    This manual should be maintained in legible condition and kept adjacent to the heater or in another safe place for future reference. Catalog No: 1000.57A Effective: 02-28-07 Replaces: 02-24-06 P/N 241275 Rev . 2 INST ALLA TION AND OPERA TING INSTR UCTIONS COLD W A TER ST AR T & COLD W A TER RUN F or Hi Delta & MVB Hea ter s & Boiler s ...

  • Raypak 241275 - page 2

    2 ...

  • Raypak 241275 - page 3

    GENERAL SAFETY T o meet commercial hot water use needs, the high limit safety control on this water heater is adjustable up to 210°F . However , water temperatures over 125°F can cause instant severe burns or death from scalds. When supplying general purpose hot water , the rec- ommended initial setting for the temperature control is 125°F . Saf ...

  • Raypak 241275 - page 4

    4 COLD WA TER ST AR T Before arriving at the job site to begin the installation, it's important to first inspect the system and determine what materials you will need. Some parts are includ- ed with the controller while others you will need to provide. 1 Control Box 1 T emperature Sensor 1 V alve assembly with actuator (Shipped separately) Wir ...

  • Raypak 241275 - page 5

    5 Connecting P ow er to the Controller Supply power from the 120 V AC power input from the heater to the controller power inputs T erminal Block (TB1). This is accomplished by connecting wiring from the control box to the heater TB1 board 120 V AC power input connections. Refer to wiring diagrams. Fig. 3: Component Locations — Hi Delta Fig. 4: Lo ...

  • Raypak 241275 - page 6

    6 Cold Star t Sequence of Operation 1) 120V AC to heater sends 120V AC to Cold Start control on terminal block 1. 2) 120/24V AC transformer and 120V AC-12VDC con- verter are powered. 3) 120/24V AC transformer outputs 24V AC to pin 2 of terminal block 2 4) 24V AC leaves pin 2 of terminal block 2 and goes to the modulating three way valve on the 20- ...

  • Raypak 241275 - page 7

    7 NO TE: Elodrive actuator is Nema 4 rated. TR OUBLESHOO TING Check your power source using a V olt-Ohm meter; check the following voltages at TB1 terminal block: TB1-1 to TB1-2 = 108 V AC Minimum, 132 V AC Maximum TB1-1 to TB1-3 = 108 V AC Minimum, 132 V AC Maximum TB1-2 to TB1-3 = Must be less than .6 V AC IF CALL FOR HEA T LED does not illuminat ...

  • Raypak 241275 - page 8

    8 Cold Wa ter Star t T r oubleshooting Guide ...

  • Raypak 241275 - page 9

    9 W iring Dia gr am ...

  • Raypak 241275 - page 10

    10 COLD WA TER R UN Pur pose The Cold W ater Run system utilizes a variable-speed pump to inject the proper amount of water from the main system loop into the boiler to maintain the opti- mum inlet temperature. This approach allows the full capacity of the boiler to be utilized to meet the system load, while at the same time continuously maintainin ...

  • Raypak 241275 - page 11

    11 Injection & Heater Pump Comparison — Hi Delta Heater Pump Injection Pump Heater Model Flow T emp. Rise Press. Drop Flow T emp. Rise Injection Pump Heater Pump 302 32 16 2 13 40 191 1- 1 ⁄ 4 hp 11 2 402 34 20 2 17 40 191 1- 1 ⁄ 4 hp 11 2 502 42 20 2.3 22 40 191 1- 1 ⁄ 4 hp 1630 4.0 652 55 20 4.1 28 40 191 1- 1 ⁄ 4 hp 1630 4.0 752 63 ...

  • Raypak 241275 - page 12

    12 Fig. 13: Remove the pump body Fig. 14: Be sure not to damage the seal when removing or replacing the pump body Injection Pump Co v er Installation Before Star ting 1) T urn off power to the unit at the circuit breaker . 2) T urn off gas supply . 3) Shut off the water supply to the heater and, if nec- essary , drain water from the system. 4) Allo ...

  • Raypak 241275 - page 13

    13 3. Insert and tighten all eight (8) wrench bolts, secur- ing the pump body in place. 4. Y ou will now be able to install the pump cover . See Fig. 18 and 19. Fig 15: Reposition the pump body so that the electrical box points downward Fig. 16: Place the cover on the pump Fig 17: Pump cover - angle view ...

  • Raypak 241275 - page 14

    14 Typical Boiler Piping (Hi Delta sho wn) ...

  • Raypak 241275 - page 15

    15 ST AR T -UP PROCEDURE • Run full system flow for two minutes. • Initiate PID pump control to achieve target inlet temperature by slowing injector pump. • Boiler ΔT will not increase during bypass operation. • If target temperature is not achieved after seven minutes from “call for heat”, the system will shut down. Sequence of Operat ...

  • Raypak 241275 - page 16

    16 W iring Dia gr am ...

  • Raypak 241275 - page 17

    17 Cold Wa ter Run T roubleshooting Guide Ste p 9 Ste p 8 Ste p 10 Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Is th ere a C all F or Heat at t he heat er? Is th e 220 VAC inver ter in t he cold r u n co ntroll er power ed ? Re place i nverte r or in stall j umper and c orr ect s witc h s ettin gs Does the col d run inv ert er o utpu t 12VDC f ...

  • Raypak 241275 - page 18

    18 ILL USTRA TED P ARTS LISTS Cold Wa ter Star t ...

  • Raypak 241275 - page 19

    19 1-M 4-M 2-M 3-M CALL OUT DESCRIPTION HI DEL T A MVB F 7 1 7 1 1 0 F 7 1 7 1 1 0 L O R T N O C - Y S S A D R A O B C P C - 1 F 8 1 7 1 1 0 F 8 1 7 1 1 0 R E M R O F S N A R T C - 2 3-C POWER SUPPL Y 120V AC/12VDC 01 1719F 01 1719F F 0 2 7 1 1 0 F 0 2 7 1 1 0 V 4 2 T D P D - Y A L E R C - 4 F 9 3 0 9 0 0 F 9 3 0 9 0 0 V 4 2 T D P S - Y A L E R C - ...

  • Raypak 241275 - page 20

    20 Cold Wa ter Run ...

  • Raypak 241275 - page 21

    21 CALL OUT B V M A T L E D I H N O I T P I R C S E D F 7 1 7 1 1 0 F 7 1 7 1 1 0 L O R T N O C - Y S S A D R A O B C P C - 1 F 0 2 7 1 1 0 F 0 2 7 1 1 0 C A V 4 2 T D P D - Y A L E R C - 2 F 9 3 0 9 0 0 F 9 3 0 9 0 0 C A V 4 2 T D P S - Y A L E R C - 3 F 5 3 8 1 1 0 F 5 3 8 1 1 0 P H 2 / 1 - R E T R E V N I C - 4 F 6 3 8 1 1 0 F 6 3 8 1 1 0 P H 1 ...

  • Raypak 241275 - page 22

    ww w .raypak.c om Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468 Raypak Canada Limited, 2805 Slough St., Mississauga, Ontario, Canada L4T 1G2 (905) 677-7999 Fax (905) 677-8036 Litho in U.S.A. ...

メーカー Raypak カテゴリー Boiler

Raypak 241275のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 241275の取扱説明書
- Raypakの製品カード
- パンフレット
- またはRaypak 241275の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Raypak 241275の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Raypak 241275の取り付け説明書、サービスマニュアル、簡易説明書、またはRaypak 241275のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Raypak 241275の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Raypak 241275デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがRaypak 241275を使用するのを助ける技術的文書のことです。説明書は通常、全てのRaypak 241275ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Raypakの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Raypak 241275の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははRaypak 241275の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Raypak 241275に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Raypak 241275デバイスの基本機能を使うにあたってのヒント。 Raypak 241275のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Raypak 241275に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるRaypak 241275のメーカー/サービスへの連絡先に関する情報。

Raypak 241275についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもRaypak 241275の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがRaypak 241275で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)