Summary
  • Rackmount PRO1100E - page 1

    ...

  • Rackmount PRO1100E - page 2

    1 © Copyright Para Systems, Inc., 2003 PRO-E Series User's Manual 1 . Introduction 2 2 . Controls and Indicators 5 3. Installation 7 4 . Operation 9 5 . T roubleshooting 12 6 . Replacing the Battery 13 7 . Obtaining Service 16 8 . Specifications 17 9 . Configurable Parameters & Settings 18 10 . Limited Product W arranty 19 1 1 . Declarati ...

  • Rackmount PRO1100E - page 3

    2 IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS ! English Thank you for purchasing a MINUTEMAN power protection product. It has been designed and manufactured to provide many years of trouble free service. Please read this manual before installing your PRO-E Series UPS, models PRO500E, PRO700E, PRO1 100E, PRO1500E, PRO500iE, PRO700iE, PRO ...

  • Rackmount PRO1100E - page 4

    3 W ARNING: Risk of Electrical Shock. Hazardous live parts inside these power supplies are energized from the battery even when the AC input is disconnected. T o de-energize the outputs of the UPS: 1. If the UPS is on press and release the On/Of f/T est button. 2. Disconnect the UPS from the AC wall outlet. 3. T o de-energize the UPS completely , d ...

  • Rackmount PRO1100E - page 5

    4 English Para Systems Life Support Policy As a general policy , Para Systems Inc. (Para Systems) does not recommend the use of any of its products in life support applications where failure or mal- function of the Para Systems product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or ef ...

  • Rackmount PRO1100E - page 6

    5 On-Line On-Battery Buck Boost English On-Line/On-Battery/Boost/Buck LED Overload LED Weak/Bad Battery LED On/Of f/T est Button Fault LED Press and release the ON/OFF/T est Button after 1 beep to turn the UPS ON or OFF (see section 4). The On-Line/On-Battery/Boost and Buck (green) LED illuminates in a steady state when the UPS is on and supplying ...

  • Rackmount PRO1100E - page 7

    6 REAR P ANEL English 5 4 3 2 1 10 8 6 7 9 5 4 3 2 1 8 6 7 9 1. The Information/Rating Label. 2. The Battery Backup and Surge output power receptacles are NEMA 5-15R type (IEC 320 C13 sockets for 230V models). 3. The USB Communications Interface Port is for UPS monitoring and control. 4. The RS232 Communications Interface Port is for UPS monitoring ...

  • Rackmount PRO1100E - page 8

    7 INST ALLA TION PLACEMENT The PRO-E series is intended to be install in a temperature controlled environ- ment that is free of conductive contaminants. Select a location which will pro- vide good air circulation for the UPS at all times. Avoid locations near heating devices, water or excessive humidity , or where the UPS is exposed to direct sunli ...

  • Rackmount PRO1100E - page 9

    8 English DO NOT plug Power Strips or Surge Protection Devices into the ”Battery Backup” Receptacles on the UPS. Plugging Power Strips or Surge Protection Devices into the “Battery Backup” Receptacles may cause internal damage to the UPS, the Power Strip, or the Surge Protection Device. W ARNING! CHARGING THE BA TTER Y The PRO-E Series UPS ...

  • Rackmount PRO1100E - page 10

    9 English TURNING THE UNIT ON/OFF ON / OFF / T est Button SELF TEST Press and release the ON/OFF/T est Button after one beep to turn the UPS ON and supply power to the load. The load is immediately powered while the UPS runs a two-second self test. Press and release the ON/OFF/T est Button after one beep to turn the UPS OFF . The UPS will continue ...

  • Rackmount PRO1100E - page 11

    10 English ALARMS ON BA TTER Y When the UPS is operating on the batteries, the On-Battery LED will blink and the audible alarm will sound once every 10-seconds. The alarm will stop once the UPS returns to the On-Line operation. UPS F AUL T When the UPS detects a hardware fault, the Fault LED will illuminate and the UPS will sound a constant alarm. ...

  • Rackmount PRO1100E - page 12

    11 COMMUNICA TIONS PORTS (RS232 and USB) The RS232 communication port is a standard DB9 female with both RS232 and simulated contact closure capability . The PRO-E series UPS will poll the port and activate the port for RS232 or contact closure in accordance with the type of cable it finds connected to the port. T o change the port configuration re ...

  • Rackmount PRO1100E - page 13

    12 English Possible Cause Symptom What T o Do Press and release the On/Off/ T est button to start UPS On/Of f/T est button not pushed UPS will not turn on Reset circuit breaker by pressing the plunger back in. If the AC circuit breaker trips after UPS starts up, reduce the load on the UPS UPS operates in battery mode only , even though there is nor ...

  • Rackmount PRO1100E - page 14

    13 REPLACING THE BA TTER Y W ARNING! This Uninterruptible Power Supply contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond battery replacement procedures below . This UPS contains no user serviceable parts. Repairs and Battery replacement must be performed by AUTHORIZED SERVICE PERSONNEL ONL Y . Do not open or muti ...

  • Rackmount PRO1100E - page 15

    14 English BA TTER Y REPLACEMENT PROCEDURE PLEASE READ THE CAUTIONS AND W ARNINGS BEFORE A TTEMPTING TO REPLACE THE BA TTERIES Hot-swappable batteries mean that the batteries can be replaced without powering down the whole UPS system. NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will ...

  • Rackmount PRO1100E - page 16

    15 9. Disconnect the positive (red) wire from the battery positve terminal. 10. Disconnect the battery negative (black) wire from the battery negative terminal. NOTE: Use CAUTION, do not touch the battery positive wire to the battery negative wire. 1 1. Remove the battery bracket retaining screw and slide the battery bracket upwards. 12. Using the ...

  • Rackmount PRO1100E - page 17

    16 English IF THE UPS REQUIRES SERVICE 1.Use the TROUBLESHOOTING section to eliminate obvious causes. 2.V erify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem. 3.Call your dealer for assistance. If you cannot reach your dealer , or if they cannot resolve the problem call or fax MINUTEMAN T echnical Suppo ...

  • Rackmount PRO1100E - page 18

    17 Default 120V (230V) / User selectable at 120/127V , (208/230V) 3-5 years, depending on discharge cycles and ambient temp 500V A 350W 700V A 490W 1500V A 1050W 1 100V A 770W 500 J (440 J) 0 ns (instantaneous) normal mode; <5 ns common mode <5% Normal and common mode EMI/RFI suppression 1-12V9Ah 2-12V7Ah 3-12V7Ah Audible noise at 1 m (3 ft.) ...

  • Rackmount PRO1100E - page 19

    18 English (These items may require optional software or hardware) Function Factory Default Description User Choices Set inverter output voltage Shut- down T ype Set audible alarm state Enable/ Disable auto restart Battery life in days Battery install date UPS ID PRO-E Date of manufacture 1826 Enabled Enabled UPS output 120V AC (230V AC) Up to 64 c ...

  • Rackmount PRO1100E - page 20

    19 English Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equip- ment sites within the United States and Canada, this warranty covers repair or replacement of defective equipme ...

  • Rackmount PRO1100E - page 21

    20 English EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL P ARA SYSTEMS BE LIABLE FOR DIRECT , INDIRECT , SPECIAL, INCIDENT AL, OR CONSEQUEN- TIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT , EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically , Para Sys- tems is not liable for any costs, such as lost profits or revenue, loss of equip- ...

  • Rackmount PRO1100E - page 22

    21 DECLARA TION OF CONFORMITY Application of Council Directive(s): 89/336/EEC, 73/23/EEC Standard(s) to which Conformity is declared: EN50091-1-1, EN50091-2 Manufacturer’s Name: Para Systems, Inc. (MINUTEMAN UPS) Manufacturer’s Address: 1455 LeMay Drive Carrollton, T exas 75007 USA T ype of Equipment: Uninterruptible Power Supplies (UPS) Model ...

  • Rackmount PRO1100E - page 23

    22 English Notes: ...

  • Rackmount PRO1100E - page 24

    Rac kmount Solutions, Ltd. 915 S . Jupiter Road Garland, TX 75042 www .rackmountsolutions .net sales@rac kmountsolutions.net 1-866-207-6631 | F ax 972-276-6484 GSA Contract # GS-35F-0208R f or IT 70 Approv ed vendor on ITSS (IT Solutions Acquisitions System) ...

メーカー Rackmount カテゴリー Power Supply

Rackmount PRO1100Eのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- PRO1100Eの取扱説明書
- Rackmountの製品カード
- パンフレット
- またはRackmount PRO1100Eの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Rackmount PRO1100Eの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Rackmount PRO1100Eの取り付け説明書、サービスマニュアル、簡易説明書、またはRackmount PRO1100Eのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Rackmount PRO1100Eの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Rackmount PRO1100Eデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがRackmount PRO1100Eを使用するのを助ける技術的文書のことです。説明書は通常、全てのRackmount PRO1100Eユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Rackmountの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Rackmount PRO1100Eの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははRackmount PRO1100Eの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Rackmount PRO1100Eに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Rackmount PRO1100Eデバイスの基本機能を使うにあたってのヒント。 Rackmount PRO1100Eのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Rackmount PRO1100Eに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるRackmount PRO1100Eのメーカー/サービスへの連絡先に関する情報。

Rackmount PRO1100Eについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもRackmount PRO1100Eの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがRackmount PRO1100Eで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)