will automatically o ...

  • York AFFINITY SERIES R-410A - page 22

    279550-YIM-A-0207 22 Unitary Products Group The “Heat” Jumper on the CFM selection board shou ld be set to “A”. Fan Only CFM: When the connectio n is made fr om “R” to “G”, the fan only mode is activated. In this mode , the blower will deliver 75% of the cooling system CFM. This conn ection is factory set from the manufacturer, but ...

  • York AFFINITY SERIES R-410A - page 23

    279550-YIM-A-0207 Unitary Products Group 23 Main Burner Operatio n High Heat Warm-up Two stage models run high heat for the first 60 se conds following Pilot Flame Stabil ization period regardless of W2 demand. If W2 is not energized at the end of this 60 second period the control de energizes the high gas output and steps the inducer to l ow speed ...

  • York AFFINITY SERIES R-410A - page 24

    279550-YIM-A-0207 24 Unitary Products Group Welded Gas Valve Relay Response. If either or both Pilo t and Main Gas valve outputs are sensed to be off for more than 1 seconds when commanded to be on th e control board shuts off all outputs and enters a hard lockout If the Pilot valve or Main valve output is sensed to be energi zed for more than 1 se ...

  • York AFFINITY SERIES R-410A - page 25

    279550-YIM-A-0207 Unitary Products Group 25 Circulating Fa n When the thermostat calls for FAN, the thermostat terminal G is energized signaling the circulating fa n to run at the heat speed 2 seconds after the G terminal is energized. If a call for HEAT occurs, the circ ulating fan continues to run at the heat speed. If a call for COOL occurs, the ...

  • York AFFINITY SERIES R-410A - page 26

    279550-YIM-A-0207 26 Unitary Products Group Figure 16: Two Stage Gas Valve Front Figure 17: Single Stage Gas Valve Rear Figure 18: Two Stage Gas Valve Rear Adjust as follows: 1. Remove the cap from the valve body. See Figures 15 and 16 for location. 2. To decrease the gas pressure, turn th e adjusting screw counterclockwise. 3. To increase the gas ...

  • York AFFINITY SERIES R-410A - page 27

    279550-YIM-A-0207 Unitary Products Group 27 Adjustment of Temperature Ris e After about 20 minutes of high heat operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts about six feet from the furnace where they will not be affected by radiant heat. The temperature rise (or temperature ...

  • York AFFINITY SERIES R-410A - page 28

    279550-YIM-A-0207 28 Unitary Products Group Typical Wiring Diagrams Typical DNX024 Cooling Un it with Single Stag e Gas Heat 208/230-1-60 volt Wiring Diagram ...

  • York AFFINITY SERIES R-410A - page 29

    279550-YIM-A-0207 Unitary Products Group 29 Typical DNX024 Coolin g Unit with Two Stag e Ga s Heat 208/230-1-60 volt Wiring Diagram ...

  • York AFFINITY SERIES R-410A - page 30

    279550-YIM-A-0207 30 Unitary Products Group Typical DNX036-048 Cooling Unit with Single St age Gas Hea t 20 8/230-1 -60 volt Wiring Diagram ...

  • York AFFINITY SERIES R-410A - page 31

    279550-YIM-A-0207 Unitary Products Group 31 Typical DNX036-048 Cooling Unit with Two Stage Gas Hea t 208/230 -1-60 volt Wiring Diagram ...

  • York AFFINITY SERIES R-410A - page 32

    279550-YIM-A-0207 32 Unitary Products Group Typical DNX036-048 Cooling Unit with Single St age Gas Hea t 20 8/230-3 -60 volt Wiring Diagram ...

  • York AFFINITY SERIES R-410A - page 33

    279550-YIM-A-0207 Unitary Products Group 33 Typical DNX036-048 Cooling Unit with Two Stage Gas Hea t 208/230 -3-60 volt Wiring Diagram ...

  • York AFFINITY SERIES R-410A - page 34

    279550-YIM-A-0207 34 Unitary Products Group Typical DNX036-048 Cooling Unit with Single St age Gas Hea t 460-3-60 volt Wiring Diagram ...

  • York AFFINITY SERIES R-410A - page 35

    279550-YIM-A-0207 Unitary Products Group 35 Typical DNX036-048 Cooling Unit with Two Stag e Gas Heat 460-3-60 volt Wiring Diagram ...

  • York AFFINITY SERIES R-410A - page 36

    Subject to change without notice. Print ed in U. S.A. 279550-YIM-A-0207 Copyright © 2007 by Unitary Products Grou p. All rights reserved. Supersedes: 98811-YI M-C-1006 Unitary 5005 Norman Products York OK Group Drive 73069 Figure 20: R-410A Quick Reference Guide R-410A QUICK REFERENCE GUIDE Refer to Installation Instruction s for specific installa ...

Fabbricante York Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoYork AFFINITY SERIES R-410A possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici York
- manuali per l’uso AFFINITY SERIES R-410A
- schede prodotto York
- opuscoli
- o etichette energetiche York AFFINITY SERIES R-410A
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso York AFFINITY SERIES R-410A.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione York AFFINITY SERIES R-410A, manuali di manutenzione, brevi manuali o manuali utente York AFFINITY SERIES R-410A. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto York AFFINITY SERIES R-410A.

Manuali per l’uso simili

Manuale completo del dispositivo York AFFINITY SERIES R-410A, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare York AFFINITY SERIES R-410A dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti York AFFINITY SERIES R-410A.

Il manuale per l’uso completo York, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale York AFFINITY SERIES R-410A - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice York AFFINITY SERIES R-410A, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per York AFFINITY SERIES R-410A che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo York AFFINITY SERIES R-410A - che ci dovrebbe aiutare nei primi passi durante l'uso York AFFINITY SERIES R-410A
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del York AFFINITY SERIES R-410A
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio York AFFINITY SERIES R-410A in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su York AFFINITY SERIES R-410A?

Utilizza il modulo sottostante

Se non hai risolto il problema con York AFFINITY SERIES R-410A con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con York AFFINITY SERIES R-410A è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)