    808 134th Street SW, Suite 120 • Everett, WA 98204 • USA • 425/745-3229 Fax: 425/745-3429 • E-mail: maple@maple-systems.com • URL: www.maple-systems.com E N T E R DELETE CLEAR SHIFT # : , ? % $ = * / + - . SP ACE 5 6 4 8 0 9 7 23 1 HI J K M G L OT U S Q R YZ X AB C D F E P N VW INSTALLATION MANUAL 1010-0046A, REV 00 Secure online ordering ...

  • B&B Electronics MAP450D - page 2

    2 MAP450D 1010-0046A, REV 00 COPYRIGHT NOTICE This manual is a publication of Maple Systems, Inc., and is provided for use by its customers only. The contents of the manual are copyrighted by Maple Systems, Inc.; reproduction in whole or in part, for use other than in support of Maple Systems equipment, is prohibited without the specific written pe ...

  • B&B Electronics MAP450D - page 3

    INSTALLATION MANUAL 3 1010-0046A, REV 00 Read Me First! Your new Maple Systems OIT comes from the factory configured with the default communication settings: 9600 baud, no parity, 8 data bits, 1 stop bit, no handshaking, no turn-around delay, 90 ° viewing angle, interactive mode, CR line terminator, underline cursor, 1 space tab width, local echo ...

  • B&B Electronics MAP450D - page 4

    4 MAP450D 1010-0046A, REV 00 TABLE OF CONTENTS 1. Control Panel Design Guidelines ...................................5 1.1. Control Panel Grounding ....................................5 1.2. Power Supply Selection .....................................5 1.3. OIT Cable Routing .........................................6 1.4. Other Steps to Improve Noi ...

  • B&B Electronics MAP450D - page 5

    1. Control Panel Design Guidelines Pay careful attention to the placement of system components and associated cable routing. These items can significantly enhance the performance and integrity of your control application. 1.1. Control Panel Grounding • The control panel should be connected to a good, high-integrity earth ground both for safety co ...

  • B&B Electronics MAP450D - page 6

    • A power line filter installed at the AC input to the OIT power supply is highly recommended as a safeguard against conducted RF noise, which is often present on factory power lines. The wires connecting the output of the power line filter to the power supply should be kept as short as possible to minimize any additional noise pickup. The case o ...

  • B&B Electronics MAP450D - page 7

    2. Connecting the MAP450D to a Host Controller It is necessary to follow all installation procedures described in this chapter for electrical noise immunity and CE compliance. STEPS 1. Remove the four screws from the back of the OIT enclosure and open the two halves. 2. A strain relief is provided for wiring access and sealing. The cable must be in ...

  • B&B Electronics MAP450D - page 8

    6. Connect the OIT operating cable wires to the terminal block. Refer to sections 2.1 through 2.3 and Figure 4. 7. Pull out any slack from the OIT operating cable. 8. Rotate the rear of the OIT enclosure back into position while gently pulling out the new slack generated in the cable as you proceed. CAUTION : Due to the large size of the ferrite co ...

  • B&B Electronics MAP450D - page 9

    2.1. RS-232 (Interactive & Block modes) Interactive and Block modes support the 3-wire RS-232 configuration with TXD, RXD and signal common. The cable requires an overall shield to protect against electrical noise. Xon and Xoff can be used for communication handshaking. 3-Wire RS-232 Host Controller MAP450D Terminal Block TXD Pin 9 - RXD RXD Pi ...

  • B&B Electronics MAP450D - page 10

    2.3. RS-422/485 (Network mode) Network mode supports the 3-wire and 5-wire RS-422/485 configurations. The 3-wire configuration has both transmit and receive on the same pair of wires plus a signal common. The 5-wire configuration has differential signal pairs for transmit and receive plus a signal common. In both configurations the signal pairs mus ...

  • B&B Electronics MAP450D - page 11

    There are several different forms of communications networks. Maple Systems’ OITs utilize the multidrop format. The host controller, located at one of the network ends, is connected to the OITs via a continuous com-link. Each OIT is connected to the network by locally tapping into the com-link with short stub cables. The end of the com-link must ...

  • B&B Electronics MAP450D - page 12

    Network Termination The com-link cable must be properly terminated to reduce the amount of interference and noise pickup from the surrounding environment. This is accomplished by using a termination circuit at both ends of the network cable. The following figure shows a typical termination circuit. The host termination is only needed if the host co ...

  • B&B Electronics MAP450D - page 13

    The cable shield must not be used as the signal ground. It is tempting to try and reduce the cost of 5-wire cabling by using a 4-wire cable with the shield used as the signal ground. DON’T DO IT. The initial cost savings are always exceeded by the maintenance costs once the system is operating under field conditions. It is often necessary to comp ...

  • B&B Electronics MAP450D - page 14

    3. Mounting the MAP450D 3.1. Panel Mount The OIT is installed in a panel by separating the front and rear covers of the OIT, and then sandwiching the panel between the two. The gasketed surface of the OIT’s front cover provides the environmental seal to NEMA 4 and NEMA 12 standards. The rear cover helps shield the OIT from dust, dirt, induced ele ...

  • B&B Electronics MAP450D - page 15

    IMPORTANT: When panel mounting the MAP450D, do not catch the display connector on the panel cutout. The display is exposed while panel mounting and extra care should be taken. The display can be damaged if the display cable connector, which protrudes from the panel cutout, is touching the panel when tightened. To avoid damage, place the MAP450D gen ...

  • B&B Electronics MAP450D - page 16

    The OIT is connected to the mounting plate with four #6-32UNC screws. The length of the mounting screws is equal to the plate thickness plus 1/4 inch. NOTE: The mounting screws must not be torqued to more than 18 pound-inches. Over-torquing can strip the threads in the enclosure. 3.3. Benchtop Mount The MAP450D’s rear cover has two legs set at a ...

  • B&B Electronics MAP450D - page 17

    4. Configuring the MAP450D The MAP450D has many operating parameters that control how it communicates to the host controller. These operating parameters can be changed in three ways: from the MAP450D’s keyboard when it is in Configuration mode, when the host controller sends a Configuration Control Command, or by downloading a STEPware-100 projec ...

  • B&B Electronics MAP450D - page 18

    Appendix A OIT Hardware Specifications Mechanical Material: Cast aluminum enclosure sealed to NEMA 4/12 Mounting: Panel, pedestal, pendant, or benchtop Wiring: Unit is field-wired by user to internal terminal block pins Weight: 2 pounds (0.90 kg) Environmental Operating Temp: +32 to +122°F (0 to +50°C) Storage Temp: -4 to +158°F (-20 to +70°C) ...

  • B&B Electronics MAP450D - page 19

    Appendix A (con’t) Dimensional Outline INSTALLATION MANUAL 19 1010-0046A, REV 00 5.75 [146] Dimensions are in inches [ mm ] . 5.00 [127] 0.90 [23] depth behind the front of a panel 8.12 [206] 6-32UNC x 0.50 [12.7] screw , 4 places SS, 6-32UNC x 0.30 [7.6] deep threads, for Pedestal Mounting only REAR VIEW FRONT VIEW SIDE VIEW , Free-Standing & ...

  • B&B Electronics MAP450D - page 20

    Appendix B Differences Between MAP450D and MAP450B The MAP450D uses the same enclosure, display, keyboard and overlay as the MAP450B, but includes the following differences: 1. The MAP450D can be configured using the Windows-based STEPware-100 configuration software. 2. The MAP450D stores and displays up to 500 user-definable messages. 3. The MAP45 ...

メーカー B&B Electronics カテゴリー Mouse

B&B Electronics MAP450Dのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- MAP450Dの取扱説明書
- B&B Electronicsの製品カード
- パンフレット
- またはB&B Electronics MAP450Dの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、B&B Electronics MAP450Dの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、B&B Electronics MAP450Dの取り付け説明書、サービスマニュアル、簡易説明書、またはB&B Electronics MAP450Dのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、B&B Electronics MAP450Dの製品を使用するにあたって最も人気のある説明書を閲覧できます。

B&B Electronics MAP450Dデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがB&B Electronics MAP450Dを使用するのを助ける技術的文書のことです。説明書は通常、全てのB&B Electronics MAP450Dユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

B&B Electronicsの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. B&B Electronics MAP450Dの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははB&B Electronics MAP450Dの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。B&B Electronics MAP450Dに関してこのドキュメントで見つけることができる全てのヒントの目次
3. B&B Electronics MAP450Dデバイスの基本機能を使うにあたってのヒント。 B&B Electronics MAP450Dのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。B&B Electronics MAP450Dに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるB&B Electronics MAP450Dのメーカー/サービスへの連絡先に関する情報。