    Inst allation InRow ™ RC ACRC100 ACRC103 ...

  • APC ACRC100 - page 2

    This manual is available in English on the enclosed CD. Dieses Handbuch ist in Deutsch auf der beiliegenden CD -ROM verfügbar . Deze handleiding staat in het Nede rlands op de bijgevoegde cd. Este manual está disponible en español en el CD-ROM adjunto. Ce manuel est disponible en français sur le CD-ROM ci-inclus. Questo manuale è disponibile i ...

  • APC ACRC100 - page 3

    American Power Conversion Legal Disclaimer The information presented in this manual is not warranted by the American Power Conversion Corporation to be authoritative, error free, or co mplete. This pub lication is not meant to be a substitute for a detailed operational and site specific development plan. Th erefore, American Power C onversion Corpo ...

  • APC ACRC100 - page 4

    ...

  • APC ACRC100 - page 5

    Content s InRow RC Installati on i General Information .................. ...................................... 1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Save these instruct ions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Manual updates . . . . . . . . ...

  • APC ACRC100 - page 6

    InRow RC Installati on ii Mechanical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Connect piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Chiller . . . . . . . ...

  • APC ACRC100 - page 7

    1 InRow RC Installation General Information Overview Save these instructions This manual contains important instructions that must be followed during the installation of this equipment. Manual up dates Check for updates to this manual on the APC W eb site, www .apc.com/support . Click on the User Manuals link and enter the manual part number or SKU ...

  • APC ACRC100 - page 8

    InRow RC Installati on 2 WA R N I N G DAMAGE TO EQUIPM ENT OR PERSONNEL The equipment is heavy and ca n easily be tipped. For safety purposes, adequate personnel must be present when moving this equipme nt. Failure to follow these instructions can result in death, injury , or equipment damage. CAUTION HAZARD TO EQUIPMENT OR PERSONNEL All work must ...

  • APC ACRC100 - page 9

    3 InRow RC Installation Inspecting the Equipment Inspect for missing compon ents. All shipped loose compon ents are identified by pa rt number and description on the bill of lading. Ensure each item is present before acceptin g delivery of the unit. Filing a claim. If damage has occ urred, or if shipped loose parts are missing, report it im mediate ...

  • APC ACRC100 - page 10

    InRow RC Installati on 4 Component Identification Exterior 1 Removable rear door 8 Door lock (front and rear doors) 2 Side panel latch 9 T op ne twork wiring access 3 Removable side panel : T o p supply (inlet) 4 Caster ; T op condensate drain 5 Adjustable level ing foot < T op return (outlet) 6 Display interface = T op power cord access 7 Remov ...

  • APC ACRC100 - page 11

    5 InRow RC Installation Interior 1 Air filter ; Bottom supply connection (op tional) 2 T op supply connection (opti onal) < Drain valve (cap is installed at factory) 3 T op return connection (optional) = User interface connection box 4 2-way supply valve (1-inch) > Power supply unit (PSU ) 5 Flow meter ? Bottom condensate drain pan 6 3-way va ...

  • APC ACRC100 - page 12

    InRow RC Installati on 6 User interface connection p anel 1 A-Link ports 5 Control RS-485 po rt 2 Reset button 6 Form C alarm contacts and shutdown input 3 Ethernet port 7 Configuration port 4 Building management system (BMS) RS-485 port 8 Leak detector port na22 36a ...

  • APC ACRC100 - page 13

    7 InRow RC Installation Room Prep aration During the design of the data center , consider ease of entry for the equipment, floor loading factors, and accessibility to piping and wiring. Seal the room with a vapor barrier to minimize moi s ture infiltration. (Polyeth ylene film is rec ommended for ceiling and wall applications.) Apply rubber- or pla ...

  • APC ACRC100 - page 14

    InRow RC Installati on 8 Piping Diagrams With cooling distribution unit (CDU) Note: Install isolation valves and particulate stra iners with 20 mesh stainless steel screen (opening size = 865 micron) in the supply line between the chiller an d the CDU. If the system is to be set up as an isolated loop - a chiller and pipe layout, dedicated only to ...

  • APC ACRC100 - page 15

    9 InRow RC Installation Without CDU Note: Install isolation valves and particulate st rainers with 20 mesh stainless steel screen (opening size = 865 micron) in the supply line between the chiller an d the CDU. If the system is to be set up as an isolated loop - a chiller and pi pe layout, dedicated only to supplying RC units and no other equipm en ...

  • APC ACRC100 - page 16

    InRow RC Installati on 10 Internal piping diagram 1 Entering water un ion (top piping) 8 Entering water union (botto m piping) 2 Leaving water union (top piping) 9 Bottom condensate pan 3 3-way actuator control valve—3/4 in : Bottom coil 4 Bypass shutoff ball valve—3/4 in ; T op cond ensate pan 5 Condensate drain < T op coil 6 Leaving water ...

  • APC ACRC100 - page 17

    11 InRow RC Installation Piping and electrical ac cess locations Dimensions are shown in mm (in). 1 Power connections 7 Power connections 2 1-in NPT female (return) 8 Low voltage i nput wiring (cu stomer) 3 1-in NPT female (supply) 9 1-in NPT female (supply) 4 Low voltage input wiring (customer-supplied) : Condensate line—0.25 in ID /0.38 in OD 5 ...

  • APC ACRC100 - page 18

    InRow RC Installati on 12 W eight s and Dimensions na15 51a Net weight (equipment only) 162.77 kg (358.5 lb) Dimensions are shown in mm (in). ...

  • APC ACRC100 - page 19

    13 InRow RC Installation Inst allation Removing Doors and Panels WA R N I N G MOVING P ARTS HAZARD • Do not open doors and panels if the equipment is operating Failure to follow these instructions can re sult in death, serious injury , or equipment damage. CAUTION UNPROTECTED P ARTS Be careful when placing doors when removed from the equipment. S ...

  • APC ACRC100 - page 20

    InRow RC Installati on 14 Positioning the Equipment Service acce ss An area of 1 143 mm (45 in) of clear floor space in front and 914.4 mm (36 in) in back of the equipment is required for service. All required maintenance can be performed from the front or back of the equipment . Leveling The leveling feet provide a stable base if the floor is unev ...

  • APC ACRC100 - page 21

    15 InRow RC Installation S t abilizing the Equipment Floor bracket s T o prevent the equipment from moving from its final lo cation (if it is not joined with an enclosure), use the included bolt-down kit (AR7701). Follow the in stallation instructions included wi th the kit. Joining to enclosures NetShelter ™ SX enclos ure. Tw o joining brackets ...

  • APC ACRC100 - page 22

    InRow RC Installati on 16 Mechanical Connections Piping Note: Ensure coolant water qua lity complies with guidelines set forth in IB0125GB001. Wa t e r. Install shutoff valves for routine service and emergency isolation of the equipment. When a CDU is not used, you must install circuit setters to regulate the chilled water flow for each InRow RC ai ...

  • APC ACRC100 - page 23

    17 InRow RC Installation Connect piping See “Piping Diagrams,” beginning on page 8 , for recommended valve, flexible adapter , and strainer installation locations. 1. Route all piping 1 to the InRow RC in compliance w ith all local and national codes. Note: Circuit setters are required to regulate the flow of chilled water to each piece of equi ...

  • APC ACRC100 - page 24

    InRow RC Installati on 18 Condensate pump. The pump is factory-wired and p iped internally to the lower condensat e pan. The pump is capable of moving liquid a maximum of 15.2 m (50 ft), including a maximum lift of 4.9 m (16 ft). Fo r example, if your lift is 3 m (10 ft), you have 12 .2 m (40 ft) of usable run. The pump also uses an on-board conden ...

  • APC ACRC100 - page 25

    19 InRow RC Installation Condensate pump drai n inst allation. The condensate drain line is coiled inside the equipment, allo wing you to route the condensate drain line for either top or bottom use. See the t a ble “Piping and electrical access locations” on page 1 1 for more information. Use the provided grommets to properly se cure and prote ...

  • APC ACRC100 - page 26

    InRow RC Installati on 20 Filling and Purging When the equipment is properly piped, begin the filling process (top piping configuration shown). 1. Open the 2-way supp ly valve and the 2-way by pass shutoff valve. 2. Using a 2.5-mm hex key , turn the flow co ntrol actuator to th e fully open position. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR A ...

  • APC ACRC100 - page 27

    21 InRow RC Installation 3. Slightly open the top coil vent. 4. At the water supply , open the appropriate valves to begin letting water slowly enter the equipment. 5. At the equipment, close the top coil vent when water begins slowly flowing out of the vent. 6. At the water supply: a. Open all valves (no greater than 76 l/m [20 gpm]), allowing the ...

  • APC ACRC100 - page 28

    InRow RC Installati on 22 Electrical Connections The following electrical connectio ns are require d in the field: • Feeds A and B •A - L i n k • Network Management Card • T em perature s ensor • Communication (b uilding management system) See the electrical schematic (l ocated on the lid of the elec trical box) for all electrical connect ...

  • APC ACRC100 - page 29

    23 InRow RC Installation Power connections Power cords may be routed through the top of the eq uipment (standard) or through the bottom (optional). T op wiring configuration (st andard). 1. Route power cords through the equipment to the top power cord access, as shown. 2. Push the power cords through the hole at the top power cord entrance. 3. Secu ...

  • APC ACRC100 - page 30

    InRow RC Installati on 24 User interface connection pinout 1 A-Link port Pin 1=High; Pin 2=Low; Pins 3, 6=Perf Power; Pins 4, 5=Ground 9 24 Vdc (bi as) 2 Reset button : 12 Vdc (bi as) 3 Networ k port Pins 1-8 = Standard RJ-45 ; Return (bias) 4 Shield/ground < NO (normally open contact) 5 A-=T rue = COM (common contact) 6 B+=T rue > NC (normal ...

  • APC ACRC100 - page 31

    25 InRow RC Installation A-Link port s Note: All input and o utput connections should be wired as Class 2 circuits. Depending on the equipment config uration, additional control connections may be required for the A-Link remote communications through APC Network Management Card support or other equipment- monitoring software. A special RJ-45 termin ...

  • APC ACRC100 - page 32

    InRow RC Installati on 26 Network port 1 LAN cable (10/100 Base-T) na224 7a Switch/Hub First InRow RC Second InRow RC Last InRow RC ...

  • APC ACRC100 - page 33

    27 InRow RC Installation Modbus Control connector 1 150 Ω termination resistor (provided) 2 Modbus cable (RS-485) 1 150 Ω termination resistor (provided) 3 Peripheral device (example: chiller) 2 Control cable (RS-485) na22 48 a Modbus MASTER First InRow RC Second InRow RC Last InRow RC na224 9a ...

  • APC ACRC100 - page 34

    InRow RC Installati on 28 Form C alarm cont acts and shut down input A relay internal to the user interface is typically co ntrolle d by a user-defined alarm (malfunctioning fans, for example). Before an alarm is de tected, the voltage on the COM terminal is routed to the NC terminal. When the alarm is activated, the relay is ener gize d, causing t ...

  • APC ACRC100 - page 35

    29 InRow RC Installation T emperature sensor The remote temperature sensor mo nitors the room temperature, monitoring the environment surro unding the cooling equipment to ensure that the conditioned air is cooling the area. Note: The remote temperature sensor comes coiled inside the equipment as shown, and must be mounted as follows, or the equipm ...

  • APC ACRC100 - page 36

    11 / 2 0 1 2 990-2402D-00 1 APC W orldwide Customer Support Customer support for this or any other APC product is available at no char ge in any of the following ways: • V isit the APC W eb site to acce ss documents in the APC Knowledg e Base and to submit customer support requests. – www .apc.com (Corporate Headquarters) Connect to localized A ...

メーカー APC カテゴリー Computer Accessories

APC ACRC100のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- ACRC100の取扱説明書
- APCの製品カード
- パンフレット
- またはAPC ACRC100の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、APC ACRC100の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、APC ACRC100の取り付け説明書、サービスマニュアル、簡易説明書、またはAPC ACRC100のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、APC ACRC100の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

APC ACRC100デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがAPC ACRC100を使用するのを助ける技術的文書のことです。説明書は通常、全てのAPC ACRC100ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

APCの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. APC ACRC100の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははAPC ACRC100の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。APC ACRC100に関してこのドキュメントで見つけることができる全てのヒントの目次
3. APC ACRC100デバイスの基本機能を使うにあたってのヒント。 APC ACRC100のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。APC ACRC100に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるAPC ACRC100のメーカー/サービスへの連絡先に関する情報。

APC ACRC100についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもAPC ACRC100の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがAPC ACRC100で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)