    SAFETY CONSIDERA TIONS Due to system pr essure, moving par ts and electr ical components, installation and ser vicing of air conditioning equipment can be hazardous. Only qualified, trained, serv ice personnel should install, repair , maintain or service this equipment. ‘Y ORK Model D CE an d DC G uni ts a re si ngle pac kag e ai r condit io ners ...

  • York D2CG300 - page 2

    Gene ral ... .... .... .... ...... .... .... .... ...... .... .... .... .... ...... .... .... .... .... ... 1 Inspe ction........ ...... .... .... .... .... ...... .... .... .... ...... .... .... .... .... ...... . 1 Referen ce ... ...... .... .... .... ...... .... .... .... ...... .... .... .... ...... .... .... .... .. 1 App rovals ..... .... ... ...

  • York D2CG300 - page 3

    LIMIT A TIONS These unit s must be inst alle d in ac corda nce wit h the following applic ab le nation al a nd loc al s af ety cod es: In U .S.A. : 1. Nation al Elec trical C od e ANSI/ NFP A No . 70. 2. Na tional Fue l Gas Code Z22 3.1. 3. Gas -Fir ed Ce ntral Fu r na ce Stan dar d ANS I Z21.47 a. 4. Loca l gas an d elec tr i c util ity req uir em ...

  • York D2CG300 - page 4

    DUCTWO RK Duct wor k shou ld b e de signed and sized acco rding to th e method s in Man ual Q of th e Air Con diti oning Co ntra ctors of America (ACCA). A clos ed re tur n du ct sys tem shal l be use d. Thi s shall no t prec lude us e of ec onomizers or outdoo r fresh air inta k e. The suppl y and retur n air du ct co nnec tions a t the unit sh ou ...

  • York D2CG300 - page 5

    FIG. 5 - TYPICAL FIELD WIRING Wire Size 1 A WG. Gaug e 22 20 19 18 16 25 40 50 65 100 Maximu m Wire Length 2 Fe et Notes: 1. Solid, Class II copper wire CONTR OL WIRE SIZES 530.18-N11Y Unitar y Products Group 5 ...

  • York D2CG300 - page 6

    THERMOST A T The roo m thermost at sh ould be lo cate d on a n insid e w all appro ximatel y 56" ab ov e the fl oor whe re it wi ll no t be sub ject to dr afts, sun expos ure o r h eat fr om el ectr i cal f ixtu res or applia nces . Follo w manuf acturer’ s inst ruction s enclos ed with ther mostat f or general installation procedure. Sev en ...

  • York D2CG300 - page 7

    W ARNING : Nat ural gas ma y conta in som e pro pane . Prop ane , bein g an e xcellen t sol v ent , will qui c kly dissol v e whit e lead o r most standard commercial com pounds. Th ere fore, a special pi pe com poun d must be ap plie d when wr ough t iron or steel pip e is used. Shellac b as e c om po unds su ch as G as k olac or Stala stic , and ...

  • York D2CG300 - page 8

    VENT AND COMBUSTION AIR HOO DS (DCG Models) T wo ven t hoo ds and a comb ustion air hood (with screen s) are sh ipp ed atta ched to th e blower hou sing in th e blower compartment. These hoo ds mus t be i nstall ed to assure proper unit funct ion. All hoods m ust be f ast ened to the outsid e of t he gas heat acc ess panel w ith the sc rews provi d ...

  • York D2CG300 - page 9

    FIG. 9 - ENTHAL PY SETP OINT AD JUST MENT 530.18-N11Y Unitar y Products Group 9 ...

  • York D2CG300 - page 10

    T ABLE 4 - P HYSIC AL D A T A MODE LS DCE/DCG 300 EV APORA T OR BLOWER CENTRIFUGAL BLO WER (Dia. x W d. in.) 18 x 15 F AN MO TOR HP 15 EV APORA T OR COIL RO W S DEEP 4 FINS PER INCH 13.5 F A CE AREA (Sq. Ft. ) 25.0 CONDENSER FA N (T wo P er Unit) PRO PELLER DIA. (in.) (Each) 30 F AN MO TOR HP (Each) 1 NOM. CFM TO T AL (Each) 7200 CONDENSER COIL RO ...

  • York D2CG300 - page 11

    Cont ’ d. FIG. 10 - DIMENSIONS & CLEARANCES - DCE & DCG All dimensions are in inches. T hey are sub- ject to change without notice. Cert i fied di- mensions will be pro vided upon request. CLEARANCES F ront 36" Back 24" (Less Economiz er) 49" (With Ec onomizer) Left Side (Filter Access) 24" (Less Economi zer) 36" ...

  • York D2CG300 - page 12

    FIG. 10 - DIMENSIONS & CLEARANCES (Cont ’ d.)- DCE & DCG SUPPLY AIR RETURN AIR OUTDOOR AIR 5-1/8" 18-5/8" 27-3/4" 29-5/8" (15 TON) 39-5/8" (20 TON) 40-1/2" OUTDOOR AIR COMPARTMENT ACCESS FILTER ACCESS 1" NPT FEMAL E COND. DRAIN CONNECTION DOT PLUG (For pressure drop reading) EVAPORATOR SECTION CONDENSER ...

  • York D2CG300 - page 13

    A B C D FRONT 4 POINT LO ADS FIG. 11 - FOUR AND SIX POINT LO ADS A E D B F C FRONT 6 POINT LO ADS UNIT 4 - PO INT LOADS (LBS) TOT A L A B C D 300 3, 130 615 671 962 882 NOTE: The se w eigh ts a re w ith ec onom izer , high he at, a nd th e larg est blower mot or available. UNIT 6 - POINT LOADS (LBS) TOT A L A B C D E F 300 3,130 418 438 533 628 603 ...

  • York D2CG300 - page 14

    T ABLE 11 - PO WER EXHA UST PERFORMANCE T ABLE 12 - BLO WE R MO TO R AND DRIVE D A T A MODEL SIZE DRIVE BLOWER RANGE (RPM) MO T OR 1 ADJUST ABL E MO T OR PULLEY FIXED BLOWER PULLEY BEL T (NO TCHED) HP FRAME EFF . (%) DESIG- NA TION OUT - SIDE DIA. (IN.) PITCH DIA. (IN.) BORE (IN.) DESIG- NA TION OUTS IDE DIA. (IN.) PITCH DIA. (IN.) BORE (IN.) DESIG ...

  • York D2CG300 - page 15

    COOL ING SYST EM The co oling se ctio n is a com plet e f actory pack age u tili zing an air-cooled condenser . The system is f actor y- charged with Refriger ant-2 2. The co mpres sor s are h er m etical ly se aled , inter nally spr ung and b ase -mou nted with r ubbe r-in sula ted hold -down bolts. Compress ors ha v e inherent (in ternal) prot ec ...

  • York D2CG300 - page 16

    s wit ch is in the “ AUTO ” p osit ion, the blower wi ll op erat e onl y when ther e is a cal l for heating by th e th er m osta t. b) Upon a cal l for first -st age hea t by the the r most at, the he ater con tactor (6M) (6 M & 7M o n 72 KW , 2 40V) will be energiz ed. If the se cond sta ge of he at is req uired , heat er cont actor (7M) w ...

  • York D2CG300 - page 17

    6. A uxili ary Limit Switch (A UX) This c ontro l is loc ated insi de the he at excha nger c ompa r tment and i s set to op en at 190 ° F . It is a manua l rese t switch. If A UX li mit t rip s, then the pr imar y limi t has not fu ncti oned corre ctly ., Repla ce the pr imar y limit OPERA TING INSTRUCT IONS CA UTION: Thi s fu r nac e is eq uipped ...

  • York D2CG300 - page 18

    3. T o increase t he ga s pr essure , tu rn the ad just ing sc re w cloc kw ise . NO TE: The cor rect mani f old pr ess ure f or t hese fur n aces is 3.65 IWG ± 0.3. PILO T CHECK OUT The pilot flame should envelope the end of the flame sensor . Ref er to Proper Flame Adjustment figure. T o adjust pilot flame , (1) remov e pilot adjustment cov er s ...

  • York D2CG300 - page 19

    2. Insert at least 8" of 1/4 inch tubin g into ea ch of th ese hol es f or suf fici ent pe netrat ion in to the air flow on both side s of the indo or coil . NO TE: Th e tube s must be inserted and hel d in a posi tion perpendicu lar to th e air f lo w so t hat v eloci ty p res- sure wil l no t af f ect the st at ic pres su re rea ding s . 3. ...

  • York D2CG300 - page 20

    If the actual input is not within 5% of the fur nace rating (with allowance being made f or the per missible range of the regulator setting), replace the or ifice spuds with spuds of the proper size. NOTE T o find the Btu input, multiply the number of cubic f eet of gas consumed per hour by the Btu content of the gas in your par ticular locality (c ...

  • York D2CG300 - page 21

    10. After b rushing is comp lete , blo w all brushed area s wit h ai r or nitro ge n. V acuum a s ne ed ed . 11 . Replace par ts in the order the y were remo v ed in Steps 1 thru 4. 12. When re plac ing t he ce nter a nd to p of the flue colle ctor box, be car eful not to tear the ad jo inin g insu lati on. 13. Ensure that al l seams on the v ent s ...

  • York D2CG300 - page 22

    4. The draft m otor r uns but the fur nace d oes no t ligh t and th e sparke r does no t sp ark. a. Th e ignition contro l (IC1, IC2) ma y be lock ed out d ue to eithe r a f lame roll ou t or 10 0% shu t off. These sa fety f eature s are d esc ri bed a bove. I f lock- out h as oc curr ed, 24V must be remo v ed from t he igni tion co ntrols . This i ...

  • York D2CG300 - page 23

    REPLA CEMENT P ARTS COMPRESSOR SECTION • Hermetic c ompress or • Compre ssor mo unti ng MO T OR SECTION • Blowe r motor • Fa n m o t o r • V e ntor mo tor ELECTRICAL SECTION • Igniti on con trol • Rela y board • Cont acto r • Circuit bre ak er • T emperat ure con trols • Capacitors • Rela ys • Tr a n s f o r m e r s • Co ...

  • York D2CG300 - page 24

    Unitary Products G roup 5005 Y ork D ri ve, Nor man , Okla homa 73069 Subje ct to chan ge wit hout n otice . Printe d in U .S .A. Cop yright  by Y ork International Corporation 1 999. All Rights Reserved. Code: SBY 530. 18-N1 1Y ...

Fabbricante York Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoYork D2CG300 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici York
- manuali per l’uso D2CG300
- schede prodotto York
- opuscoli
- o etichette energetiche York D2CG300
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso York D2CG300.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione York D2CG300, manuali di manutenzione, brevi manuali o manuali utente York D2CG300. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto York D2CG300.

Manuali per l’uso simili

Manuale completo del dispositivo York D2CG300, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare York D2CG300 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti York D2CG300.

Il manuale per l’uso completo York, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale York D2CG300 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice York D2CG300, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per York D2CG300 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo York D2CG300 - che ci dovrebbe aiutare nei primi passi durante l'uso York D2CG300
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del York D2CG300
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio York D2CG300 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su York D2CG300?

Utilizza il modulo sottostante

Se non hai risolto il problema con York D2CG300 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con York D2CG300 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)