    05/26/06 Freestanding Gas Stove FOR YOUR SAFETY What to do if you smell gas: Do not try to light any appli- ance Do not touch any electrical switch: do not use any phone in your building. Immediately call your gas supplier from a neighbour's phone. Follow the gas sup- plier's instructions. If you cannot reach your gas supplier, call the f ...

  • Regency FG37-NG - page 2

    2 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater To the New Owner: Congratulations! You are the owner of a state-of-the-art Regency Rear Flued Room Sealed Freestanding Gas Stove by FPI Fireplace Products International. The Regency Gas Series of hand crafted appliances has been designed to provide you with all the warmth and charm of a ...

  • Regency FG37-NG - page 3

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 3 T ABLE OF CONTENTS Page Page Operating Instructions Operating Instructions ............................................... 1 9 Lighting Procedure .................................................... 1 9 Resetting the Unit ..................................................... 1 9 Shutdown ...

  • Regency FG37-NG - page 4

    4 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater This is a copy of the label that accompanies each REGENCY Rear Flued Room Sealed Free- standing Gas Stove. We have printed a copy of D A T A PLA TE the contents here for your review. The data plate is located on the inside of the drop down pedestal door. NOTE: Regency units are constantl ...

  • Regency FG37-NG - page 5

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 5 INSTALLATION AND REPAIRS SHOULD BE DONE BY AN AUTHOR- IZED SERVICE PERSON. THIS AP- PLIANCE SHOULD BE INSTALLED, REPAIRED, INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY AN AUTHORIZED SERVICE PER- SON. MORE FREQUENT CLEAN- ING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPET- ING, ETC. I ...

  • Regency FG37-NG - page 6

    6 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 14) Under no circumstances should any solid fuels (wood, paper, cardboard, coal, etc.) be used in this appliance. 15) The appliance area must be kept clear and free of combustible materials, (gases and other flammable vapours and liquids). INST ALLA TI ON CHECKLIST 1) Check Clearances to ...

  • Regency FG37-NG - page 7

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 7 INST ALLA TION EXTERIOR FLUE TERMINA TION LOCA TIONS Minimum clearances required for balanced flue terminals or the flue terminals of outdoor appliances according to AS5601-2004 (AGA gas installation code) or NZS 5261 (New Zealand) Min imum Clearance (mm) a Below eaves, balconies or othe ...

  • Regency FG37-NG - page 8

    8 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater PLANNING YOUR FLUING INST ALLA TION INST ALLA TION FLUING The Regency Room Sealed System (Horizontal Termination Kit (946-110) and the Vertical Ter- mination with the Co-linear Flex System in combination with the REGENCY Room Sealed- Rear Freestanding Gas Stoves (FG37-NG and FG37-LPG) ha ...

  • Regency FG37-NG - page 9

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 9 INST ALLA TION FLUING ARRANGEMENTS - VERTICAL TERMINA TIONS FOR BOTH RESIDENTIAL & MANUF ACTURED HOMES/MOBILE HOMES Offset to Vertical Terminations If connecting to a Dura-Vent sys- tem, the Adapter to Dura-Vent # 640-994 is required. Vertical Terminations with Co-linear Flex System ...

  • Regency FG37-NG - page 10

    10 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater INST ALLA TION Diagram 2 HORIZONT A L INST ALLA TIONS Diagram 1 *Dia 2: Local codes or regulations may require different clearances. RESIDENTIAL AND MANUF ACTURED HOMES/ MOBILE HOMES INST ALLA TIONS You will require the following components with your new Regency Rear Flued Room Sealed F ...

  • Regency FG37-NG - page 11

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 11 Diagram 5 Diagram 4 Below Grade Snorkel Installation If the Snorkel Termination must be installed below grade, i.e. basement application, proper drainage must be provided to pre- vent water from entering the Snorkel Ter- mination. Refer to Dura-Vent Installation instructions for details ...

  • Regency FG37-NG - page 12

    12 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater System Data - FG37 Burner Inlet Orifice Sizes: NG # 37 LPG # 5 2 Max. Input Rating 31.7 mj Min. Input Rating 16 mj Supply Pressure N G min. 1.13 kPa L P G min. 2.75 kPa Manifold Pressure N G .89 kPa L P G 2.55 kPa GAS CONNECTION The gas connection is a 1/2" (13mm) NPT Male Thread. ...

  • Regency FG37-NG - page 13

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 13 INST ALLA TION Conversion Kit for NG to LPG Model #516-969 THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !! Burner Orifice Conversion Kit 516-969 Contains: Qty. Part # Desc ription 1 904-390 Burner Orifice #52 1 908-528 Red "LPG" ...

  • Regency FG37-NG - page 14

    14 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater Installer Notice: These instructions must be left with the appliance. Minimum pressure: Remove one of the cables connected to the electric modulator. Keeping the nut (B) blocked, screw in the screw (C) to increase the pressure and screw it out to decrease it. Use a screw- driver 6 x 1 b ...

  • Regency FG37-NG - page 15

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 15 INST ALLA TION C)02-44 AERA TION ADJUSTMENT The burner aeration is factory set but may need adjusting due to either the local gas supply, air supply or altitude. N G : 10mm open LPG: 10mm open The aeration adjustment gears are located on the right side of the burner box and can be acces ...

  • Regency FG37-NG - page 16

    16 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater Diagram 2 Diagram 3 4) The latches should already be at the proper setting. If they are too hard or too easy to close, you may want to adjust them by loosening the locking nut and turning the latch catch. See diagram 3. 5) Remove the blue plastic protective coat- ing from the glass. 6) ...

  • Regency FG37-NG - page 17

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 17 INST ALLA TION LOUVRE INST ALLA TI ON Attach the top & bottom louvres to the side stove panel using 2 screws per side. GAS PIPE PRESSURE TESTING The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testi ...

  • Regency FG37-NG - page 18

    18 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater FINAL CHECK Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly. This includes: 1) Clocking the appliance to ensure the cor- rect firing rate (rate noted on label) at 15 minutes. 2) If required, adjusting the primary air to ensure ...

  • Regency FG37-NG - page 19

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 19 OPERA TING INSTRUCTIONS FIRST FIRE The FIRST FIRE in your heater is part of the paint curing process. To ensure that the paint is properly cured, it is recommended that you burn your fireplace for at least four (4) hours the first time you use it with the fan on. When first operated, th ...

  • Regency FG37-NG - page 20

    20 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater NORMAL OPERA TING SOUNDS OF GAS APPLIANCES It is possible that you will hear some sounds from your gas appliance. This is perfectly nor- mal due to the fact that there are various gauges and types of steel used within your appliance. Listed below are some examples. All are nor- mal oper ...

  • Regency FG37-NG - page 21

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 21 COPY OF THE LIGHTING PLA TE INSTRUCTIONS OPERA TING INSTRUCTIONS WARNING: DO NOT SPRAY AEROSOLS IN THE VICINITY OF THIS APPLIANCE WHILE IN OPERATION. FOR YOUR SAFETY READ BEFORE LIGHTING A ) BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor ...

  • Regency FG37-NG - page 22

    22 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater MAINTENANCE CAUTION: ANY SAFETY SCREEN OR GUARD REMOVED FOR SERV- ICING AN APPLIANCE MUST BE REPLACED PRIOR TO OPERAT- ING THE APPLIANCE. CLOTHING OR OTHER FLAMMA- BLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLI- ANCE. DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN UNDER WATER. I ...

  • Regency FG37-NG - page 23

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 23 L A TCH ADJUSTMENT The door latch may require adjustment as the door gasket material compresses after a few fires and after glass replacement. Turn the handle on the adjustable catch to tighten or loosen the latch. Installing Glass 1) Install both center and side glass onto extrusions a ...

  • Regency FG37-NG - page 24

    24 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater MAINTENANCE FAN MAINTENANCE If your fan requires maintenance or replace- ment it must be performed by an authorised person. Access to the fan is through the plate on the rear wall of the firebox. NOTE: the unit MUST NOT be operated without the fan access panel securely in place and cor- ...

  • Regency FG37-NG - page 25

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 25 MAINTENANCE 4) Remove the two outside frame pieces by removing two screws per side. See dia- gram below. REMOVING VAL VE TRA Y If your valve requires maintenance or replace- ment, follow these instructions: NOTE: Always shut off the gas and dis- connect the power supply before removing ...

  • Regency FG37-NG - page 26

    26 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater FG37 FG38 FG39 PG33 PG36 HG35 PG121/PG131 910-915 910-082 910-088 910-089 910-084 910-526 910-080 910-521, 910-522, 910-523 910-909 Fan Resistor 910-915 Intermittent Pilot 910-082 Direct Spark Ignitor 910-089 Flame Cable 910-088 Spark Cable 910-084 Control Box 910-526 Manual Control 910 ...

  • Regency FG37-NG - page 27

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 27 P ARTS LIST 1 ) 560-920 Louvre Assy (Set) - Gold 560-922 Louvre Assy (Set) - Black 4 ) 730-038 Door Screen (Australia Only) 8 ) 730-560 R el ie f Door Assembly 10) 640-034 Mounting Plate Gasket 560-519/P Fan Assembly (240 V) 1 1) 910-169/P Fan Motor (240 V) 12) 910-714 Power Cord (240 V ...

  • Regency FG37-NG - page 28

    28 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater FG37 BURNER & LOG ASSEMBL Y 52) 910-190 Piezo Ignitor & Nut 54) 910-373 Knob - Pilot Valve Extension 55) 910-372 Flame Adjusting Knob 56) 918-088 D ecal - Control Panel 57) 591-041 Switch Plate 680-574/P Valve Assembly - NG 680-576/P Valve Assembly - LPG 60) 910-378 Valve - S.I. ...

  • Regency FG37-NG - page 29

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 29 FG37 DOOR ASSEMBLIES Pa rt # Description P ARTS LIST 730-924 Gold Mitred Door - Complete 730-926 Black Mitred Door - Complete 730-932 Gold Wrap Door - Complete 730-928 G old Panel Door - Complete 101) 650-920 Door Gasket Kit 105) * Ceramic Paper 106) 940-323/P Side Glass 107) 936-243 Gl ...

  • Regency FG37-NG - page 30

    30 FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater _____________________________________________________________________________________ ____________________________________________________________ __________________________________________________________ ____________________________________________________________ ____________________ ...

  • Regency FG37-NG - page 31

    FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater 31 W ARRANTY Exclusions: This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim. It does not cover installation and operational related problems such as over- firing, downdrafts or spillage caused by environmental con- ditions, nearby trees, bui ...

  • Regency FG37-NG - page 32

    Printed in Canada © Copyright 2006, FPI Fireplace Products International Ltd. All rights reserved. ...

Fabbricante Regency Categoria Stove

I documenti che otteniamo dal fabbricante del dispositivoRegency FG37-NG possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Regency
- manuali per l’uso FG37-NG
- schede prodotto Regency
- opuscoli
- o etichette energetiche Regency FG37-NG
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Regency FG37-NG.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Regency FG37-NG, manuali di manutenzione, brevi manuali o manuali utente Regency FG37-NG. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Regency FG37-NG.

Manuali per l’uso simili

Manuale completo del dispositivo Regency FG37-NG, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Regency FG37-NG dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Regency FG37-NG.

Il manuale per l’uso completo Regency, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Regency FG37-NG - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Regency FG37-NG, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Regency FG37-NG che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Regency FG37-NG - che ci dovrebbe aiutare nei primi passi durante l'uso Regency FG37-NG
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Regency FG37-NG
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Regency FG37-NG in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Regency FG37-NG?

Utilizza il modulo sottostante

Se non hai risolto il problema con Regency FG37-NG con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Regency FG37-NG è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)