    P/N 240499 CATALOG NO.: 6200.50 M Effective: 04-15-05 Replaces: 06-01-00 INST ALLA TION AND OPERA TING INSTRUCTIONS COMMERCIAL SWIMMING POOL HEA TERS Raytherm Models 514-824 This manual should be maintained in legible condition and kept adjacent to the heater or kept in a safe place for future reference. WARNING: If the information in these instruc ...

  • Raypak 514-824 - page 2

    WATER CHEMISTRY (Corrosive water voids all warranties) For your health and the protection of your pool equipment it is essential that your water chemically balanced. The following levels must be used as a guide for balance water. Free Chlorine MUST NOT EXCEED 5 PPM! • Occasional chemical shock dosing of the poolm or spa water should not damage th ...

  • Raypak 514-824 - page 3

    4 PART ONE - OWNER’S OPERATING INSTRUCTIONS 4 SECTION 1/START-UP PROCEDURES 4 Before Start-Up 5 Operating Instructions 6 After Start-up 6 SECTION 2/CAUTION 6 SECTION 3/MAINTENANCE AND CARE PROCEDURES Pool & Spa Water Chemistry 7 PART TWO - INSTALLATION/SERVICE INSTRUCTIONS 7 SECTION 1/RECEIVING EQUIPMENT 7 SECTION 2/GENERAL SPECIFICATION 7 SE ...

  • Raypak 514-824 - page 4

    P ART ONE - OWNER’S OPERA TING INSTRUCTIONS FOR YOUR SAFETY - READ BEFORE OPERATING WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. SECTION 1/START-UP PROCEDURES BEFORE START-UP BURNERS Clean main burners and air louvers of dust, lint and debris. Keep hea ...

  • Raypak 514-824 - page 5

    5 1. STOP! Read the safety information above. 2. Set the thermostat on the lowest setting. 3. Turn off all electric power to the appliance. 4. Remove heater door panel. 5. This appliance is equipped with an ignition device which automatically light the pilot. Do not try to light the pilot by hand. 6. For Models 514-724 with Honeywell Gas Valve. Pus ...

  • Raypak 514-824 - page 6

    AFTER START-UP Feel the inlet and outlet pipes. Outlet pipe should be only slightly warmer than the inlet. It should not be hot. WARNING: Should overheating occur or the gas supply fail to shut off, turn off the manual gas control to the appliance. VISUAL INSPECTION With the heater on, remove the door and make a visual check of the pilot and burner ...

  • Raypak 514-824 - page 7

    5 . On indoor heater, clean room intake openings to assure adequate flow of combustion and ventilation air. CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater and void the warranty. 6. Keep air around heater clear and free from com- bustible materials, gasoline and other flammable and corrosive ...

  • Raypak 514-824 - page 8

    4 foot Minimum 4 foot Minimum 1 foot Minimum 4 foot Minimum 3 foot Minimum 10 foot Minimum Forced Air Inlet 12" Minimu m 12" M inimum 4" Minimum HEA TER Sheet Metal 24 Gauge 8 HIGH WIND CONDITIONS (OUTDOOR UNITS ONLY) In areas where high winds are fre- quent, it may be necessary to locate the heater a minimum of 3' from high ver ...

  • Raypak 514-824 - page 9

    INDOOR HEATER The design is also certified for indoor installation when equipped with the approved draft hood. Locate heater as close as practical to a chimney or gas vent. Heater must always be vented to the outside. See Vent Piping Section for venting details. Minimum allowable space is shown on the nameplate. COMBUSTION AIR (Indoor Units Only) A ...

  • Raypak 514-824 - page 10

    As much as possible avoid long horizontal runs of vent pipe and too many elbows. If installation requires horizontal non-vertical runs, the vent pipe must have a minimum of 1/4 inch per foot rise and should be supported at not less than five foot intervals. Plumbers tape, crisscrossed, will serve to space both horizontal and vertical piping. Gas ve ...

  • Raypak 514-824 - page 11

    GAS SUPPLY CONNECTIONS Gas piping must have a sediment trap ahead of the heater gas controls, and a manual shut off valve located outside the heater jacket. All gas piping should be tested after installation in accordance with local codes. MANUAL SHUT OFF VALVE GAS INLET HEATER JACKET SEDIMENT GA S TRAP UNION VALVE Fig. #8090.0 CAUTION: the heater ...

  • Raypak 514-824 - page 12

    PIPE SIZING FOR GAS CONNECTIONS MAXIMUM EQUIVALENT PIPE LENGTH Natural gas 1000 BTU/Ft .60 Specific Gravity @ 0.5” W.C. Pressure Drop Propane Gas 2500 BTU/Ft 1.53 Specific Gravity @ 0.6” W.C. Pressure Drop 1/2” 1” 1-1/4” 1-1/2” 2” 2-1/2” N P N P N P N P N P N P 5 1 4 - 10 15 35 65 150 130 360 500 - - - 6 2 4 - - 10 25 45 100 95 250 ...

  • Raypak 514-824 - page 13

    AUTOMATIC CHLORINATORS AND CHEMICAL FEED- ERS All chemicals must be introduced and completely diluted into the pool or spa water before being circulated through the heater. Do not place chlorine tablets or bromine sticks in the skimmer. High chemical concen- trations will result when the pump is not running (i.e. overnight). Chlorinators must feed ...

  • Raypak 514-824 - page 14

    To avoid water damage or scalding due to valve operation, drain pipe must be connected to valve outlet and run to a safe place of discharge. Drain pipe must be the same size as the valve discharge connection through- out its entire length and must pitch downward from the valve. No shutoff valve shall be installed between the relief valve and the dr ...

  • Raypak 514-824 - page 15

    15 ...

  • Raypak 514-824 - page 16

    16 151965 824 825,000 BTUH ...

  • Raypak 514-824 - page 17

    17 152141 514-724 512,000 THRU 726,000 BTUH 5 ...

  • Raypak 514-824 - page 18

    18 152142 824 825,000 BTUH 6 ...

  • Raypak 514-824 - page 19

    CONTROLS/ADJUSTMENTS/REPLACEMENTS THERMOSTAT The heater is built with a single mechanical thermo- stat, located in the front panel above the door. The thermostat maybe set for any desired pool or spa temperature TEMPERATURE SENSOR MECHANICAL THERMOSTAT Fig. # 8060.1 TYPICAL COMFORTABLE SPA TEMPERATURE RANGE KNOBSTOP RING SET SCREW TYPICAL COMFORTAB ...

  • Raypak 514-824 - page 20

    PRESSURE SWITCH The pressure switch, or heater actuator, insures that the heater operates only when the filter pump is in operation. It is factory set at 1.75 PSI for deck level installations. When the heater is located below the level of the spa or pool it may be necessary to reset the pressure switch to compensate for the no-flow static head. If ...

  • Raypak 514-824 - page 21

    GAS VALVE REMOVAL 1. Shut off gas supply to the heater. Remove gas piping to gas valve inlet. 2. Disconnect wires, pilot tubing and bleed line, if required. 3. Turn vertical gas pipe from manifold slightly and unscrew gas valve. 4. Reverse above procedure to re-install. MAIN BURNER AND ORIFICE REMOVAL 1. Remove burner drawer. See burner drawer remo ...

  • Raypak 514-824 - page 22

    22 Shut gas and power off to the unit, close the system off and drain the heater. Remove the draft diverter. Remove the access panel and jacket top. Lift flue collector off. Remove “V” baffles over tube(s) to be replaced. If no pipe unions have been provided, use the header as a union, remove the flange nuts off the inlet- outlet header, break ...

  • Raypak 514-824 - page 23

    23 SECTION 5/TROUBLESHOOTING GUIDE IMPORTANT NOTICE These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by some states to be licensed. Persons not quali ...

  • Raypak 514-824 - page 24

    Inspect bypass for movement, if no movement, replace. Replace if no movement when heated. Replace well and maintain water chemistry properly. Replace heat exchanger and maintain chemistry properly. See pressure switch adjustment. Replace refractory. Determine cause of sooting and correct. Bypassing too much water…………………… U. G. not f ...

  • Raypak 514-824 - page 25

    WARNING HIGH VOLTAGE For qualified Technicians ONLY NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater. Intermittent Pilot System TROUBLESHOOTING HONEYWELL S8600 NOTE:Before troubleshooting, familiarize yourself with the startup and checkout procedure. Che ...

  • Raypak 514-824 - page 26

    26 SECTION 6/REPLACEMENT PARTS LIST NOTE: To supply the correct part it is important that you state the model number, serial number and type of gas when applicable. Any part returned for replacement under standard company warranties must be properly tagged with RAYPAK return parts tag, completely filled in with the heater serial number, model numbe ...

  • Raypak 514-824 - page 27

    this page is empty ...

  • Raypak 514-824 - page 28

    28 PILOT ASSEMBLY- ELECTRONIC IGNITION PILOT ASSEMBLY- STANDING PILOT Fig # 9293 Fig # 9294 ...

  • Raypak 514-824 - page 29

    29 ...

  • Raypak 514-824 - page 30

    30 ...

  • Raypak 514-824 - page 31

    ...

  • Raypak 514-824 - page 32

    RAYPAK, INC., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 FAX (800) 872-9725 Litho in U.S.A. ww w .raypak.com ...

メーカー Raypak カテゴリー Fan

Raypak 514-824のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 514-824の取扱説明書
- Raypakの製品カード
- パンフレット
- またはRaypak 514-824の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Raypak 514-824の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Raypak 514-824の取り付け説明書、サービスマニュアル、簡易説明書、またはRaypak 514-824のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Raypak 514-824の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Raypak 514-824デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがRaypak 514-824を使用するのを助ける技術的文書のことです。説明書は通常、全てのRaypak 514-824ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Raypakの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Raypak 514-824の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははRaypak 514-824の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Raypak 514-824に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Raypak 514-824デバイスの基本機能を使うにあたってのヒント。 Raypak 514-824のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Raypak 514-824に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるRaypak 514-824のメーカー/サービスへの連絡先に関する情報。

Raypak 514-824についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもRaypak 514-824の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがRaypak 514-824で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)