  • Panasonic CU-5E36QBU - page 1

    © Panasonic Corporation 2013 Order No: PAPAMY1312037CE Air Conditioner Outdoor Unit CU-5E36QBU Destination U.S.A. Canada Please file and use this manual together w ith the servic e manual for Model No. CS- E9NKUAW CS-E12NKUAW CS-E18 NKUA, CS-E24NKUA, CS-ME7QK UA, Order No. PHAAM1111087C1 PAPAMY1204088CE PAPAMY 1312045CE PRECAUTION OF LOW TEMPERATU ...

  • Panasonic CU-5E36QBU - page 2

    2 TABLE OF CONTENTS PAGE PAGE 1. Safety Pr ecautions ............................................. 3 2. Specifications ..................................................... 5 3. Dimensions ......................................................... 9 4. Refrigeration Cy cle Diagram ........................... 10 5. Block Di agram .................... ...

  • Panasonic CU-5E36QBU - page 3

    3 CAUT ION WA RNI NG WA RNI NG 1. Safety Precautions  Read the following “SAFET Y PRECAUTIONS” carefully bef ore perform any servicing.  Electrical work must be installed or serviced by a licens ed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installe d.  The caution items stated here ...

  • Panasonic CU-5E36QBU - page 4

    4 CAUT ION 18. For R410A models, when connecting the piping, do not use any existing (R22) pipes and flare nuts. Using such same may cause abnormally high pressure in the refrigeration cy cle (piping), and possibly result in explosion and injury. Use only R410A materials. Thickness of copper pipes used with R410A must be more than 1/32" (0.8mm ...

  • Panasonic CU-5E36QBU - page 5

    5 2. Specifications Item Unit OUTDOOR UNIT Indoor Unit Combination 2.0kW + 2.0kW + 2.0kW + 2.0kW + 2.5kW Power Source 1 Phase, 208-230V, 60Hz (Power supply from outdoor unit) Cooling Operation Capacity kW 10.56 (2.9 ~ 11.5) BTU/h 36000 (9900 ~ 39000) Electrical Data Running Current A 19.0 - 17.2 Power Input kW 3.75 (0.55 ~ 3.86) EER W/W 2.82 (5.27 ...

  • Panasonic CU-5E36QBU - page 6

    6 Item Unit OUTDOOR UNIT Dry Bulb Wet Bulb Indoor Operation Range Cooling Maximum °C (°F) 32 (89.6) 23 (73.4) Minimum °C (°F) 16 (60.8) 11 (51.8) Heating Maximum °C (°F) 30 (86.0) — Minimum °C (°F) 16 (60.8) — Outdoor Operation Range Cooling Maximum °C (°F) 46 (114.8) 26 (78.8) Minimum °C (°F) -10 (14.0) — Heating Maximum °C (°F ...

  • Panasonic CU-5E36QBU - page 7

    7  Multi Split Combination Possibility: o A single outdoor unit enables air con ditioning of up to five separate rooms. ...

  • Panasonic CU-5E36QBU - page 8

    8  Indoor Unit : CS-ME7QKUA, CS-E9NKUAW, CS-E12NKUA W, CS-E18NKUA, CS-E24NKUA  Outdoor Unit : CU-5E36QB U 5 Room 4 Room 3 Room 2 Room 1 Room Indoor Unit Capacity (kW) Total Indoor Capacity (kW) Indoor Unit Capacity (kW) Total Indoor Capacity (kW) Indoor Unit Capacity (kW) Total Indoor Capacity (kW) Indoor Unit Capacity (kW) Total Indoor Capac ...

  • Panasonic CU-5E36QBU - page 9

    9 3. Dimensions ...

  • Panasonic CU-5E36QBU - page 10

    10 4. Refrigeration Cycle Diagram ...

  • Panasonic CU-5E36QBU - page 11

    11 5. Block Diagram ...

  • Panasonic CU-5E36QBU - page 12

    12 6. Wiring Connection Diagram R e s i s t a n c e o f C o m p r e s s o r Wi n di n g s CONNECTI ON U- V U- W V- W 0.72 0.73 0.71 5KD240XA L21 ( Ω ) CONTROL BOARD Y/G BL BL 1 2 3 W W BL R 1 CN-COM (WHITE) FUSE 401 (30A 250V) ACL1 (BLACK) ACN1 (WH ITE) FG1 (GRE EN) FG2 (GRE EN) DCP ( RED ) DCN ( BLACK ) CN-BLK (BLACK) REACTOR GRY RY -PW R SMOOTH ...

  • Panasonic CU-5E36QBU - page 13

    13 7. Electronic Circuit Diagram ...

  • Panasonic CU-5E36QBU - page 14

    14 8. Printed Circuit Board 8.1 Main Printed Circuit Board ...

  • Panasonic CU-5E36QBU - page 15

    15 8.2 Noise Filter Printed Circuit Board 8.3 Display Printed Circuit Board ...

  • Panasonic CU-5E36QBU - page 16

    16 9. Installation Information 9.1 Check Points ...

  • Panasonic CU-5E36QBU - page 17

    17 10. Installation Instruction 10.1 Select The Best Location  If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radia tion from the condenser is not obstru cted.  There should not be any animal or plant whi ch could be affected by hot air discha rged.  Keep the spaces indicated by arro ws from wa ...

  • Panasonic CU-5E36QBU - page 18

    18 Outdoor Unit Installation Guidelines  Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follo w the installation guidelines below.  For any of the below installation patterns, the wall height on the exhaust side should be 47-1/4" (1200 mm) or less. 10.2 Install The Outdoor Unit  After sele ...

  • Panasonic CU-5E36QBU - page 19

    19 CUTTING AND FLA RING THE PIPING 1. Please cut using pipe cutter and then re move the burrs. 2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be ca used. Turn the piping end down to avoid the metal powder e ntering the pipe. 3. Please make flare after inserting the flare nut onto the copper pip es. 10.4 Evacuation Of ...

  • Panasonic CU-5E36QBU - page 20

    20 10.5 Connect The Cable To The Outdoor Unit 1. Remove Plugs. 2. Fix the conduit conne ctors to the knock out holes with lock-nuts, then secure them. 3. Connecting wire between indoor unit and outdoor unit should be UL listed or CSA approved 4 conductor wires minimum A WG16 in accordance with local electric codes. 4. Wire Connection to the power s ...

  • Panasonic CU-5E36QBU - page 21

    21 10.7 Disposal Of Outdoor Unit Drain Water  If a drain elbow is used, the unit should b e plac ed on a stand which is taller than 1-31/32" (50 mm).  If the unit is used in an area where temperature falls below 32°F (0°C) for 2 or 3 days in succession, it is recommended not to use a drain elbow, for the drain water freezes and the fan ...

  • Panasonic CU-5E36QBU - page 22

    22 11. Operation Control 11.1 Cooling Operation 11.1.1 Outdoor fan control  When cooling operation is enabled, based on outdoor am bient temperature, fan motor control will be adjusted according to figure below: 11.1.2 Annual Cooling control  This control is to enable cooling operation when outdoor am bient temperature is low.  Control sta ...

  • Panasonic CU-5E36QBU - page 23

    23 11.2 Heating Operation 11.2.1 Outdoor fan control  When heating operation is enabled, based on outdoor ambi ent temperature, fan motor control will be adjusted according to figure below for Heating ov erload control: 11.2.2 Heating Room Temp Sampling Control  To improve the judgment accuracy, indoor ro om temp erature sampling starts when ...

  • Panasonic CU-5E36QBU - page 24

    24 12. Simultaneous Operation Control  Operation modes which can be sel ected using the remote control unit: o Automatic, Cooling, Dry, Heating and e-ion operation mode.  Types of operation modes which can be performed simultaneously o Cooling operation and Cooling, Dry o r e-ion operation. o Heating operation and Heating ope ration.  Type ...

  • Panasonic CU-5E36QBU - page 25

    25 13. Protection Control 13.1 Freeze Prevention control (Cool)  When received freeze prevention signal from indoor uni t, the compressor frequency changes accordi ng to indoor heat exchanger temperature.  When indoor unit request capability OFF due to freeze condition, immediately the capability supply to targeted indoor unit stops. 13.2 Dew ...

  • Panasonic CU-5E36QBU - page 26

    26 13.5 Cooling overload control (Cool)  This control detect outdoor pipe tempe rature and perform the compressor frequ ency restriction during coolin g operation. 13.6 Heating overload control (Heat)  This control detect indoor pipe tempe rature and perfor m the compressor freque ncy restriction during heating operation.  This control det ...

  • Panasonic CU-5E36QBU - page 27

    27 13.8 Deice Control  When outdoor pipe temperature and out door air temperature is low, deice operat ion starts where indoor fan motor and outdoor fa n motor stop, indoor unit h orizontal vane clo se and operation LED blink with compressor ON. 13.9 Time Delay Safety Control (Restart Control)  The compressor will not restart within three min ...

  • Panasonic CU-5E36QBU - page 28

    28  DC peak current cont rol o When IPMDC current exceeds set value of 30.0 ± 3.0 A, the compressor will stop. o If the DC peak current detec ted within 30 seconds after operation starts, compressor will restart after 1 minute. o If the DC peak current detec ted 30 seconds or more after operation starts, compressor will restart after 2 minutes. ...

  • Panasonic CU-5E36QBU - page 29

    29 14. Servicing Mode 14.1.1 Pump down operation (SW1)  Operate the pump down proce ss according to the following procedu re. o Confirm the valve on the li quid side and gas si de are open. o Press PUMP DOWN button (SW1) on t he Service PCB inside the outdoor unit for more than 5 se conds. Pump down (cooling) operation is performed for 15 mi nut ...

  • Panasonic CU-5E36QBU - page 30

    30 14.1.3 Wiring Error Check  The unit capable to correct the wiring error automatica lly by following procedures. o Confirm the valve on the liquid side and gas si de is open. o Press WIRING CHECK button (SW3 ) on the Service PCB inside the outdoor unit for more than 10 seconds to start wiring check operation. o Wiring check proce ss will compl ...

  • Panasonic CU-5E36QBU - page 31

    31 15. T roubleshooting Guide 15.1 Self Diagnosis Function  The display screen of wireless remote control unit an d the self-di agnosis LEDs (green ) on the outdoor printed circuit board in the outdoor unit can be used to identify the location of the problem. Refer to the table below to identify and solve the cau se of the problem, and then re - ...

  • Panasonic CU-5E36QBU - page 32

    32 ...

  • Panasonic CU-5E36QBU - page 33

    33 ...

  • Panasonic CU-5E36QBU - page 34

    34 WA RNI NG 16. Disassembly and Assembly Instructions High voltages are generated in the electrical parts area by the capa citor. Ensure t hat the capacitor has discharged sufficientl y before proceeding with repair work. Failure to heed this c aution may result in electric shocks. 16.1 Outdoor Unit Removal Procedure Caution! When handling electro ...

  • Panasonic CU-5E36QBU - page 35

    35 3. Remove the particular plate (rem ove the 3 screws). Fig. 3 4. Remove the particular plate (rem ove the 8 screws). Fig. 4 16.1.3 Removing the Cabinet Front Plate 5. Remove the cabinet front plate (remove the 7 screws). Fig. 5 ...

  • Panasonic CU-5E36QBU - page 36

    36 16.1.4 Removing the Control P.C. Board 6. Remove the cover by release the screw. Fig. 6 7. Disconnect the connectors (lead wires of the compressor, senso rs, and others). 8. Release the Control P.C. Board tab to remove the Control P.C. Board. Fig. 7 16.1.5 Removing the Propeller Fan and Fan Motor 9. Remove the propeller fan by removing t he nut ...

  • Panasonic CU-5E36QBU - page 37

    37 17. T echnical Data 17.1 Operation Characteristics 17.1.1 One Indoor Unit Operation  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz A) Indoor unit capacity: Cooling (2.0: CS -ME7QKUA), servi ce mode frequency ...

  • Panasonic CU-5E36QBU - page 38

    38  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz B) Indoor unit capacity: Cooling (2.5: CS -E9NKUAW), service mode frequency = 20 Hz ...

  • Panasonic CU-5E36QBU - page 39

    39  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz C) Indoor unit capacity: Cooling (3.2: CS -E12 NKUAW), service mode frequency = 34 Hz ...

  • Panasonic CU-5E36QBU - page 40

    40  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz D) Indoor unit capacity: Cooling (5.0: CS-E18 NKUA), service mode frequency = 49 Hz ...

  • Panasonic CU-5E36QBU - page 41

    41  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz A) Indoor unit capacity: Heating (2.0: CS -ME7QK UA), service mode frequency = 39 Hz ...

  • Panasonic CU-5E36QBU - page 42

    42  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz B) Indoor unit capacity: Heating (2.5: CS -E9NKUAW), service mode frequency = 39 Hz ...

  • Panasonic CU-5E36QBU - page 43

    43  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz C) Indoor unit capacity: Heating (3.2: CS -E12 NKUAW), service mode frequency = 47 Hz ...

  • Panasonic CU-5E36QBU - page 44

    44  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz D) Indoor unit capacity: Heating (5.0: CS -E18 NKUA), service mode frequency = 55 Hz ...

  • Panasonic CU-5E36QBU - page 45

    45 17.1.2 Two Indoor Unit Operation  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz A) Indoor unit capacity: Cooling (2.0 + 2.5: CS-ME7QKUA + CS-E 9NKUAW), serv ice mode frequency = 49 Hz ...

  • Panasonic CU-5E36QBU - page 46

    46  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz B) Indoor unit capacity: Cooling (2.0 + 3.2: CS-ME7 QKUA + CS-E 12NKUAW), servic e mode f requency = 49 Hz ...

  • Panasonic CU-5E36QBU - page 47

    47  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz C) Indoor unit capacity: Cooling (2.0 + 5.0: CS-ME7 QKUA + CS-E18NKUA), se rvic e mode frequency = 51 Hz ...

  • Panasonic CU-5E36QBU - page 48

    48  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz D) Indoor unit capacity: Cooling (2.5 + 3.2: CS-E 9NKUAW + CS-E12NKUAW), service mo de frequency = 49 Hz ...

  • Panasonic CU-5E36QBU - page 49

    49  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz E) Indoor unit capacity: Cooling (2.5 + 5.0: CS-E 9NK UAW + CS-E18NKUA), service mode freque ncy = 51 Hz ...

  • Panasonic CU-5E36QBU - page 50

    50  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz F) Indoor unit capacity: Co oling (3.2 + 5.0: CS-E 12NKUAW + CS-E 18NKUA), service mode frequency = 5 3 Hz ...

  • Panasonic CU-5E36QBU - page 51

    51  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz A) Indoor unit capacity: Heating (2.0 + 2.5: CS-ME7 QKUA + CS-E 9NKUAW), serv ice mode frequency = 58 Hz ...

  • Panasonic CU-5E36QBU - page 52

    52  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz B) Indoor unit capacity: Heating (2.0 + 3.2: CS-ME7 QKUA + CS-E 12NKUAW), servic e mode f requency = 64 Hz ...

  • Panasonic CU-5E36QBU - page 53

    53  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz C) Indoor unit capacity: Heating (2.0 + 5 .0: CS-ME7 QKUA + CS-E18NKUA), serv ic e mode frequency = 68 Hz ...

  • Panasonic CU-5E36QBU - page 54

    54  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz D) Indoor unit capacity: Heating (2.5 + 3 .2: CS-E 9NKUAW + CS-E12NKUAW), servi ce mode frequency = 64 Hz ...

  • Panasonic CU-5E36QBU - page 55

    55  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz E) Indoor unit capacity: Heating (2.5 + 5.0: CS-E 9NK UAW + CS-E18NKUA), service mo de frequency = 68 Hz ...

  • Panasonic CU-5E36QBU - page 56

    56  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz F) Indoor unit capacity: He ating (3.2 + 5.0: CS-E12N KUAW + CS-E18NKUA), service mode f requency = 73 Hz ...

  • Panasonic CU-5E36QBU - page 57

    57 17.1.3 Three Indoor Unit Operation  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz A) Indoor unit capacity: Cooling (2.0 + 2.5 + 3.2: CS-ME7QKUA + CS-E 9NKUAW + CS-E12 NKUAW), service mode frequency = 55 Hz ...

  • Panasonic CU-5E36QBU - page 58

    58  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz B) Indoor unit capacity: Cooling (2.0 + 2.5 + 5.0: CS-ME7QKUA + CS-E 9NKUAW + CS-E18NKUA), service mode frequency = 57 Hz ...

  • Panasonic CU-5E36QBU - page 59

    59  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz C) Indoor unit capacity: Cooling (2.0 + 3.2 + 5.0: CS-ME7QKUA + CS-E 12NKUA W + CS-E18NKUA), service mode frequency = 59 Hz ...

  • Panasonic CU-5E36QBU - page 60

    60  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz D) Indoor unit capacity: Cooling (2.5 + 3.2 + 5.0: CS-E9NKUAW + CS-E 12NK UAW + CS-E18NKUA), service mode frequency = 59 Hz ...

  • Panasonic CU-5E36QBU - page 61

    61  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz A) Indoor unit capacity: Heating (2.0 + 2.5 + 3.2: CS-ME7QKUA + CS-E 9NKUAW + CS-E12NKUA W), service mode frequency = 77 Hz ...

  • Panasonic CU-5E36QBU - page 62

    62  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz B) Indoor unit capacity: Heating (2.0 + 2.5 + 5.0: CS-ME7QKUA + CS-E 9NKUAW + CS-E18NKUA), service mode frequency = 77 Hz ...

  • Panasonic CU-5E36QBU - page 63

    63  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz C) Indoor unit capacity: Heating (2.0 + 3 .2 + 5.0: CS-ME7QKUA + CS-E 12NKU AW + CS-E18NKUA), service mode frequency = 82 Hz ...

  • Panasonic CU-5E36QBU - page 64

    64  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz D) Indoor unit capacity: Heating (2.5 + 3 .2 + 5.0: CS-E9NKUAW + CS-E 12NKU AW + CS-E18NKUA ), service mode frequency = 82 Hz ...

  • Panasonic CU-5E36QBU - page 65

    65 17.1.4 Four Indoor Unit Operation  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz A) Indoor unit capacity: Cooling (2.0 + 2.5 + 3.2 + 5.0: CS-ME7QKUA + CS-E9NKUA W + CS-E12NKUAW + CS-E18NKUA), service mode fre ...

  • Panasonic CU-5E36QBU - page 66

    66  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz A) Indoor unit capacity: Heating (2.0 + 2.5 + 3.2 + 5.0: CS-ME7QKUA + CS-E9NKUAW + CS-E12NK UAW + CS-E18NKUA), service mode freq uency = 86 Hz ...

  • Panasonic CU-5E36QBU - page 67

    67 17.1.5 Five Indoor Unit Operation  Cooling Characteristic [Condition] Room temperature: 80.06° F ( 26.7°C) (DBT), 66.92°F (19.4°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz A) Indoor unit capacity: Cooling (2.0 + 2.5 + 3.2 + 3. 2 + 5.0: CS-ME7QKUA + CS-E 9NKUAW + CS-E12NKUAW + CS-E12NKUAW + CS -E18N ...

  • Panasonic CU-5E36QBU - page 68

    68  Heating Characteristic [Condition] Room temperature: 69.98° F ( 21.1°C) (DBT), 60.08°F (15.6°C) (WBT) Operation condition: High fan speed Piping Length: 7.5m (24.6 ft) 230V 60Hz A) Indoor unit capacity: Heating (2.0 + 2.5 + 3.2 + 3. 2 + 5.0: CS-ME7QKUA + CS-E 9NK UAW + CS-E12NKUAW + CS-E12NKUAW + CS -E18NKUA), se rvice mode frequency = 9 ...

  • Panasonic CU-5E36QBU - page 69

    69 18. Exploded V iew and Replacement Parts List Note The above exploded view is for the purp os e of parts disassembly and replacement. The non-numbered pa rts are not kept as standard service parts. ...

  • Panasonic CU-5E36QBU - page 70

    70 SAFETY REF.NO. DESCRIPTION & NAME QTY. CU-5E36QBU REM ARK 1 CHASSIS ASSY 1 CWD52K1364A 2 SOUND PROOF BOARD 1 CWH151367 3 FAN MOTOR BRACKET 1 CWD54K1081 4 SCREW-BRACKET FAN MOTOR 2 CWH551217 5 CONDENSER COMPLETE 1 CWB32C3961 6 FAN MOTOR 1 L6CBYYYL0116 O 7 SCREW-FAN MOTOR MOUNT 4 CWH551323 8 PROPELLER FAN ASSY 1 CWH03K1075 9 NUT 1 CWH561092 10 ...

  • Panasonic CU-5E36QBU - page 71

    71 SAFETY REF.NO. DESCRIPTION & NAME QTY. CU-5E36QBU REM ARK 61 INSTALLATION I NSTRUCTION 1 CWF616290 62 INSTALLATION I NSTRUCTION 1 CWF616291 74 ACCESSORY CO. (DRAIN ELBOW) 1 CWG87C900 78 TUBE ASS’Y (LIQUID SIDE) 1 CWT029390 79 MANIFOLD TUBE ASS’Y (GAS SIDE) 1 CWT029391 80 BAG 1 CWG861520 81 BASE BOARD-COMPLETE 1 CWG62C1172 82 SHOCK ABSOR ...

メーカー Panasonic カテゴリー Air Conditioner

Panasonic CU-5E36QBUのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- CU-5E36QBUの取扱説明書
- Panasonicの製品カード
- パンフレット
- またはPanasonic CU-5E36QBUの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Panasonic CU-5E36QBUの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Panasonic CU-5E36QBUの取り付け説明書、サービスマニュアル、簡易説明書、またはPanasonic CU-5E36QBUのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Panasonic CU-5E36QBUの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Panasonic CU-5E36QBUデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがPanasonic CU-5E36QBUを使用するのを助ける技術的文書のことです。説明書は通常、全てのPanasonic CU-5E36QBUユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Panasonicの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Panasonic CU-5E36QBUの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははPanasonic CU-5E36QBUの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Panasonic CU-5E36QBUに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Panasonic CU-5E36QBUデバイスの基本機能を使うにあたってのヒント。 Panasonic CU-5E36QBUのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Panasonic CU-5E36QBUに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるPanasonic CU-5E36QBUのメーカー/サービスへの連絡先に関する情報。

Panasonic CU-5E36QBUについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもPanasonic CU-5E36QBUの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがPanasonic CU-5E36QBUで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)