    TI-RNC 0108 Residential Heat Reco very V entilators (HR V) Manufactured with 2 Speed RNC Electr onics Installation Instructions for Heat Reco very V entilators with 2 Speed RNC Electronics RNC Series Models RNC95 RNC155 RNC200 RNC10 RNC20 RNC120D RNC5-TPD ...

  • Lifebreath RNC95 - page 2

    Introduction.........................................................................2 Engineering Data - RNC95 .............................................3-4 Engineering Data - RNC155 ...............................................5 Engineering Data - RNC200 ...............................................6 Engineering Data - RNC10 .............. ...

  • Lifebreath RNC95 - page 3

    3 Removab le Heat Recovery Core Drain P an Drain spout FRONT TOP knockout f or side mounting of EXHA UST return port 6" round collar converted to oval minimum 18 inches (459 mm) required for service access Threaded inserts (4) at corners SUPPL Y Fresh air from outside 5" round collar SUPPL Y Fresh air to building 6" round (conv . to ...

  • Lifebreath RNC95 - page 4

    4 RNC95 Specifications The RNC95 HRV (Heat Recovery Ventilator) has been designed to allow the installer to choose between two possible positions on the cabinet for the Stale Air Exhaust (from building) port. Illustrations in this manual show standard (side mounted) port location. The same specifications apply to both RNC95 setups, regardless of wh ...

  • Lifebreath RNC95 - page 5

    5 Engineering Data - HRV Model RNC155 THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation. FILTERS Washable air filters ...

  • Lifebreath RNC95 - page 6

    6 THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two air streams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor. 2 speed fan operation. FILTERS Washable air filters in exhaust and supply air streams. ...

  • Lifebreath RNC95 - page 7

    7 All units conform to CSA and UL standards Engineering Data - HRV Model RNC10 Date: _______________________________________________ Tag: __________________________Qty: __________________ Project: _____________________________________________ Engineer: ____________________________________________ Contractor: ________________________________________ ...

  • Lifebreath RNC95 - page 8

    8 All units conform to CSA and UL standards Engineering Data - HRV Model RNC20 Date: _______________________________________________ Tag: __________________________Qty: __________________ Project: _____________________________________________ Engineer: ____________________________________________ Contractor: ________________________________________ ...

  • Lifebreath RNC95 - page 9

    9 All units conform to CSA and UL standards Engineering Data - HRV Model RNC5-TPD Date: _______________________________________________ Tag: __________________________Qty: __________________ Project: _____________________________________________ Engineer: ____________________________________________ Contractor: _____________________________________ ...

  • Lifebreath RNC95 - page 10

    10 All units conform to CSA and UL standards Engineering Data - HRV Model RNC120D Date: _______________________________________________ Tag: __________________________Qty: __________________ Project: _____________________________________________ Engineer: ____________________________________________ Contractor: _____________________________________ ...

  • Lifebreath RNC95 - page 11

    11 Engineering Data - HRV Model RNC120D FRESH AIR FROM OUTSIDE ST ALE AIR TO OUTSIDE ST ALE AIR FROM BUILDING FRESH AIR TO B UILDING BOTT OM VIEW FOR HORIZONT AL MOUNT SER VICE CLEARANCE FROM BO TTOM OF UNIT IS MINIMUM 3’0” SIDE VIEW FOR HORIZONT AL MOUNT ALL DUCT COLLARS ARE 5” DIAMETER Connect drain hose to spout located in door . 9-1/8” ...

  • Lifebreath RNC95 - page 12

    Ventilation Dehumidistat PART NO. 99-116 The High/Low Speed Switch initiates High or Low speed ventilation. This control also has an ON/OFF Switch and a Dehumidistat Dial. 20/40 ON/OFF Dehumidistat PART NO. 99-2040 The 20/40 Switch will toggle from continuous low speed ventilation to an intermittent mode of 20 minutes fan ON (in low speed) and 40 m ...

  • Lifebreath RNC95 - page 13

    13 Location Selection The HRV must be located in a heated space where it will be possible to conveniently service the unit. Typically the HRV would be located in the mechanical room or an area close to the outside wall where the weather hoods will be mounted. If a basement area is not convenient or does not exist, a utility or laundry room may be u ...

  • Lifebreath RNC95 - page 14

    14 Suspending the RNC120D STRAPS AND SCREWS (supplied) JOIST F ASTENERS (not supplied) DET AIL Using full length hanger straps is recommended for vibration contr ol, but can be shorter if required. Horizontal Installation W all Mounting the HR V V er tical Installation The unit must be mounted le vel for pr oper drainage of the condensate pans. A T ...

  • Lifebreath RNC95 - page 15

    15 Drain Connection (HRV Only) During a defrost cycle, the HRV may produce some condensation. This water should flow into a nearby drain, or be taken away by a condensate pump. The HRV cabinet has prepunched holes for the drain (see below). Insert the drain spout through the hole in the drain pan. Do not forget the “O ring” which seals each spo ...

  • Lifebreath RNC95 - page 16

    16 The Three Methods of Installation The three methods of installation for the HRV system are the Simplified, Partially Dedicated and Fully Dedicated Installations. Refer to the installation illustrations in this manual. Simplified Installations The Simplified Installation draws stale air from the cold air return duct of the air handler/furnace and ...

  • Lifebreath RNC95 - page 17

    17 The Simplified Installation (Return/Return Method) Defrost air port needs to be drawn fr om clean area without combustion appliances. T o av oid backdrafting of combustion pr oducts, never draw defrost air from a room with a naturally aspirated appliance, i.e . furnace, hot water heater , gas dr yer , stove, fire place etc. W ARNING Air Handler ...

  • Lifebreath RNC95 - page 18

    18 The Partially Dedicated Installation Defrost air port needs to be drawn fr om clean area without combustion appliances. T o av oid backdrafting of combustion pr oducts, never draw defrost air from a room with a naturally aspirated appliance, i.e . furnace, hot water heater , gas dr yer , stove, fire place etc. W ARNING FIVE PORT MODELS - P ar ti ...

  • Lifebreath RNC95 - page 19

    19 The Fully Dedicated Installation Defrost air port needs to be drawn fr om clean area without combustion appliances. T o av oid backdrafting of combustion pr oducts, never draw defrost air from a room with a naturally aspirated appliance, i.e . furnace, hot water heater , gas dr yer , stove, fire place etc. W ARNING FIVE PORT MODELS - Full y Dedi ...

  • Lifebreath RNC95 - page 20

    Intake Weatherhood Requirements • Should be located upstream (if there are prevailing winds) from the exhaust outlet. • At least 6' (2m) from the exhaust weatherhood. • At least 6' (2m) away from dryer vents and air handler exhaust. • A minimum of 6' (2m) from driveways, oil fill pipes, gas meters, swimming pools or garbage c ...

  • Lifebreath RNC95 - page 21

    21 Electrical The HRV unit should be plugged into a standard designated (120VAC) electrical outlet with a ground. The outlet should be serviced by a separate 15 amp/120V circuit. An extension cord should not be used with this appliance. A qualified service technician should make any required electrical connections. Remote Control Connections Prior ...

  • Lifebreath RNC95 - page 22

    22 Red to Red Black to Black Green LED Drive to Green DEH UMI DISTA T Red to Red Orange to Orange Black to Black Dehumidistat Ventilation Control Part No. 99-116 20 Minute Timer (shown in a Decora cover plate)* Red to Red Black to Black Remote Dehumidistat Part No. 99-130W Remove factory installed jumper when installing this control Factory install ...

  • Lifebreath RNC95 - page 23

    23 Recirculating Damper Defrost (4 port models) The recirculating damper defrost HRV has an electronically controlled damper defrost mechanism. The defrost timer is activated when the outside temperature drops below 27°F (- 3°C). A motor driven damper door mechanism closes off the supply air from outside allowing the exhaust air to recirculate th ...

  • Lifebreath RNC95 - page 24

    24 It is necessary to have balanced air flow in an HRV. The volume of air brought in from the outside must equal the volume of air exhausted by the unit. If the air flow is not properly balanced, then: • The HRV may not operate at its maximum efficiency • A negative or positive air pressure may occur in the house • The unit may not defrost pr ...

  • Lifebreath RNC95 - page 25

    25 Air Flow Balancing Place pitot tube a minimum of 18" from blower or elbows Note: Duct connections may vary , depending on model. Outdoors MAGNEHELIC Pitot tube Magnehelic gauge M A GN E HELIC Magnehelic gauge Pitot tube Additional dampers may be required Placement of Pitot Tube HRV M AG NEHELIC DUCT AIR FLOW Pitot tube High Pressure Side Lo ...

  • Lifebreath RNC95 - page 26

    26 AccuFlow Gauge Kit 1 - Accu-Flow Balancing Gauge 2 - Connection Hoses 4 - Rubber Fittings 1 - Instruction Page Lifebreath Accu-Flow is designed to quickly and accurately balance the airflows on units equipped with balancing ports. Normally the HRV/ERV would be balanced on high speed. If the HRV/ERV is connected to a forced air system, both syste ...

  • Lifebreath RNC95 - page 27

    27 Air Flow Balancing using the Door Ports Models RNC155 and RNC200 Only The door ports ( MODELS RNC155 & RNC 200) are designed to quickly and measure the airflows for balancing. Normally the HRV would be balanced on high speed. If the HRV is connected to a forced air system, both systems should be set to run at the highest operational speed wh ...

  • Lifebreath RNC95 - page 28

    28 When using the Interface relay contacts to initiate b lower operation on a furnace, cer tain thermostats will initiate the outdoor cooling condenser when R and G are closed. Use this wiring configur ation to pre vent the Interf ace rela y contacts from initializing the condenser unit. This problem can occur at the thermostat because the Y ter mi ...

  • Lifebreath RNC95 - page 29

    29 Wiring Diagrams Model RNC5-TPD DEFROST DET AILS P1 12 3 4 PIN 1 - RED PIN 2 - ORANGE PIN 3 - BLACK PIN 4 - SP ARE PCB PLUG - IN RED BLACK PLUG IN CONNECTOR BI-DIRECTIONAL DAMPER MO TOR ORANGE RED BLACK ORANGE Model RNC5 (Only) TO MO TORS BLUE RED INTERF ACE RELA Y CONT A CTS ...

  • Lifebreath RNC95 - page 30

    30 Wiring Diagrams RNC120D HRV Control Box DEFROST DET AILS P1 12 3 4 PIN 1 - RED PIN 2 - ORANGE PIN 3 - BLACK PIN 4 - SP ARE PCB PLUG - IN RED BLACK PLUG IN CONNECTOR BI-DIRECTIONAL DAMPER MO TOR ORANGE RED BLACK ORANGE TO MO TORS INTERF ACE RELA Y CONT A CTS BLUE 60-120D-WIRING ...

  • Lifebreath RNC95 - page 31

    31 RNC3WIRINGDIAGRAM HIGHVOLTAGE 12VLOWVOLTAGE FIELDINSTALLED LEGEND 12VLOWVOLTAGE FANMOTORDETAILS CAPACITOR ORANGE WHITE BLACK GREEN DIRECTMOUNTEDCAPACITOR T6 T9 RED YELLOW P1 12 3 4 PIN1-BLACK PIN2-ORANGE PIN3-RED PIN4-SPARE PCBPLUG-IN RED BLACK PLUGIN CONNECTO ...

  • Lifebreath RNC95 - page 32

    32 Troubleshooting Poor Air Flow Supply air feels cold Dehumidistat is not Operating Humidity Levels are too High in Winter Condensation is appearing on the windows Humidity Levels are too Low HRV and / or Ducts Frosting up Condensation or Ice Build Up in Insulated Duct to the Outside Water in the bottom of the HRV 20 Minute Timer Not Working • 1 ...

  • Lifebreath RNC95 - page 33

    33 1. Inspect Exterior Hoods at least once a month. Make sure exhaust and fresh air supply hoods are not blocked or restricted by leaves, grass, or snow. In winter, it is especially important to make sure snow is not blocking the hoods or that frost has not built up on the wire mesh (bird screen). WARNING: Blockage of hoods may cause an imbalance. ...

  • Lifebreath RNC95 - page 34

    34 ...

  • Lifebreath RNC95 - page 35

    35 ...

  • Lifebreath RNC95 - page 36

    36 ...

メーカー Lifebreath カテゴリー Ventilation Hood

Lifebreath RNC95のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- RNC95の取扱説明書
- Lifebreathの製品カード
- パンフレット
- またはLifebreath RNC95の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Lifebreath RNC95の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Lifebreath RNC95の取り付け説明書、サービスマニュアル、簡易説明書、またはLifebreath RNC95のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Lifebreath RNC95の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Lifebreath RNC95デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがLifebreath RNC95を使用するのを助ける技術的文書のことです。説明書は通常、全てのLifebreath RNC95ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Lifebreathの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Lifebreath RNC95の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははLifebreath RNC95の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Lifebreath RNC95に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Lifebreath RNC95デバイスの基本機能を使うにあたってのヒント。 Lifebreath RNC95のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Lifebreath RNC95に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるLifebreath RNC95のメーカー/サービスへの連絡先に関する情報。

Lifebreath RNC95についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもLifebreath RNC95の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがLifebreath RNC95で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)