Toshiba ME00070Bの取扱説明書

32ページ 0.67 mb
ダウンロード

ページに移動 of 32

Summary
  • Toshiba ME00070B - page 1

    CONTENTS TMS7 SERIES ME00070B 1 CONTENTS Quick Start 2 1. Caution Statements 1.1 Cautions and warnings ............................................ 3 2. General Description 2.1 Feature list .............................................................. 4 2.2 Part Number format ................................................ 4 3. Specifications 3.1 ...

  • Toshiba ME00070B - page 2

    QUICK START 2 ME00070B TMS7 SERIES QUICK START For simple applications TMS7 sof t starters can be installed using the three simple steps outlined below. For applications with advanced control, protection or interface requirements a comprehensive review of this Users Manual is recommended. 1. Installation & Connection WARNING - ELECTRICAL SHOCK ...

  • Toshiba ME00070B - page 3

    CAUTION STATEMENTS TMS7 SERIES ME00070B 3 Caution Statements WARNING - ELECTRICAL SHOCK HAZARD The TMS7 contains dangerous voltages when connected to line voltage. Only a competent electrician should carry out the electrical installation. Improper installation of the motor or the TMS7 may cause equipment failure, serious injury or death. Fol low th ...

  • Toshiba ME00070B - page 4

    GENERAL DESCRIPTION 4 ME00070B TMS7 SERIES General Description 2.1 Feature List Starting • Current Limit mode. • R amp Start mode. Stopping • Soft stop. • Pump stop. • Soft braking. Protection • Overcurrent protection. • Motor thermistor input. • Current imbalance. • Phase rotation. • Stall protection. • Undercurrent. • Supp ...

  • Toshiba ME00070B - page 5

    SPECIFICATIONS TMS7 SERIES ME00070B 5 Specifications 3.1 Current Ratings Continuous Operation (Not Bypassed), 3 Wire Connection Start Current (%FLC) 300% 350% 400% 450% AC53a 3 - 10:70 - 10 45 o C <1000 metres AC53a 3.5 - 15:70 - 10 45 o C <1000 metres AC53a 4 - 20:70 - 10 45 o C <1000 metres AC53a 4.5 - 30:70 - 10 45 o C <1000 metres T ...

  • Toshiba ME00070B - page 6

    SPECIFICATIONS 6 ME00070B TMS7 SERIES Bypassed Operation ,3 Wire Connection Start Current (%FLC) 300% 350% 400% 450% AC53b 3 - 10:350 45 o C <1000 metres AC53b 3.5 - 15:345 45 o C <1000 metres AC53b 4 - 20:340 45 o C <1000 metres AC53b 4.5 - 30:330 45 o C <1000 metres TMS7 - 4007 18 18 16 14 TMS7 - 4015 34 34 34 28 TMS7 - 4018 41 41 41 ...

  • Toshiba ME00070B - page 7

    SPECIFICATIONS TMS7 SERIES ME00070B 7 3.2 Dimensions & Weights A B C a b Wei ght mm mm mm mm mm Kg IP42/NEMA 1 TMS7 - 4007 TMS7 - 4015 TMS7 - 4018 TMS7 - 4022 380 185 180 365 130 6 TMS7 - 4030 TMS7 - 4037 TMS7 - 4045 TMS7 - 4055 380 185 250 365 130 7 TMS7 - 4075 TMS7 - 4090 TMS7 - 4110 425 270 275 410 200 17.5 TMS7 - 4132 425 390 275 410 300 23 ...

  • Toshiba ME00070B - page 8

    SPECIFICATIONS 8 ME00070B TMS7 SERIES 3.4 Power Terminations T M S 7 - 40 07 ~ T M S 7 - 402 2 ( 3 . 5 N M , 2 . 6 FT - L B S ) 3 m m 14 m m 6 mm T M S 7 - 4 030 ~ T M S 7 - 40 55 ( 3 . 5 N M , 2 . 6 FT - L BS ) 4 m m 1 6 m m 6 mm T M S 7 - 4 07 5 ( 8 . 5 N M , 6 . 3 FT - L B S ) 5 m m 20 m m 8 m m T M S 7 - 40 90 ~ T M S 7 - 41 10 ( 8 . 5 N M , 6 ...

  • Toshiba ME00070B - page 9

    INSTALLATION TMS7 SERIES ME00070B 9 Installation 6.1 General Layout Diagrams TMS7 - 4007 ~ TMS7 - 4055 TMS7 - 4075 ~ TMS7 - 4132 TMS7 - 4150 ~ TMS7 - 4800 4.2 Power Termination Configuration The bus bars on models TMS7 - 4150 ~ TMS7 - 4800 can be adjusted to provide four different input/output power terminal configurations. I n p u t / O u t p u t ...

  • Toshiba ME00070B - page 10

    INST ALLATION 10 ME00070B TMS7 SERIES 4.4 Ventilation When installing TMS7 starters in an enclosure there must be sufficient air flow through the enclosure to limit heat rise within the enclosure. Temperature within the enclosure must be kept at, or below, the TMS7 maximum ambient temperature rating. If installing an TMS7 within a totally sealed en ...

  • Toshiba ME00070B - page 11

    POWER CIRCUITS TMS7 SERIES ME00070B 11 Power Circuits 5.1 Overview TMS7 starters can be wired with a number of different power circuits depending on application requirements. 5.2 3 Wire Connection This is the standard connection format. Supply voltage is connected to t he starter input terminals L1, L2 & L3. The motor cables are connected to th ...

  • Toshiba ME00070B - page 12

    POWER CIRUCITS 12 ME00070B TMS7 SERIES 5.7 Line contactors The TMS7 is designed to operate with or without a line contactor. In many regions there is a statutory requirement that a line contactor be employed with electronic motor control equipment. From a safety point of view, this is the preferable option, however is not necessary for starter oper ...

  • Toshiba ME00070B - page 13

    CONTROL CIRCUITS TMS7 SERIES ME00070B 13 Control Circuits 6.1 Electrical Schematic F L C SE L E C T I 43 I 44 I 11 I 12 I 2 1 I 22 I 3 3 R E SE T S T O P I 3 4 S T A R T O R O R C 7 C 6 4 - 20 m A O U T P U T ( M O T O R CUR R E N T ) P R O G R A MM AB L E O U T P U T C ( T r i pped ) RUN O U T P U T R 3 4 R 33 L2 B L3 B L1 B E T 2 R S 48 5 SE R I ...

  • Toshiba ME00070B - page 14

    CONTROL CIRCUITS 14 ME00070B TMS7 SERIES S t a r t s i g na l O u t pu t v o l t age R E L A Y F UNC T I O N S M a i n c o n t a c t o r S t a r t/ R u n R un P r e - s t a r t T e s t s Motor Thermistors Motor thermistors (if installed in the motor) may be connected directly to the TMS7. A trip will occur when the re sistance of the thermistor cir ...

  • Toshiba ME00070B - page 15

    CONTROL CIRCUITS TMS7 SERIES ME00070B 15 CAUTION NOTE: If no TMS7 starter is configured to the specific slave address, no response will be received by the host. The host software timeout should be set to a minimum of 250 ms. CAUTION NOTE: Slave address must be two digit, addresses less than 10 must have a leading zero (0). Master command to slave. ...

  • Toshiba ME00070B - page 16

    CONTROL CIRCUITS 16 ME00070B TMS7 SERIES or 02h 42h 31h 30h 35h 42h 03h 1. 35h (ASCII hex) = 5H = 00000101 42h (ASCII hex) = Bh = 00001011 Note: 03h is the EXT character (end of transmission) and is not part of the message. 2. 00000101 = 01010000 3. 01010000 + 00001011 = 01011011 4. 02h + 42h + 31h + 30h = A5h 5. A5h + 5Bh = 100h 6. The least signi ...

  • Toshiba ME00070B - page 17

    PROGRAMMING TMS7 SERIES ME00070B 17 Programming 7.1 Programming Procedure Step 1. Enter program mode. 1. Simultaneously press and release the <FUNCTION > and <STORE> keys. (When in program mode the three LEDs to the right of the numeric display will be illuminated.) Step 2. Select the function number to be viewed or adjusted. 1. Press a ...

  • Toshiba ME00070B - page 18

    PROGRAMMING 18 ME00070B TMS7 SERIES 7.2 Function List No. Function Primary Motor Setti ngs Default Setting 1 Motor full load current - 2 Current limit 350 3 Minimum current 350 4 Start ramp time 1 5 Stop ramp time 0 6 Motor trip class 10 7 Current imbalance sensitivity 5 8 Undercurrent protection 20 9 Stall protection 400 Start/Stop Formats 10 Soft ...

  • Toshiba ME00070B - page 19

    PROGRAMMING TMS7 SERIES ME00070B 19 Adjustment : Function 3 Minimum Current and Function 4 Start Ramp Time are used together to activate and co ntrol the Ramp Start mode. If the Ramp Start mode is required, set the Minimum Current so that the motor begins to accelerate immediately a start is initiated. Ramp Start mode is not required, set the Minim ...

  • Toshiba ME00070B - page 20

    PROGRAMMING 20 ME00070B TMS7 SERIES 7. Current Im balance Sensitivity Range : 1 – 10 1 = Highest sensitivity (lowest imbalance) I 5 = Average sensitivity I 10 = Lowest sensitivity (highest imbalance) Default Setting : 5 Description : Sets the sensitivity of the current imbalance protection. Adjustment : The factory setting is suitable for most ap ...

  • Toshiba ME00070B - page 21

    PROGRAMMING TMS7 SERIES ME00070B 21 Adjustment : Refer Function 21 Relay Output A Functionality for adjustment detail. 30. Phase Rotation Range : 0 – 2 0 = Off (forward and reverse rotation accepted) 1 = Forward rotation only (reverse rotation prohi bited) 2 = Reverse rotation only (forward rotation prohibited) Default Setting : 0 (Off) Descripti ...

  • Toshiba ME00070B - page 22

    PROGRAMMING 22 ME00070B TMS7 SERIES 61. RS485 Baud Rate Range : 1 – 5 1 = 1200 baud 2 = 2400 baud 3 = 4800 baud 4 = 9600 baud 5 = 19200 baud Default Setting : 4 (9600 baud) Description : Sets the baud rate for RS485 serial activity. Adjustment : Set as required. 62. RS485 Satellite Address Range : 1 - 99 Default Setting : 20 Description : Assigns ...

  • Toshiba ME00070B - page 23

    PROGRAMMING TMS7 SERIES ME00070B 23 83. Start Ramp Time Range : 1 – 30 Seconds Default Setting : 1 Second Description : Sets the ramp time for the Current Ramp start mode. Adjustment : Refer to Function 4 for further detail. 84. Stop Ramp Time Range : 0 – 100 Seconds Default Setting : 0 Second (Off) Description : Sets the soft stop ramp time fo ...

  • Toshiba ME00070B - page 24

    PROGRAMMING 24 ME00070B TMS7 SERIES Default Setting : 0 Description : Allows function adjustments be returned to the factory defaults. Adjustment : Set to 50 to load default parameter settings. 7.4 Operation Once installed, wir ed and programmed according to the instructions earlier in this manual the TMS7 can be operated. Local control panel. 1. N ...

  • Toshiba ME00070B - page 25

    PROGRAMMING TMS7 SERIES ME00070B 25 CAUTION NOTE: Function 20. Local/Remote Operation can be used to limit operation to either local or remote mode operation. If the <LOCAL/REMOTE> push button is used in an attempt to switch to a prohibited mode the numeric displ ay will show 'OFF'. CAUTION NOTE: Simultaneously pressing the <STOP ...

  • Toshiba ME00070B - page 26

    APPLICATION EXAMPLES 26 ME00070B TMS7 SERIES Application Examples 8.1 Installation With Line Contactor O R O R S 1 S t a r t C on t a c t Legend S 2 R e s e t P u s hbu t t on F 1 S e m i c ondu c t o r F u s e s ( op t i ona l ) K 1 M K 1 M L i ne C on t a c t o r C 24 m o de l s C 7 C 6 R 34 R 33 L2 B L3 B L1 B E T 2 G N D C 5 C 4 C 3 R 43 R 44 M ...

  • Toshiba ME00070B - page 27

    APPLICATION EXAMPLES TMS7 SERIES ME00070B 27 8.3 Sof t Braking I 34 I 33 I 12 I 11 I 21 I 2 2 S T A R T S T O P R ESE T K 2 A S 3 S 3 R ESE T P U S H B U T T O N S 2 S T O P P U S H B U T T O N B R AK E D E L AY T I M E R RUN D E L A Y T I M E R K 2 T K 1 T L I N E C O N T A C T O R ( RUN ) K 1 M L I N E C O N T A C T O R ( B R AK E ) K 2 M S 1 S T ...

  • Toshiba ME00070B - page 28

    APPLICATION EXAMPLES 28 ME00070B TMS7 SERIES 8.4 Two Speed Motors I 34 I 33 L E G E ND K 2 A K 1 M R E M O T E S T A R T R E L AY ( H I G H SP EE D ) L I N E C O N T A C T O R ( H I G H S PE E D ) K 1 A R E M O T E S T A R T R E L AY ( L O W SP EE D ) K 2 M K 3 M S 1 L I N E C O N T A C T O R ( L O W SP EE D ) S T A R C O N T A C T O R ( H I G H SP ...

  • Toshiba ME00070B - page 29

    TROU BLE SHOOTING TMS7 SERIES ME00070B 29 Section 9 Trouble Shooting 9.1 Trip Codes When the TMS7 enters the trip state the cause o f the trip is indicated on the LED display panel. Code Description 0 Shorted SCR The TMS7 has detected a shorted SCR(s). 1. Determine the affected phase using the 3 phase indicators LEDs located on the left hand side o ...

  • Toshiba ME00070B - page 30

    TROUBLE SHOOTING 30 ME00070B TMS7 SERIES Code Description TMS7 and reconnect the motor in 6 Wire. Incorrect main control module. The TMS7 is fitted with an incompatible main control module. 1. Fit a suitable main control module. u CPU error Reset the TMS7. If the problem persists contact your supplier. 9.2 Fault History The TMS7 includes a Fault Hi ...

  • Toshiba ME00070B - page 31

    TROU BLE SHOOTING TMS7 SERIES ME00070B 31 Symptom Cause Erratic motor operation and tripping. SCRs not latching. SCRs require a minimum current flow to ‘latch’ on. In situations where very small motors are being controlled by large soft starters the current drawn may be insufficient to latch on the SCRs. Increase motor size or reduce soft start ...

  • Toshiba ME00070B - page 32

    APPENDIX 32 ME00070B TMS7 SERIES Appendix 10.1 Typical Start Current Requirements 300% 350% 400% 450% Agitator — Atomiser — Bottle Washer — Centrifuge — Chipper — Compressor - Recip (loaded) — Compressor - Recip (unloaded) — Compressor - Screw (loaded) — Compressor - Screw (unloaded) — Conveyor - Belt — Conveyor - Roller — Con ...

メーカー Toshiba カテゴリー Remote Starter

Toshiba ME00070Bのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- ME00070Bの取扱説明書
- Toshibaの製品カード
- パンフレット
- またはToshiba ME00070Bの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Toshiba ME00070Bの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Toshiba ME00070Bの取り付け説明書、サービスマニュアル、簡易説明書、またはToshiba ME00070Bのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Toshiba ME00070Bの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Toshiba ME00070Bデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがToshiba ME00070Bを使用するのを助ける技術的文書のことです。説明書は通常、全てのToshiba ME00070Bユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Toshibaの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Toshiba ME00070Bの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははToshiba ME00070Bの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Toshiba ME00070Bに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Toshiba ME00070Bデバイスの基本機能を使うにあたってのヒント。 Toshiba ME00070Bのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Toshiba ME00070Bに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるToshiba ME00070Bのメーカー/サービスへの連絡先に関する情報。

Toshiba ME00070Bについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもToshiba ME00070Bの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがToshiba ME00070Bで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)