Hoshizaki 73183の取扱説明書

42ページ 2.08 mb
ダウンロード

ページに移動 of 42

Summary
  • Hoshizaki 73183 - page 1

    Hoshizaki “A Superior Degr ee of Reliability” www .hoshizaki.com Models Reach-In B-Series Commercial Series Refrigerated Kitchen Equipment Hoshizaki America, Inc. Number: 73183 Issued: 3-23-2011 SE RV ICE MA NU AL ...

  • Hoshizaki 73183 - page 2

    2 IMPOR T ANT Only quali ed ser vice technicians should inst all, ser vice , and maintain the unit. No ser vice or maint enance should be under tak en until the t echnician has thoroughl y read this Ser vice Manual. F ailure t o ser vice and maintain the equipment in accordance with this man ual ma y adver sely af fect saf et y , perf ormance, c ...

  • Hoshizaki 73183 - page 3

    3 CONTENTS Impor tant Saf et y Inf or mation ................................................................................................. 5 I. Specications ...................................................................................................................... 7 A. Nameplate Ratings ............................................ ...

  • Hoshizaki 73183 - page 4

    4 D . Diagnostic Char t ......................................................................................................... 35 1 . Unit Not Cooling ..................................................................................................... 35 2. Evaporat or is F r ozen Up ............................................................. ...

  • Hoshizaki 73183 - page 5

    5 Impor tant Safety Inf ormation Throughout this man ual, notices appear t o bring your at tention t o situations which could result in death, serious injur y , or damage to the unit. W ARNING Indicates a hazardous sit uation which could result in death or serious injury . C A UTION Indicates a sit uation which could result in dama ge to the unit. ...

  • Hoshizaki 73183 - page 6

    6 •Makesur ethepowers witchisinthe"OFF"positionbefor eplugginginor unplugging the unit to r educe the r isk of electric shock. •Donotuseaunitwithadamagedpow ercor d.  Thepowercor dshouldnotbe alter ed, jer k ed, b undled, weighed do wn, pin ...

  • Hoshizaki 73183 - page 7

    7 I. Specications A. Nameplate Ratings Model A C Supply V oltage Amperes Design Pr essur e (PSIG) Refr igerant (oz.) HIGH LOW 1 34a 404A CR1B-FS/HS 1 1 5/60/1 4 240 12 0 11 - CF1B-FS/HS 9 450 250 - 8 CR2B-FS/HS 7 240 12 0 12 - CF2B-FS/HS 11 450 250 - 17 CR3B-FS/HS 1 1 5/60/1 9 240 12 0 1 -Section 11 - 2-Section 12 CF3B-FS/HS 208-230/1 1 5/60/1 1 ...

  • Hoshizaki 73183 - page 8

    8 2. One Section/T wo Section/Thr ee Section Unit: mm (in.) Ad ditional Dimensions Model Inter ior Width Inter ior Height Inter ior Depth Door Stay Open P osition Caster Height (Standard) Caster Height (Option) Leg Height (Option) One Section 579 (22.8) 1 51 3.6 (59.59) 71 1 .2 (28) 80° 1 0 1. 6 (4) 1 52.4 (6) 1 53±28.6 (6.02±1 .1 3) Tw o Sectio ...

  • Hoshizaki 73183 - page 9

    9 II. General Inf ormation A. Construction 1 . One Section Contr ol Module Condenser F an Motor Condenser Displa y Module F ront P anel Door Door Gasket Contr ol Bo x P ower S witch Door Lock Models CR1B-FS/HS and CF1B-FS/HS Model Shown: CR1B-FS Light Compr essor Condensat e P ump Reservoir Float Switch f or Condensat e P ump P ower C ord Door S wi ...

  • Hoshizaki 73183 - page 10

    10 2. T wo Section Models CR2B-FS/HS and CF2B-FS/HS Model Shown: CR2B-HS P ower C ord Compr essor Condenser F an Motor Condenser F ront P anel Contr ol Module Displa y Module P ower S witch Door Lock Light Reservoir Float Switch Reservoir Cover Door Door Gasket Contr ol Bo x Door Switch Door S witch Door Latch •Ev aporat or •C abinet T ...

  • Hoshizaki 73183 - page 11

    11 3. Three Section Compr essor Condenser F an Motor F ront P anel Contr ol Module Displa y Module P ower S witch Door Lock Light Reservoir Float S witch Reservoir Cover Door Door Gasket Contr ol Bo x Door S witch •Ev aporat or •C abinet Ther mistor •Defrost Thermistor •Ev aporat orF anShroud Ther mostatic Expansion ...

  • Hoshizaki 73183 - page 12

    12 B. Sequence of Operation 1 . Sequence Cy c les and Shutdo wn The steps in the sequence ar e as outlined below . Note: 1 . There is a slight dela y at star tup. 2. W hen power is turned on, the 2-hour high-temperatur e alar m timer is bypassed. Theref ore , a high-temperatur e alarm can occur at star tup . T o silence the alar m, press and r elea ...

  • Hoshizaki 73183 - page 13

    13 b) F r eez er 1 . Startup/Cool Down MH and PH energiz e. Ther e is a slight dela y befor e cabinet t emperatur e or high-temper atur e alarm (Hi) appears on DM and Comp , ConFM, and Ev apFM energiz e. 2. Cool D o wn Ac hie ved CM monitor s cooling of the cabinet via CTh. CTh cools to 3 ° F (1 .7 ° C) below setpoint. Ev apFM, MH, and PH continu ...

  • Hoshizaki 73183 - page 14

    14 2. Sequence Flow Charts a) Refr iger at or Refr ig er at or Sequence Flow Chart Legend: Comp -compressor ConFM -condenser f an motor CTh -cabinet thermistor DTh- defrost thermistor EvapFM -e vaporat or f an mot or MH -mullion heat er 1 . Startup/Cool Do wn 2. Cool Down Achiev ed Comp energiz ed ConFM energiz ed EvapFM ener gized MH energiz ed CT ...

  • Hoshizaki 73183 - page 15

    15 b) F r eez er F r eezer Sequence Flow Chart 3. Cool Down Restart Legend: Comp -compressor ConFM -condenser f an motor CTh -cabinet thermistor DH -defrost heat er DTh- defrost thermistor EvapFM -e vaporat or f an mot or MH -mullion heat er PH -perimeter heater 1 . Startup/Cool Do wn 2. Cool Down Achiev ed Comp energiz ed ConFM energiz ed EvapFM e ...

  • Hoshizaki 73183 - page 16

    16 C. Display Module Whenthepo wers witchismov edtothe"ON"positionther eisaslightdela y ,thenthe current cabinet t emperature is displa yed. F rom the displa y module, the cabinet setpoint andtemper atur edispla yscalecanbechanged. F orfur therdetails,see& ...

  • Hoshizaki 73183 - page 17

    17 2. Controls and A djustments a) Default Set tings 1 . T emperatur e Set ting: Refrigerat or : 36°F (2°C). F reez er : -4°F (-20°C). 2. T emperatur e Displa y Scale: F . b) T emperat ur e Setpoint The temper atur e setpoint is the v alue for the a v erage cabinet temper atur e. The temper atur e dif f er ential f or the compressor t o tur n o ...

  • Hoshizaki 73183 - page 18

    18 Displa y C able F ig. 2 D . Contr ol Module All models are pr etest ed and f actor y set . C A UTION 1 . The control module is fr agile, handle v er y carefull y . 2. Do not change wir ing and connections. Ne v er misconnect t erminals. 3. Do not shor t out pow er suppl y t o t est f or voltage . 1 . Contr ol Module Lay out F reezer Control Modu ...

  • Hoshizaki 73183 - page 19

    19 2. Alarm Safeties Alar m signals ar e designed t o pr ot ect the unit and f ood product. These alarms give inf ormation or war nings in the e vent the unit is operating out of accept ab le paramet ers. Should one of the alar ms occur , f ollow the instructions in the table belo w t o addr ess the alar m. The alar m code  ashes once e v er y s ...

  • Hoshizaki 73183 - page 20

    20 E. Compressor O ver load, Short Cyc le Pr ot ection, and High-Pr essure S witch 1 . Compr essor Ext ernal or Int ernal Ov erload If combined temper atur e/amperage v alue is abov e the limit speci ed by the compressor man uf acturer , the compr essor ov er load operat es independently t o turn of f the compressor . The compressor ov er load d ...

  • Hoshizaki 73183 - page 21

    21 III. T echnical Data A. Refr ig er ation Cir cuit Ev aporat or F ans (2 or 3 depending on model) Ev aporat or Expansion V al v e Compr essor Low -Side Access Va l v e Condensat e P an High-P ressur e S witch Drier Condenser F an Condenser Defrost Ther mist or Defrost Heat er and Defrost Thermostat (freez er onl y) Cabinet Thermistor High-Side Ac ...

  • Hoshizaki 73183 - page 22

    22 B. W iring Diagr ams 1 . CR1B-FS/HS, CR3B-FS/HS * High-Pr essure Switc h Cut-out 270±1 0 PSIG Cut-in 1 90±20 PSIG * ...

  • Hoshizaki 73183 - page 23

    23 2. CR2B-FS/HS, CR3B-FS/HS * High-Pr essure Switc h Cut-out 270±1 0 PSIG Cut-in 1 90±20 PSIG * ...

  • Hoshizaki 73183 - page 24

    24 3. CF1B-FS/HS, CF3B-FS/HS ** Defr ost Thermostat Cut-out 12 0 ° F±5 ° F (49 ° C±3 ° C) Cut-in 70 ° F±5 ° F (21 ° C±3 ° C) * High-Pr essure Switc h Cut-out 490±1 0 PSIG Cut-in 370±20 PSIG * ** ...

  • Hoshizaki 73183 - page 25

    25 4. CF2B-FS/HS, CF3B-FS/HS ** Defr ost Thermostat Cut-out 12 0 ° F±5 ° F (49 ° C±3 ° C) Cut-in 70 ° F±5 ° F (21 ° C±3 ° C) * High-Pr essure Switc h Cut-out 490±1 0 PSIG Cut-in 370±20 PSIG * ** ...

  • Hoshizaki 73183 - page 26

    26 5. CR3B-FS/HS Receptac le Bo x Connection 6. CF3B-FS/HS Receptac le Bo x Connection Note: Only the t op r eceptacles ha ve po wer . Note: Only the t op r eceptacles ha ve po wer . ...

  • Hoshizaki 73183 - page 27

    27 IV . Service Diagnosis W ARNING 1 . This unit should be diagnosed and repair ed only by quali ed ser vice personnel t o reduce the risk of death, electr ic shoc k, serious injur y , or re . 2. Risk of electr ic shock. Use e xtr eme caution and e xer cise safe electrical practices . 3. Moving par ts (e.g ., f an b lade) can crush and cut. K ...

  • Hoshizaki 73183 - page 28

    28 1 . R efr igerat or 7) Startup/Cool Down– Ev apFM and MH energiz e . Ther e is a slight dela y , then Comp and ConFM ener gize and cabinet temper atur e or high-t emperatur e alar m (Hi) appears on DM. a) StartupDiagnosis: Chec k that Ev apFM ener gize . If not, conr m that the door(s) are closed and DS contacts ar e closed. Check Ev apF ...

  • Hoshizaki 73183 - page 29

    29 8) Cool Down Ac hie ved –CTh cools t o 3°F (1 .7°C) below setpoint. Ev apFM and MH continue . Comp and ConFM de-ener gize. Diagnosis: If Comp and C onFM do not de-energiz e,conr mCThstatus . See"IV .C .  Ther mistorChec k."IfCThohmreading is in range and C omp and ConFM do not de-ener gize, CM ...

  • Hoshizaki 73183 - page 30

    30 2. F reezer 7) Startup/Cool Down– MH and PH ener gize. There is a slight dela y , then Comp , ConFM, and Ev apFM ener gize and cabinet t emperature or high-t emperature alarm (Hi) appears on DM. Once DTh reaches 32 ° F (0 ° C), 4-hourComp cum ulativ e run timer star ts. a) Startup Diagnosis: Chec k that EvapFM ener giz e. If not, conr ...

  • Hoshizaki 73183 - page 31

    31 c) HPS Activ ation: Conr m C onFM is ener gized and f an blade turns freel y . Check that the condenser coil is not clogged or restrict ed. Check that ther e ar e no r estrictions in the refrigeration cir cuit (dr ier , TXV). Conrm that the location meets fact or y requir ements: • Thisunitisnotintendedf oroutdoor ...

  • Hoshizaki 73183 - page 32

    32 Defrost T ermination: Has DTh w ar med to 59°F (1 5°C)? If not yet conrmed, conr m DThstatus . See"IV .C .  Ther mistorChec k."IfDThisgoodbutdefrostt er mination temper atur e is not r eached, conrm DH amp draw and contin uity . If DTh is good and defrost t er mination temper atur e is ...

  • Hoshizaki 73183 - page 33

    33 B. Control Module Chec k Bef or e r eplacing a contr ol module that does not sho w a visible def ect and that you suspect is bad, alw ay s conduct the follo wing chec k pr ocedur e. This procedur e will help you v er ify y our diagnosis . Alwa ys choose a whit e (W) neutral wire t o estab lish a good neutral connection when chec king high v olta ...

  • Hoshizaki 73183 - page 34

    34 "IV .A.2.9)Defrost"and"IV .C .  Ther mistorChec k."Ifcomponentsfailt ostar t,control module must be r eplaced. C. Thermist or Chec k In the e v ent the cabinet ther mistor r eading is out of range (E1 alarm), the compressor operat es on a x ed time basis of 5-minutes on and 5-min ut es o ...

  • Hoshizaki 73183 - page 35

    35 D . Diagnostic Chart Bef or e consulting the diagnostic char ts, chec k the follo wing: •Checkthesetpoint. F orf actor ydef aultset tings,see"II.C .2.a)Def aultSet tings." •Makesur ethedoorsar enotlef topenoropenedtooof t enandthatthe yaresealing ...

  • Hoshizaki 73183 - page 36

    36 Unit Not Cooling - P ossible Cause 1 1. Compr essor Overload a) Dir ty condenser . b) Condenser f an not operating. c) Def ective . 12 . Compr essor a) Def ectiv e. 13 . Condenser a) Dirt y . 14 . Ev aporat or See"2. Evaporat orisFr ozenUp ." a) Clogged or froz en. 15 . Refrigerant/R efrigerant Lines a) Gas leak. b) Refr ...

  • Hoshizaki 73183 - page 37

    37 V . R eplacement of Components W ARNING 1 . This unit should be diagnosed and repair ed only by quali ed ser vice personnel t o reduce the risk of death, electr ic shoc k, serious injur y , or re . 2. Movethepo wers witcht othe"OFF"position,thenunplugtheunitfromthe electrical outlet be ...

  • Hoshizaki 73183 - page 38

    38 2. Brazing W ARNING 1 . R-1 34a and R-404A themselv es ar e not  ammable at atmospheric pressur e and temper atur es up t o 1 7 6°F (80°C). 2. R-134a and R-404A themsel ves ar e not explosiv e or poisonous. Ho we ver , when e xposed t o high t emperatur es (open ames), R-1 34a and R-404A can be decomposed to f or m h ydr ouoric acid a ...

  • Hoshizaki 73183 - page 39

    39 4) Close the low -side val v e and high-side val v e on the g auge manif old. 5) Disconnect the gauge manif old hose from the v acuum pump and at tach it t o a refrigerant service cylinder . Remember t o loosen the connection and purge the air fr om the hose. See the nameplate f or the requir ed refrigerant charge . Hoshizaki recommends only vir ...

  • Hoshizaki 73183 - page 40

    40 B. Impor tant Not es f or Component R eplacement C A UTION When r eplacing a component listed belo w , see the notes t o help ensure pr oper operation. Component Notes Compr essor Install a ne w star t r ela y , star t capacitor , and compressor o v erload (compressor o v erload is integ rat ed with the start rela y on refrigerat ors; internal o ...

  • Hoshizaki 73183 - page 41

    41 VI. Cleaning and Maint enance Instructions A. Cleaning W ARNING 1 . Bef or ecleaningtheunit,mov ethepowers witchtothe"OFF"positionand unplug the unit to pr ev ent electr ic shoc k b y une xpected entrance of w at er into the unit or injury by mo ving par ts. 2. Befor e cleaning the unit, mo v e ...

  • Hoshizaki 73183 - page 42

    42 C. Shutdown and Long St orage W ARNING 1 . When pr eparing the unit for long st orage, pr e vent the door s fr om closing t o reduce the risk of childr en get ting trapped. 2. T o reduce the risk of electric shock, do not t ouch the at tachment plug or pow er s witch with damp hands. 3. 1 1 5V Units: T o unplug the unit, be sure t o pull the plu ...

メーカー Hoshizaki カテゴリー Refrigerator

Hoshizaki 73183のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 73183の取扱説明書
- Hoshizakiの製品カード
- パンフレット
- またはHoshizaki 73183の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Hoshizaki 73183の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Hoshizaki 73183の取り付け説明書、サービスマニュアル、簡易説明書、またはHoshizaki 73183のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Hoshizaki 73183の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Hoshizaki 73183デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがHoshizaki 73183を使用するのを助ける技術的文書のことです。説明書は通常、全てのHoshizaki 73183ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Hoshizakiの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Hoshizaki 73183の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははHoshizaki 73183の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Hoshizaki 73183に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Hoshizaki 73183デバイスの基本機能を使うにあたってのヒント。 Hoshizaki 73183のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Hoshizaki 73183に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるHoshizaki 73183のメーカー/サービスへの連絡先に関する情報。

Hoshizaki 73183についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもHoshizaki 73183の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがHoshizaki 73183で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)