    ZONEKIT2ZCAR WeatherMaker® Two-Zone Installation and Start-Up Instructions NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. TABLE OF CONTENTS PAGE Safety Considerations .....................................................................1 Installation Consideration ...

  • Carrier ZONEKIT2ZCAR - page 2

    Step 2—Wiring To prevent personal injury or possible equipment damage, disconnect the power supply before routing wire. All wiring must comply with local, state, and national codes. NOTE: Use No. 18 AWG color-coded, insulated (35°C min) wire. If thermostats are to be located more than 100 ft from the WeatherMaker Two-Zone Center as measured alon ...

  • Carrier ZONEKIT2ZCAR - page 3

    2. Properly seal joint using duct tape, mastic, or other approved method. Do not allow mastic to come in contact with actuator. 3. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check your local codes.) (See Fig. 7.) NOTE: All zone dampers and ductwork must be properly sup- ported according to local codes or SMACNA standards. NOTE: There sho ...

  • Carrier ZONEKIT2ZCAR - page 4

    Step 5—Install Barometric Bypass Damper NOTE: The barometric bypass damper is a critical part of the WeatherMaker Two-Zone System for control of minimum airflow and noise reduction. It is recommended that the bypass be installed. The bypass should be installed according to local codes and SMACNA standards. Be sure the bypass is properly supported ...

  • Carrier ZONEKIT2ZCAR - page 5

    In automatic changeover, the zoning system works on a first come first serve basis. If 1 zone is calling for heating and the other for cooling, the zone which sent its demand to the I/O center first will operate the equipment in that mode until that zone is satisfied. Step 5—Duct Temperature Optimizer (DTO) For Monitoring Leaving Air Temperature ...

  • Carrier ZONEKIT2ZCAR - page 6

    Fig. 12—WeatherMaker Two-Zone Circuit Board with Standard Thermostat Wiring A97293 3 Thermostat Zone 2 Y 2 Y 1 R W 1 W 2 C G Thermostat Zone 1 Y 2 Y 1 R W 1 W 2 C Sensors HP Duct Equipment R c B O Y 2 Y 1 W 1 W 2 G R h 24 VAC Power 24 v CL OP C Zone 1  Damper Zone 2  Damper CL OP C G B D 4 F A E C K J I H L M N 2 3 1 ZONE 1? ...

  • Carrier ZONEKIT2ZCAR - page 7

    NOTE: An HP temperature sensor must be used with a heat pump application using electric strip heat. This is necessary in case the DTO is set to the Off position. Timeguard The WeatherMaker Two-Zone provides equipment protection with an internal 5-minute timeguard delay. This delay is present upon initial power up. There is also a 5-minute timeguard ...

  • Carrier ZONEKIT2ZCAR - page 8

    timer will start counting down 15, 14, 13...0 minutes. Once the timer expires the control will allow a new mode to restart the equipment. The internal time, as well as the cooling 5-minute timeguard can be cleared by using the comprotec override feature. CARE AND MAINTENANCE For continuing optimum performance and to minimize possible equipment fail ...

  • Carrier ZONEKIT2ZCAR - page 9

    TROUBLESHOOTING This section contains information to assist you in troubleshooting problems and errors associated with the WeatherMaker Two-Zone system. See Table 2. Step 1—System Diagram, Jumpers, and Switches NOTE: For correct control board operation, it must have either a sensor attached or a 10k resistor in place at the duct and HP inputs. 1 ...

  • Carrier ZONEKIT2ZCAR - page 10

    I Red LED—Displays ON when fan is energized. J Red LED—Displays ON when first-stage cooling is energized. K Red LED—Displays ON when second-stage cooling is energized. L Red LED—Displays ON when reversing valve is ener- gized. M Red LED—Displays ON when first-stage heat is energized. N Red LED—Displays ON when second-stage heat is energ ...

  • Carrier ZONEKIT2ZCAR - page 11

    Table 3 shows a temperature/ohm/voltage relationship to help aid in troubleshooting the WeatherMaker Two-Zone System. This table will evaluate both the Duct/HP temperature sensor operation. Use a digital multimeter to perform the following: To verify a sensor is good, disconnect both leads from the I/O board and measure the resistance through the s ...

  • Carrier ZONEKIT2ZCAR - page 12

    → Fig. 17—Typical Fan Coil With Single-Speed Air Conditioner A97298 SINGLE-SPEED AIR CONDITIONER TYPICAL FAN COIL C Y G W2 W3 C R Y/Y2 O L E RH G W2 W1 Y1 Y2 O B RC TWO-ZONE SYSTEM See notes 1 and 3 * * * * * Y1 * * → Fig. 15—Single-Stage Furnace With Single-Speed Air Conditioner A97296 SINGLE-SPEED AIR COND ...

  • Carrier ZONEKIT2ZCAR - page 13

    → Fig. 21—Typical Fan Coil With 2-Speed Air Conditioner A97302 2-SPEED AIR CONDITIONER TYPICAL FAN COIL R G R C W2 Y/Y2 E W3 L O Y1 C Y2 Y1 RH G W2 W1 Y1 Y2 O B RC TWO-ZONE SYSTEM See notes 1, 2, and 3 * * * * * → Fig. 19—Single-Stage Furnace With 2-Speed Air Conditioner A97300 2-SPEED AIR CONDITIONER SINGLE ...

  • Carrier ZONEKIT2ZCAR - page 14

    → Fig. 23—Single-Stage Furnace With Single-Speed Heat Pump A97304 SINGLE-STAGE FURNACE TWO-ZONE SYSTEM INTERFACE CONTROL R GF RF WF R GT E HP O HP OT Y HP C W2 Y O RH G W2 W1 Y1 Y2 O B RC G R W C SINGLE-SPEED HEAT PUMP YT E T C  Y 2 1 3  OUTDOOR THERMOST A T (KHAO T0301FST) See notes 4, 5, 6, a ...

  • Carrier ZONEKIT2ZCAR - page 15

    → Fig. 27—Single-Stage Furnace With 2-Speed Heat Pump A97308 2-SPEED HEAT PUMP SINGLE-STAGE FURNACE R G R C W Y C Y2 W3 RH G W2 W1 Y1 Y2 O B RC TWO-ZONE SYSTEM W2 Y1 O See notes 2, 5, 6, 7, 9, 10, and 11 → Fig. 25—Typical Fan Coil With Single-Speed Heat Pump A97306 SINGLE-SPEED HEAT PUMP TWO-ZONE SYSTEM TYPI ...

  • Carrier ZONEKIT2ZCAR - page 16

    → Fig. 29—Typical Fan Coil With 2-Speed Heat Pump A97310 RH G W2 W1 Y1 Y2 O B RC 2-SPEED HEAT PUMP TYPICAL FAN COIL C G W2 Y/Y2 R C W3 L E Y1 R W2 O W3 Y1 Y2 O TWO-ZONE SYSTEM See notes 1, 2, 3, 9, and 11 * * * * * → Fig. 30—FK4C Fan Coil With 2-Speed Heat Pump A97311 FK4C FAN COIL R R G W1 C DH W2 Y1 Y/Y2 O ...

メーカー Carrier カテゴリー Air Conditioner

Carrier ZONEKIT2ZCARのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- ZONEKIT2ZCARの取扱説明書
- Carrierの製品カード
- パンフレット
- またはCarrier ZONEKIT2ZCARの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Carrier ZONEKIT2ZCARの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Carrier ZONEKIT2ZCARの取り付け説明書、サービスマニュアル、簡易説明書、またはCarrier ZONEKIT2ZCARのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Carrier ZONEKIT2ZCARの製品を使用するにあたって最も人気のある説明書を閲覧できます。

Carrier ZONEKIT2ZCARデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがCarrier ZONEKIT2ZCARを使用するのを助ける技術的文書のことです。説明書は通常、全てのCarrier ZONEKIT2ZCARユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Carrierの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Carrier ZONEKIT2ZCARの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははCarrier ZONEKIT2ZCARの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Carrier ZONEKIT2ZCARに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Carrier ZONEKIT2ZCARデバイスの基本機能を使うにあたってのヒント。 Carrier ZONEKIT2ZCARのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Carrier ZONEKIT2ZCARに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるCarrier ZONEKIT2ZCARのメーカー/サービスへの連絡先に関する情報。

Carrier ZONEKIT2ZCARについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもCarrier ZONEKIT2ZCARの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがCarrier ZONEKIT2ZCARで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)